Daikin D2C20ND028A5AA Скачать руководство пользователя страница 21

4 Installation

Installation manual

21

D2C20ND0 D2C24ND035A5AA
Wall-mounted condensing boiler
3P469346-10J – 2018.05

a

c

d

e

L

b

a

90° elbow 60 mm

b

Extension 60 mm

Optional:

c

90° elbow 60 mm

d

45° elbow 60 mm

e

Extension 60 mm
L= 250-500-1000-1500-2000 mm

Type B33 (open flue system)

The  multi  served  chimnet  is  a  system  that  is  a  part  of  the  building
and has a separate CE marking. The connection between the boiler
and the shaft must be obtained via Daikin.

b

c

a

d

L

a

B33 flue kit

Optional:

b

90° elbow 60 mm

c

45° elbow 60 mm

d

Extension 60 mm
L = 500 mm

Flue parts order codes

Required flue kits and/or additional parts can be ordered from Daikin
with the order codes given in the table below:

Flue part

Order code

Wall terminal kit 60/100 (C13x)

DRWTER60100AA

Wall terminal kit 80/125 (C13x)

EKFGW6359

Flue part

Order code

Roof terminal kit 60/100 (C33x)

EKFGP6837

Roof terminal kit 80/125 (C33x)

EKFGP6864

Tee 60/100 with measurement point

EKFGP4667

90° elbow 60/100 (boiler outlet)

DRMEEA60100BA

90° elbow 60/100

EKFGP4660

90° elbow 80/125

EKFGP4810

45° elbow 60/100

EKFGP4661

45° elbow 80/125

EKFGP4811

30° elbow 60/100

EKFGP4664

30° elbow 80/125

EKFGP4814

Extension duct 60/100

500 mm

EKFGP4651

1000 mm

EKFGP4652

Extension duct 80/125

500 mm

EKFGP4801

1000 mm

EKFGP4802

Tile roof outlet kit 60/100

18°/22°

EKFGS0518

23°/27°

EKFGS0519

25°/45°

EKFGP7910

43°/47°

EKFGS0523

48°/52°

EKFGS0524

53°/57

EKFGS0525

Tile roof outlet kit 80/125

18°/22°

EKFGT6300

23°/27°

EKFGT6301

25°/45°

EKFGP7909

43°/47°

EKFGT6305

48°/52°

EKFGT6306

53°/57°

EKFGT6307

Flat roof outlet kit

60/100

EKFGP6940

80/125

EKFGW5333

Wall bracket

DN.100

EKFGP4631

DN.125

EKFGP4481

60/100 to 80/125 adapter

DRDECO80125BA

Tee flex boiler connection set

100 mm

EKFGP6368

130 mm

EKFGP6215

Flex + support elbow

60/100

EKFGP6354

60/130

EKFGS0257

Chimney connection

60/100

EKFGP4678

80/125

EKFGS4828

Roof terminal kit 80 mm

EKFGP6864

90° elbow 80 mm

EKFGW4085

45° elbow 80 mm

EKFGW4086

Extension duct 80 mm

500 mm

EKFGW4001

1000 mm

EKFGW4002

2000 mm

EKFGW4004

60/100 to 80/80 adapter

DRDECOP8080BA

Air intake 80 mm (C53 kit)

EKFGV1102

Air intake 80 mm (C83 kit)

EKFGV1101

Flex kit PP DN.80 (C93 kit)

EKFGP2520

Flex kit PP DN.60/80 (C93 kit)

EKFGP1856

Extension flex PP 80 mm

10 m

EKFGP6340

15 m

EKFGP6344

25 m

EKFGP6341

50 m

EKFGP6342

Connector flex - flex PP 80

EKFGP6324

Spacer PP 80 to 100 mm

EKFGP6333

Содержание D2C20ND028A5AA

Страница 1: ...Installation manual Wall mounted condensing boiler English Manuel d installation Chaudi re murale condensation Fran ais Installation manual Wall mounted condensing boiler D2C20ND028A5AA D2C24ND035A5AA...

Страница 2: ...tiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lie...

Страница 3: ...commission the domestic hot water 25 6 Hand over to the user 25 Disposal Old units must be appropriately disposed of in accordance with local and national regulations The components are easy to separa...

Страница 4: ...ualified person shall explain the operating principles and the use of the unit to the user The user is not allowed to perform any modifications maintenance or repairs on the unit unless otherwise stat...

Страница 5: ...llation Automatic air vents There are two air vents one on the pump other on the heat exchanger They help discharging the air inside the installation and heating circuit to avoid air traps and consequ...

Страница 6: ...vessel 10 litres d Gas valve e Heat exchanger f 3 way valve stepper motor g Domestic hot water temperature sensor h Plate heat exchanger i Safety valve 3 bar j Condensate trap k Ignition transformer...

Страница 7: ...min max m h 0 51 2 04 0 51 2 45 Natural Gas G25 Consumption min max m h 0 59 2 35 0 59 2 85 LPG G31 Consumption min max m h 0 2 0 98 0 2 1 19 Combustion products mass flow rate min max G20 g s 2 2 12...

Страница 8: ...60 C return temperature at heater inlet and 80 C flow temperature at heater outlet b Low temperature means for condensing boilers 30 C for low temperature boilers 37 C and for other heaters 50 C retur...

Страница 9: ...room or compartment it does not require a dedicated ventilation for combustion air If however installed in a room containing a bath or a shower then particular reference is drawn to the current I E E...

Страница 10: ...3 m 1 5 bar h h System water height m p System charge pressure bar According to the graph below there is no need to install an additional expansion vessel for the systems with a water volume in the ar...

Страница 11: ...central heating circuit 0 0 100 200 300 400 500 600 700 800 200 400 600 800 1000 1200 1400 1600 1800 A mbar B l h A Residual pump lift mbar B Flow l h 4 8 Connections NOTICE During installation do no...

Страница 12: ...onger than 1 5 metres The safety valve piping should be connected to a water outlet with an additional hose or piping This outlet should not be installed in places where there is risk of freezing nor...

Страница 13: ...b a L N a b WARNING Do not interchange the supply conductors L and the neutral conductor N DANGER Do not use gas and water pipes for earthing purposes and ensure that they have not been used for this...

Страница 14: ...C20ND028A5AA D2C24ND035A5AA Wall mounted condensing boiler 3P469346 10J 2018 05 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing...

Страница 15: ...temperature sensor Ext1 X8 BCC Boiler Chip Card Ext2 X10 Personal computer production interface Ext3 X1M Daikin room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1...

Страница 16: ...The boiler must be installed so that the terminal is exposed to external air Position of the terminal must allow the free passage of air across it at all times Pluming may occur at the flue terminal P...

Страница 17: ...flue length value Flue length determination Flue duct length L is measured from lip of the elbow to end of the flue terminal L a L Flue duct length a Distance of outer lip of terminal to outer wall a...

Страница 18: ...e flex boiler connection set 100 or 130 b Extension 60 mm c Chimney connection 60 100 d Elbow 60 100 90 Optional e 90 elbow 60 100 f 45 elbow 60 100 g Inspection elbow 60 100 h 30 elbow 60 100 i Exten...

Страница 19: ...45 elbow 80 mm 1 0 m 90 elbow 80 mm 2 0 m Subtract equivalent length value of bends from the allowable flue length value Note The air intake length is 3 metres In case of longer air intake use flue o...

Страница 20: ...ular and rough 140 18 2 53 5 Allowable flue length for C93x DN 80 Flex circular and rough 130 11 6 34 1 DN 80 Flex circular and rough 120 4 4 13 0 DN 80 Flex square and rough 140 23 8 69 9 DN 80 Flex...

Страница 21: ...FGP4661 45 elbow 80 125 EKFGP4811 30 elbow 60 100 EKFGP4664 30 elbow 80 125 EKFGP4814 Extension duct 60 100 500 mm EKFGP4651 1000 mm EKFGP4652 Extension duct 80 125 500 mm EKFGP4801 1000 mm EKFGP4802...

Страница 22: ...t the update process When the app finalizes the update the next screen with the current firmware version appears It will take some time before the adapter finalized the firmware update reboot process...

Страница 23: ...e opened Vent the air from the installation with the manual air vent screws on the radiators Make sure screws are tightened after venting 9 If after the venting the pressure decreases below 0 8 bar re...

Страница 24: ...outlet 5 2 Gas air ratio No need to adjust The installer does not have to adjust the gas air ratio because the boiler has an electronic gas adaptive feature 5 3 To check for gas leakage DANGER Before...

Страница 25: ...weeper mode again press Cancel and Menu buttons together five seconds Sweeper mode will be deactivated and boiler will return to normal operation mode Sweeper mode also finishes automatically after 15...

Страница 26: ...e en service de l eau chaude sanitaire 49 6 Remise l utilisateur 49 Mise au rebut Les anciennes unit s doivent tre mises au rebut correctement conform ment aux r glements locaux et nationaux Les compo...

Страница 27: ...r L utilisateur n est pas autoris effectuer une quelconque modification maintenance ou r paration de l unit sauf mention contraire ou demander des tiers non agr s d effectuer de telles actions Sinon l...

Страница 28: ...Purgeurs d air automatiques Il y a deux purgeurs d air un sur la pompe et un autre sur l changeur de chaleur Ils aident d charger l air l int rieur de l installation et du circuit de chauffage afin d...

Страница 29: ...r pas pas de vanne 3 voies g Capteur de temp rature d eau chaude sanitaire h changeur de chaleur plaques i Vanne de s curit 3 bar j Purgeur de condensat k Transformateur d allumage l Capteur de temp r...

Страница 30: ...in max m h 0 51 2 04 0 51 2 45 Consommation de gaz naturel G25 min max m h 0 59 2 35 0 59 2 85 Consommation de GPL G31 min max m h 0 2 0 98 0 2 1 19 D bit de masse de produits de combustion min max G2...

Страница 31: ...de retour de 60 C l entr e du chauffage et une temp rature du d part de 80 C la sortie du chauffage b Une temp rature faible signifie 30 C pour les chaudi res condensation 37 C pour les chaudi res bas...

Страница 32: ...la mesure applicable Reportez vous la section Espacements d installation minimaux la page 32 Si la chaudi re est install e dans une pi ce ou un compartiment une a ration s par e pour l air comburant n...

Страница 33: ...rature de l eau qui circule dans le circuit La d termination de la hauteur d eau du syst me et de la pression de charge du syst me concern e est indiqu e ci dessous h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0...

Страница 34: ...Graphique de rel vement de pompe r siduel Le graphique de rel vement de pompe r siduel montre la quantit de rel vement de pompe mbar qui reste pour le circuit de chauffage central 0 0 100 200 300 400...

Страница 35: ...ges Le circuit de chauffage central doit tre capable de r sister une pression d au moins 6 bar Le branchement crois doit tre privil gi dans les radiateurs d une longueur sup rieure 1 5 m tre La tuyaut...

Страница 36: ...idement Le c ble d alimentation lectrique doit tre au minimum quivalent H05RN F 2451EC57 Conformez vous au point ci dessous lors du c blage au bloc de bornes d alimentation b a L N a b AVERTISSEMENT N...

Страница 37: ...2C24ND035A5AA Chaudi re murale condensation 3P469346 10J 2018 05 4 8 6 Sch ma de c blage DANGER RISQUE D LECTROCUTION D branchez l alimentation lectrique pendant plus de 10 minutes avant d effectuer l...

Страница 38: ...ce pour chaudi re Ext2 X10 Interface de production pour ordinateur personnel Ext3 X1M Thermostat d ambiance Daikin Ext4 X2M Sortie d alimentation ext rieure 230 V c a Ext5 X2M R serv pas en usage X1M...

Страница 39: ...r rapport aux ouvertures pour l a ration doivent tre conformes aux r glementations nationales La chaudi re doit tre install e de mani re exposer le terminal l air externe La position du terminal doit...

Страница 40: ...gment e jusqu 19 9 m tres en r glant le param tre C3 sur 5 Reportez vous aux consignes d entretien pour cette op ration La longueur de ventouse 80 125 peut tre augment e jusqu 99 m tres en r glant le...

Страница 41: ...une valeur de longueur de coudes quivalente de la valeur de longueur de ventouse admissible Syst me de ventouse 80 125 mm Pour augmenter la longueur de conduit de combustion maximale admissible vous p...

Страница 42: ...ion maximale autoris e entre l entr e d air comburant et la sortie de gaz de combustion y compris les pressions du vent 185 Pa pour les mod les D2C T ND028 et D2C T ND035 D bit de masse minimale des p...

Страница 43: ...oivent tre obtenus par l interm diaire de Daikin Dans les unit s de type C83x le flux de condensat n est pas admis dans l unit a b d c d f g L h e a Plaque murale b Rallonge 80 mm c Adaptateur 60 100...

Страница 44: ...yez une valeur de longueur de coudes quivalente de la valeur de longueur de ventouse admissible Type B53 syst me de ventouse ouverte La chaudi re aspire de l air comburant de la pi ce d installation e...

Страница 45: ...54 60 130 EKFGS0257 Raccord de chemin e 60 100 EKFGP4678 80 125 EKFGS4828 Kit de terminal pour toit 80 mm EKFGP6864 Coude 80 mm de 90 EKFGW4085 Coude 80 mm de 45 EKFGW4086 Conduit de rallonge de 80 mm...

Страница 46: ...vous dans l cran d accueil 2 Appuyez sur les r glages partie sup rieure droite de l cran pour afficher l heure et la date de l adaptateur LAN 3 Appuyez sur Heure pour afficher une fen tre de dialogue...

Страница 47: ...8 bar 10 R glez la vanne 8 sur la position arr t D montez la boucle de remplissage si les r glementations locales l exigent 11 V rifiez que le circuit de chauffage central les raccords du circuit en...

Страница 48: ...combustion de la chaudi re 5 2 Rapport gaz air R glage non n cessaire L installateur ne doit pas r gler le rapport gaz air car la chaudi re dispose d une fonctionnalit de gaz adaptatif lectronique 5 3...

Страница 49: ...ouveau les boutons Annuler et Menu appuy s ensemble pendant cinq secondes Le mode ramoneur se d sactive et la chaudi re repasse au mode de fonctionnement normal Le mode ramoneur s arr te aussi automat...

Страница 50: ......

Страница 51: ......

Страница 52: ...MA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr 3P469346 10J 2018 05...

Отзывы: