Troubleshooting for RA Indoor Unit
Si18-525B
336
Troubleshooting
4.5
Shutter Drive Motor / Shutter Limit Switch Abnormality
Remote
Controller
Display
C7
Method of
Malfunction
Detection
The shutter open / close performance is detected by the limit switch attached on its structure. In
this way, the shutter drive motor and the shutter limit switch are checked for failure.
Malfunction
Decision
Conditions
When the shutter is open, the limit switch is closed.
Supposed
Causes
Shutter drive motor defective
Shutter limit switch defective
Shutter itself deformed (warped)
Shutter's sealing material too thick
Detection error by broken relay harness or disconnected connector
Detection error due to defective PCB (2)
Foreign substance in blow port
Troubleshooting
Check No.03
Refer to P.337
Turn off the power.
Check No. 03
Check the limit switch continuity.
Remove such substance.
Replace the limit switch.
Reconnect the connector or
replace the relay harness.
Replace the shutter drive
motor or the PCB (2).
Check the shutter's sealing
material.
Check the shutter for
deformation or its sealing
material.
(Q0410)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Foreign substance in
the shutter structure?
YES
NO
NO
NO
YES
Shutter closed?
NO
Shutter opening itself?
YES
YES
YES
NO
Relay harness
broken or connector
disconnected?
Limit switch on power?
Open the shutter and turn on the
power.
Содержание D-Series
Страница 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Страница 33: ...List of Functions Si18 525B 20 List of Functions ...
Страница 34: ...Si18 525B Specifications 21 Part 2 Specifications 1 Specifications 22 1 1 Cooling Only 22 1 2 Heat Pump 42 ...
Страница 71: ...Specifications Si18 525B 58 Specifications ...
Страница 107: ...Printed Circuit Board Connector Wiring Diagram Si18 525B 94 Printed Circuit Board Connector Wiring Diagram ...
Страница 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Страница 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Страница 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Страница 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Страница 443: ...BP Unit Si18 525B 430 Removal Procedure The clamps are to be kept in stock Step Procedure Points Clamps Q0529 ...
Страница 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Страница 475: ...Si18 525B vi Index ...