
CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions
SiUS121632EA
48
Functions and Control
CTXS, FTXS series
CDXS, FDXS, FVXS series
Refer to Temperature Control on page 37 for details.
2.6
NIGHT SET Mode
Outline
When the OFF TIMER is set, NIGHT SET Mode is automatically activated. NIGHT SET Mode
keeps the airflow rate setting.
Details
NIGHT SET Mode continues operation at the target temperature for the first one hour, then
automatically raises the target temperature slightly in cooling, or lowers it slightly in heating. This
prevents excessive cooling or heating to ensure comfortable sleeping conditions, and also
conserves electricity.
Cooling
Heating
Zone B
Zone A
OFF
ON
Zone C
2.0˚C (3.6˚F)
1.0˚C (1.8˚F)
0.5˚C (0.9˚F)
1.5˚C (2.7˚F)
2.0˚C (3.6˚F)
Room thermistor temperature – target temperature
(R24033)
Zone B
Zone A
OFF
ON
Zone C
1.5˚C (2.7˚F)
Room thermistor temperature – target temperature
0˚C (0˚F)
(R24034)
1.0˚C (1.8˚F)
(R23917)
Target temperature
+0.5˚C (+0.9˚F)
temperature shift
Operation stops
at the set hour
0.5˚C (0.9˚F)
1 hour
TIMER operation
NIGHT SET Mode ON
Target temperature
–2˚C (–3.6˚F)
temperature shift
1 hour
2˚C (3.6˚F)
(R23918)
TIMER operation
NIGHT SET Mode ON