Actuator Check
DAMA-SM-21-003
88
Service Diagnosis
5.5 Inverter Unit Refrigerant System Check
Check No.14
5.6 Rotation Pulse Check on the Outdoor Unit PCB
Check No.16
Outdoor fan motor.
Check if the sinusoidal voltage is generated between pins 1 -3 and 3 - 5 when the fan motor is
manually rotated once.
Applicable for CTX07/09/12
Refrigerant system check
Is the discharge pipe
thermistor disconnected from
the holder?
Check for refrigerant leakage.
See the section on refrigerant
shortage detection.
YES
NO
Reconnect the thermistor.
Replace the refrigerant.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
PCB
S70
Free
Free
Phase W
Phase V
Phase U
(R24900)
5
4
3
2
1