Troubleshooting
DAMA-SM-21-003
68
Service Diagnosis
Reference
4.12 Compressor Lock
Error Code
E6
Description
Compressor lock.
Method of Error
Detection
A compressor lock is detected by checking the compressor running condition through the
position detection circuit.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error.
Supposed
Causes
Closed stop valve
Compressor locked
Disconnection of compressor harness
Troubleshooting
Check No.12
Refer to P.86
Stop valve closed?
YES
NO
YES
NO
YES
NO
Open the stop valve.
System shut
down after errors repeated
several times?
Emergency
stop without compressor
running?
Turn off and turn on the power
to restart the system
Check the electronic expansion
valve coil. Go to Check No. 12.
Replace the compressor. /
outdoor unit PCB (main PCB)
Replace the compressor. /
outdoor unit PCB (main PCB)
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
DAMA-SM-21-003 -Inverter Multi Split-CTX Series.book Page 68 Wednesday, September 1, 2021 5:44 PM