9 SEALING ALONG THE PANEL GAP

IMPORTANT NOTE: 

To prevent cabinet “sweating”, apply field

provided insulation tape along all joining surfaces between
the coil, gas furnace, duct work, and panels. See Figure11.

APPLY INSULLATION TAPE

Figure 11

10

DRAIN PIPING WORK

In all cooling applications where condensate overflow may cause
damage, a secondary drain pan must be provided by the installer
and placed under the entire unit with a separate drain line prop-
erly sloped and terminated in an area visible to the owner. This
secondary drain pan can provide extra protection to the area un-
der the unit should the primary drain plug up and overflow. As
expressed in our product warranty, we will not be liable for any
damages, structural or otherwise due to the failure to follow this
installation requirement.
Condensate drain connections are located in the drain pan at the
bottom of the coil/enclosure assembly see Figure 12. Use the fe-
male

 

(¾" FPT) threaded fitting that protrudes outside of the en-

closure for external connections. The connectors required are (¾"
NPT) male, either PVC or metal pipe and must be hand tightened
to a torque of no more than 37 in-lbs, to prevent damage to the
drain pan connection. An insertion depth between .36 to .49 inches
(3-5 turns) should be expected at this torque.

1. Ensure drain pan hole is NOT obstructed.

2. To prevent potential sweating and dripping on to finished

space, it may be necessary to insulate the condensate drain
line located inside the building. Use Armaflex or similar
material.

A secondary condensate drain connection has been provided for
areas where the building codes require it. Use a downward slope
of at least  ¼"  per foot to provide free drainage, or as required by
local code. Provide required support to the drain line to prevent
bowing. If the secondary drain line is required, run the line sepa-
rately from the primary drain and end it where condensate dis-
charge can be easily seen.
Drain port labeled (A) in Figure 12 is the primary drain and con-
densate drain line must be attached to this drain port.
Drain port (B) is for the secondary drain line (if used).

A

B

Figure 12

NOTE:

Water coming from secondary line means the coil primary
drain is plugged and needs immediate attention.

Insulate drain lines located inside the building or above a
finished living space to prevent sweating.

The installation must include a “P” style trap that is located
as close as a practical to the evaporator coil. See Figure 13
for details of a typical condensate line “P” trap.

Trapped lines are required by many local codes. In the ab-
sence of any prevailing local codes, please refer to the re-
quirements listed in the uniform mechanical building code.

A drain trap in a draw-through application prevents air from
being drawn back through the drain line during fan opera-
tion, thus preventing condensate from draining and if con-
nected to a sewer line, to prevent sewer gases from being
drawn into  the airstream during blower operation.

In a blow-through application, the drain trap prevents con-
ditioned air from escaping. It is permissible in this applica-
tion to use a shallow trap design, sometimes referred to as
a running trap. The depth of a running trap (Figure 14)
should be either 1" or a depth that permits unrestricted
condensate drainage without excessive air discharge.

If using copper drain line, solder a short piece of pipe, mini-
mum 6" length, to the connector before installing a drain
fitting. DO NOT over torque the ¾" copper connector to
the plastic drain connection. Using a wet rag or heatsink
material on the short piece to protect the plastic drain pan.

Cased Coil

3" MIN.

POSITIVE LIQUID

SEAL REQUIRED

AT TRAP

Drain

Connection

2" MIN.

Figure 13

Содержание CHPE Series

Страница 1: ...hange in specifications without notice 5151 San Felipe St Suite 500 Houston TX 77056 Index 1 Important Safety Instructions 2 2 Shipping Inspection 3 2 1 Parts 3 2 2 Handling 3 3 Codes Regulations 3 4...

Страница 2: ...n the unit control boxtothebuildingelectrical servicepanel Other methods of ground are permitted if performed in accordance with the National Electric Code NEC American National Standards Institute AN...

Страница 3: ...lity of the installer The manufacturer assumes no responsibility for equipment installed in violation of any codes or regulations The United States Environmental Protection Agency EPA has issued vario...

Страница 4: ...Horizontal Right Application 5 3 Clearances Refrigerant lines must be routed depending on configuration of unit to maintain the required 24 minimum clearance for service Consult all appropriate regula...

Страница 5: ...RETURN DUCTWORK Do not locate the return ductwork in an area that can introduce toxic or objectionable fumes ordors into the ductwork 8 REFRIGERANT PIPING WORK IMPORTANT NOTE Do not handle coil assem...

Страница 6: ...on the outside of the control panel See Figure 7 Remove the control panel The control panel is detached from the front panel by removing the fourn mounting screws located on the four corners of the co...

Страница 7: ...based flux is used it will cause piping corrosion Flux containing fluorine will damage refrigerant oil 8 5 Re assemble the Coil and Controls Once heat from the brazed area has dissipated route com po...

Страница 8: ...port to the drain line to prevent bowing If the secondary drain line is required run the line sepa rately from the primary drain and end it where condensate dis charge can be easily seen Drain port la...

Страница 9: ...ersonal injury or death To avoid property damage personal injury or death due to electrical shock this unit MUST have an uninterrupted unbroken electricalground The electrical ground circuit may consi...

Страница 10: ...former A transformer has been included in the transformer kit with the cased coil This unit is designed to operate on 24 VAC from provided transformer NEVER connect high voltage 120 208 240 VAC to the...

Страница 11: ...Figure 17 FOR 80 UPFLOW FURNACE 21 0 and 24 5 width cabinet CASED COIL TRANSFORMER MOUNTED TO TRANSFORMER BRACKET A Figure 18 11 5 1B INSTALLATION BRACKET B Furnace transformer should be removed from...

Страница 12: ...revent interference with the blower housing NOTE Extreme caution must be taken when installing the trans former to the partition plate and wiring the transformers so as to not damage the furnace contr...

Страница 13: ...e control cover make sure you do not pinch any wires 12 COMFORTNET SYSTEM 12 1 Overview The ComfortNet system is a system that includes a ComfortNet compatible cased coil and outdoor unit with a commu...

Страница 14: ...al components Use the following precautions during cased coil installation and servicing to protect the integrated control module from damage By putting the cased coil the control and the person at th...

Страница 15: ...are displayed a maximum of three times IfFAULTRECALLbuttonis pressedforlongerthan15seconds control goes back to Standby Mode 14 4 Network Troubleshooting The ComfortNet system is a fully communicatin...

Страница 16: ...l l e d a s a n o n co m m u n i ca ti n g tra d i ti o n a l s ys te m Ch e ck co m m u n i ca ti o n s w i ri n g d a ta 1 d a ta 2 w i re s Ch e ck w i re co n n e cti o n s a t te rm i n a l b l...

Страница 17: ...Check for possible short in 115 230 volt and 24 volt circuits Repair as necessary Replace the control board Populate shared data set using memory card Replace circuit board Rewrite data using the corr...

Страница 18: ...ow to use the mode display DISPLAY The display consists of 2 digits DISPLAY BUTTON LAYOUT The display buttons shown can be used to navigate and select items FAULT CODE HISTORY NAVIGATION This mode wil...

Страница 19: ...more than 2 sec Release Fault Recall between 2 to 5 sec Hold Fault Recall for more than 5 sec Flashing Display First Error Code Last Error Code Press Fault Recall for Error Code Press Fault Recall fo...

Страница 20: ...he most up to date wiring NOTE THESE INSTRUCTIONS ARE SPECIFICALLY FOR CHPE MODELS DO NOT ATTEMPT TO APPLY THESE DIAGRAMS TO ANY OTHER MODELS HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPL...

Страница 21: ...a blower unit or in filter grilles in your ceiling or walls The installer of your air conditioner or heat pump can tell you where your filter s are and how to clean or replace them Check your filter s...

Страница 22: ...22 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 23: ...23 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 24: ...ted in all product comments Please fill out the feedback form on the following link https daikincomfort com contact us You can also scan the QR code on the right to be directed to the feedback page Qu...

Отзывы: