Daikin CHPE Series Скачать руководство пользователя страница 17

17

7-SEGMENT LED CODES

TROUBLESHOOTING

EE

No display

(EE display is

EMG mode)

INTERNAL FAULT

• No 24 volt power to PCB

• Blown fuse or circuit breaker

• PCB has an internal fault

  • Manual disconnect switch OFF
  • No 24 volt power to PCB
  • Blown fuse or faulty circuit breaker
  • Control board has internal fault

d0

E_d0

Data Not Yet On Network

(NO NET DATA)

Data not on Network

  • No shared data on the network

d4

E_d4

Invalid Memory Card data 

(INVALID MC DATA)

Invalid Memory Card Data

  • Wrong memory card data

70

E_70

EEV OPEN CKT

EEV disconnection detected

  • Indoor EEV coil not connected
  • Incorrect wiring to EEV

73

E_73

LIQ TEMP FLT

Liquid side thermistor abnormality

  • Open (or) short circuit of the liquid thermistor (X5A)
  • Liquid thermistor reading incorrect
     or values outside the normal range

74

E_74

GAS TEMP FLT

Gas side thermistor abnormality

  • Open (or) short circuit of the gas thermistor (X5A)
  • Gas thermistor reading incorrect
     or values outside the normal range

75

E_75

PRESSURE FLT

Pressure sensor abnormality

  • Open (or) short circuit of the Pressure sensor (X15A)
  • Pressure sensor reading incorrect
     or values outside the normal range

76

E_76

EQUIP COMM LOSS

Outdoor unit - Gas furnance or Blower 

unit comminication error (during 

operation)

  
  • Open communication circuit
  • Incorrect wiring between OD unit, Gas furnace
     or Modular blower
  • No power supply to OD unit, Gas furnace
     or Modular blower

77

E_77

TSTAT ID NO COM

Indoor Unit - Thermostat 

communication error (start-up & 

during operation) 

  
• Incorrect wiring between ID unit and thermostat.
   

The system may have the communication error

    without error code 77 on the indoor PCB.
    Follow section
    14.5 SYSTEM TROUBLESHOOTING

  • Thermostat failure
  • Power interruption (low voltage)

78

E_78

CONNECT EQUIP

Outdoor unit - Gas furnance or Blower 

unit comminication error (Startup 

operation)

  
  • Open communication circuit
  • Incorrect wiring between OD unit, Gas furnace
     or Modular blower
  • No power supply to OD unit, Gas furnace
     or Modular blower

Error 

Code

PCB 

LED Display

ClimateTalk Message

Description

Possible Causes

   • Assure 24 volt power to blower and control board. 
   • Check fuse F2U on control board
   • Check for possible short in 115/230 volt and 24 volt circuits. Repair as necessary.
   • Replace the control board.

  • Populate shared data set using memory card.

  • Replace circuit board
  • Rewrite data using the correct memory card

  • Check Indoor EEV coil connection (PCB and junction connector)
  • Replace EEV coil
  • Check the resistance value of EEV coil (refer service manual)
  • Replace the control board

  • Check the connection to liquid thermistor (PCB and junction connector)
  • Check the resistance value of the thermistor (refer service manual)
  • Replace thermistor
  • Replace the control board

  • Check the connection to gas thermistor (PCB and junction connector)
  • Check the resistance value of the thermistor (refer service manual)
  • Replace thermistor
  • Replace the control board

  • Check the connection to pressure sensor (PCB and junction connector)
  • Check the output voltage of the pressure sensor (refer service manual)
  • Replace pressure sensor
  • Replace the control board

  • Check for cased coil and other unit wiring.
  • Replace the control board
  • Check power supply to OD unit, Gas furnace or Modular blower

  • Check for thermostat and indoor unit wiring
  • Verify the input voltage at the ID unit and thermostat
     

After recovering the system with power supply, TSTAT ID NO COM will continue to be

     displayed on the thermostat within 2 minutes. 
     The error code will be cleared automatically.

  • Replace control board or thermostat
  • Press "LEARN" button on PCB for more than 5 seconds to reestablish network

  • Check for cased coil and other unit wiring.
  • Replace the control board
  • Check power supply to OD unit, Gas furnace or Modular blower

Corrective Actions

On

Normal Operation

--

EE

EMERGENCY MODE

--

d0

DATA NOT ON NETWORK

Data Not Yet On Network

d4

INVALID MEMORY CARD DATA

Invalid Memory Card data

70

EEV DISCONNECTION DETECTED

EEV OPEN CKT

73

LIQUID SIDE THERMISTOR ABNORMALITY

LIQ TEMP FLT

74

GAS SIDE THERMISTOR ABNORMALITY

GAS TEMP FLT

75

PRESSURE SENSOR ABNORMALITY

PRESSURE FLT

76

CASED COIL - OUTDOOR UNIT, GAS FURNACE OR BLOWER UNIT
COMMUNICATION ERROR (DURING OPERATION)

EQUIP COMM LOSS

77

INDOOR UNIT - THERMOSTAT COMMUNICATION ERROR
(STARTUP OPERATION & DURING OPERATION)

TSTAT ID NO COM

78

CASED COIL - OUTDOOR UNIT, GAS FURNACE OR BLOWER UNIT
COMMUNICATION ERROR (STARTUP OPERATION)

CONNECT EQUIP

7 SEGMENT LED 

DISPLAY

DESCRIPTION OF CONDITION

ERROR MESSAGE

Содержание CHPE Series

Страница 1: ...hange in specifications without notice 5151 San Felipe St Suite 500 Houston TX 77056 Index 1 Important Safety Instructions 2 2 Shipping Inspection 3 2 1 Parts 3 2 2 Handling 3 3 Codes Regulations 3 4...

Страница 2: ...n the unit control boxtothebuildingelectrical servicepanel Other methods of ground are permitted if performed in accordance with the National Electric Code NEC American National Standards Institute AN...

Страница 3: ...lity of the installer The manufacturer assumes no responsibility for equipment installed in violation of any codes or regulations The United States Environmental Protection Agency EPA has issued vario...

Страница 4: ...Horizontal Right Application 5 3 Clearances Refrigerant lines must be routed depending on configuration of unit to maintain the required 24 minimum clearance for service Consult all appropriate regula...

Страница 5: ...RETURN DUCTWORK Do not locate the return ductwork in an area that can introduce toxic or objectionable fumes ordors into the ductwork 8 REFRIGERANT PIPING WORK IMPORTANT NOTE Do not handle coil assem...

Страница 6: ...on the outside of the control panel See Figure 7 Remove the control panel The control panel is detached from the front panel by removing the fourn mounting screws located on the four corners of the co...

Страница 7: ...based flux is used it will cause piping corrosion Flux containing fluorine will damage refrigerant oil 8 5 Re assemble the Coil and Controls Once heat from the brazed area has dissipated route com po...

Страница 8: ...port to the drain line to prevent bowing If the secondary drain line is required run the line sepa rately from the primary drain and end it where condensate dis charge can be easily seen Drain port la...

Страница 9: ...ersonal injury or death To avoid property damage personal injury or death due to electrical shock this unit MUST have an uninterrupted unbroken electricalground The electrical ground circuit may consi...

Страница 10: ...former A transformer has been included in the transformer kit with the cased coil This unit is designed to operate on 24 VAC from provided transformer NEVER connect high voltage 120 208 240 VAC to the...

Страница 11: ...Figure 17 FOR 80 UPFLOW FURNACE 21 0 and 24 5 width cabinet CASED COIL TRANSFORMER MOUNTED TO TRANSFORMER BRACKET A Figure 18 11 5 1B INSTALLATION BRACKET B Furnace transformer should be removed from...

Страница 12: ...revent interference with the blower housing NOTE Extreme caution must be taken when installing the trans former to the partition plate and wiring the transformers so as to not damage the furnace contr...

Страница 13: ...e control cover make sure you do not pinch any wires 12 COMFORTNET SYSTEM 12 1 Overview The ComfortNet system is a system that includes a ComfortNet compatible cased coil and outdoor unit with a commu...

Страница 14: ...al components Use the following precautions during cased coil installation and servicing to protect the integrated control module from damage By putting the cased coil the control and the person at th...

Страница 15: ...are displayed a maximum of three times IfFAULTRECALLbuttonis pressedforlongerthan15seconds control goes back to Standby Mode 14 4 Network Troubleshooting The ComfortNet system is a fully communicatin...

Страница 16: ...l l e d a s a n o n co m m u n i ca ti n g tra d i ti o n a l s ys te m Ch e ck co m m u n i ca ti o n s w i ri n g d a ta 1 d a ta 2 w i re s Ch e ck w i re co n n e cti o n s a t te rm i n a l b l...

Страница 17: ...Check for possible short in 115 230 volt and 24 volt circuits Repair as necessary Replace the control board Populate shared data set using memory card Replace circuit board Rewrite data using the corr...

Страница 18: ...ow to use the mode display DISPLAY The display consists of 2 digits DISPLAY BUTTON LAYOUT The display buttons shown can be used to navigate and select items FAULT CODE HISTORY NAVIGATION This mode wil...

Страница 19: ...more than 2 sec Release Fault Recall between 2 to 5 sec Hold Fault Recall for more than 5 sec Flashing Display First Error Code Last Error Code Press Fault Recall for Error Code Press Fault Recall fo...

Страница 20: ...he most up to date wiring NOTE THESE INSTRUCTIONS ARE SPECIFICALLY FOR CHPE MODELS DO NOT ATTEMPT TO APPLY THESE DIAGRAMS TO ANY OTHER MODELS HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPL...

Страница 21: ...a blower unit or in filter grilles in your ceiling or walls The installer of your air conditioner or heat pump can tell you where your filter s are and how to clean or replace them Check your filter s...

Страница 22: ...22 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 23: ...23 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 24: ...ted in all product comments Please fill out the feedback form on the following link https daikincomfort com contact us You can also scan the QR code on the right to be directed to the feedback page Qu...

Отзывы: