17
7-SEGMENT LED CODES
TROUBLESHOOTING
EE
No display
(EE display is
EMG mode)
INTERNAL FAULT
• No 24 volt power to PCB
• Blown fuse or circuit breaker
• PCB has an internal fault
• Manual disconnect switch OFF
• No 24 volt power to PCB
• Blown fuse or faulty circuit breaker
• Control board has internal fault
d0
E_d0
Data Not Yet On Network
(NO NET DATA)
Data not on Network
• No shared data on the network
d4
E_d4
Invalid Memory Card data
(INVALID MC DATA)
Invalid Memory Card Data
• Wrong memory card data
70
E_70
EEV OPEN CKT
EEV disconnection detected
• Indoor EEV coil not connected
• Incorrect wiring to EEV
73
E_73
LIQ TEMP FLT
Liquid side thermistor abnormality
• Open (or) short circuit of the liquid thermistor (X5A)
• Liquid thermistor reading incorrect
or values outside the normal range
74
E_74
GAS TEMP FLT
Gas side thermistor abnormality
• Open (or) short circuit of the gas thermistor (X5A)
• Gas thermistor reading incorrect
or values outside the normal range
75
E_75
PRESSURE FLT
Pressure sensor abnormality
• Open (or) short circuit of the Pressure sensor (X15A)
• Pressure sensor reading incorrect
or values outside the normal range
76
E_76
EQUIP COMM LOSS
Outdoor unit - Gas furnance or Blower
unit comminication error (during
operation)
• Open communication circuit
• Incorrect wiring between OD unit, Gas furnace
or Modular blower
• No power supply to OD unit, Gas furnace
or Modular blower
77
E_77
TSTAT ID NO COM
Indoor Unit - Thermostat
communication error (start-up &
during operation)
• Incorrect wiring between ID unit and thermostat.
The system may have the communication error
without error code 77 on the indoor PCB.
Follow section
14.5 SYSTEM TROUBLESHOOTING
• Thermostat failure
• Power interruption (low voltage)
78
E_78
CONNECT EQUIP
Outdoor unit - Gas furnance or Blower
unit comminication error (Startup
operation)
• Open communication circuit
• Incorrect wiring between OD unit, Gas furnace
or Modular blower
• No power supply to OD unit, Gas furnace
or Modular blower
Error
Code
PCB
LED Display
ClimateTalk Message
Description
Possible Causes
• Assure 24 volt power to blower and control board.
• Check fuse F2U on control board
• Check for possible short in 115/230 volt and 24 volt circuits. Repair as necessary.
• Replace the control board.
• Populate shared data set using memory card.
• Replace circuit board
• Rewrite data using the correct memory card
• Check Indoor EEV coil connection (PCB and junction connector)
• Replace EEV coil
• Check the resistance value of EEV coil (refer service manual)
• Replace the control board
• Check the connection to liquid thermistor (PCB and junction connector)
• Check the resistance value of the thermistor (refer service manual)
• Replace thermistor
• Replace the control board
• Check the connection to gas thermistor (PCB and junction connector)
• Check the resistance value of the thermistor (refer service manual)
• Replace thermistor
• Replace the control board
• Check the connection to pressure sensor (PCB and junction connector)
• Check the output voltage of the pressure sensor (refer service manual)
• Replace pressure sensor
• Replace the control board
• Check for cased coil and other unit wiring.
• Replace the control board
• Check power supply to OD unit, Gas furnace or Modular blower
• Check for thermostat and indoor unit wiring
• Verify the input voltage at the ID unit and thermostat
After recovering the system with power supply, TSTAT ID NO COM will continue to be
displayed on the thermostat within 2 minutes.
The error code will be cleared automatically.
• Replace control board or thermostat
• Press "LEARN" button on PCB for more than 5 seconds to reestablish network
• Check for cased coil and other unit wiring.
• Replace the control board
• Check power supply to OD unit, Gas furnace or Modular blower
Corrective Actions
On
Normal Operation
--
EE
EMERGENCY MODE
--
d0
DATA NOT ON NETWORK
Data Not Yet On Network
d4
INVALID MEMORY CARD DATA
Invalid Memory Card data
70
EEV DISCONNECTION DETECTED
EEV OPEN CKT
73
LIQUID SIDE THERMISTOR ABNORMALITY
LIQ TEMP FLT
74
GAS SIDE THERMISTOR ABNORMALITY
GAS TEMP FLT
75
PRESSURE SENSOR ABNORMALITY
PRESSURE FLT
76
CASED COIL - OUTDOOR UNIT, GAS FURNACE OR BLOWER UNIT
COMMUNICATION ERROR (DURING OPERATION)
EQUIP COMM LOSS
77
INDOOR UNIT - THERMOSTAT COMMUNICATION ERROR
(STARTUP OPERATION & DURING OPERATION)
TSTAT ID NO COM
78
CASED COIL - OUTDOOR UNIT, GAS FURNACE OR BLOWER UNIT
COMMUNICATION ERROR (STARTUP OPERATION)
CONNECT EQUIP
7 SEGMENT LED
DISPLAY
DESCRIPTION OF CONDITION
ERROR MESSAGE