11.3 SAFETY DEVICE

Every installation must include an NEC (USA) or CEC (Canada) ap-
proved overcurrent protection device. Also, check with local or
state codes for any special regional requirements. Protection can
be in the form of fusing or HACR style circuit breakers. The Series
and Rating Plate provides the maximum overcurrent device per-
missible. When using residual current operated circuit breakers,
be sure to use a high-speed type (0.1 second or less) 30mA rated
residual operating current.

NOTE

: Fuses or circuit breakers are to be sized larger than the

equipment MCA but not to exceed the MOP.

11.4 TRANSFORMER INSTALLATION

Measure the power supply to the gas furnace or modular blower.
Selection of correct supply voltage for transformer depends on
measured power supply to gas furnace or modular blower. The
supply voltage must be measured and be in agreement with the
equipment’s unit nameplate power requirements and within the
range shown. 24 VAC power voltage is supplied to EEV cased coil
control board from transformer supply terminals. See Figure 15
For appropriate wiring identification and installation for the cased
coil, refer to the proveid wiring schematic located on the PCB Con-
trol Panel cover.

EEV Cased Coil 24 VAC 
supply voltage

Select single appropriate
power supply

Connect COM to 
field common.

Figure 15

The cased coil PCB must be supplied 24 VAC supply voltage from
an appropriately powered transformer. A transformer has been
included in the transformer kit with the cased coil.

This unit is designed to operate on 24 VAC from provided 
transformer. NEVER connect high voltage (120/208/240 VAC) 
to the cased coil directly or to the cased coil control board. 
Doing so would result in equipment damage and/or personal 
injury or death.
Use designated UL certified transformer included with coil 
accessory kit. Do not alter or modify the transformer. 
Attempting to modify or alter the transformer may result in 
product damage or personal injury.

11.5 HOW TO INSTALL THE TRANSFORMER

Furnace application requires the use of the multi-tap (120/204/
240) VAC to 24 VAC transformer. Appropriate supply voltage for
multi-tap transformer is based on field wiring. Select from the coil
accessory kit the following components:

1. Multi-tap (120/208/240) VAC to 24 VAC transformer.

2. Appropriate PCB transformer bracket (see Table 1).

3. Supplied red/black voltage transformer power wires.

NOTE: 

Based on furnace selection, use the following table to de-

termine appropriate PCB transformer bracket.

Bracket A

Bracket B No Bracket

DM80*

All

X

DM96*

All

X

DM97*

All

X

Gas

DC80*

All

X

Furnace

DC96*

X

DC97*

X

DC96*

21.0"

X

DC97*

24.5"

X

Modular

Blower

MBVC*

All

X

Bracket Select

Mode

Name

Cabinet

Width

17.5"

Table 1

Bracket “A”

Bracket “B”

Figure 16

NOTE: 

Based on furnace or modular blower model, the applicable

bracket and PCB transformer are mounted inside the furnace or
modular blower cabinet. It is recommended to use self tapping
screws to secure the PCB transformer and bracket plate to the
mounting position. See Figures 17 through 23 to determine ap-
propriate location.

Содержание CHPE Series

Страница 1: ...hange in specifications without notice 5151 San Felipe St Suite 500 Houston TX 77056 Index 1 Important Safety Instructions 2 2 Shipping Inspection 3 2 1 Parts 3 2 2 Handling 3 3 Codes Regulations 3 4...

Страница 2: ...n the unit control boxtothebuildingelectrical servicepanel Other methods of ground are permitted if performed in accordance with the National Electric Code NEC American National Standards Institute AN...

Страница 3: ...lity of the installer The manufacturer assumes no responsibility for equipment installed in violation of any codes or regulations The United States Environmental Protection Agency EPA has issued vario...

Страница 4: ...Horizontal Right Application 5 3 Clearances Refrigerant lines must be routed depending on configuration of unit to maintain the required 24 minimum clearance for service Consult all appropriate regula...

Страница 5: ...RETURN DUCTWORK Do not locate the return ductwork in an area that can introduce toxic or objectionable fumes ordors into the ductwork 8 REFRIGERANT PIPING WORK IMPORTANT NOTE Do not handle coil assem...

Страница 6: ...on the outside of the control panel See Figure 7 Remove the control panel The control panel is detached from the front panel by removing the fourn mounting screws located on the four corners of the co...

Страница 7: ...based flux is used it will cause piping corrosion Flux containing fluorine will damage refrigerant oil 8 5 Re assemble the Coil and Controls Once heat from the brazed area has dissipated route com po...

Страница 8: ...port to the drain line to prevent bowing If the secondary drain line is required run the line sepa rately from the primary drain and end it where condensate dis charge can be easily seen Drain port la...

Страница 9: ...ersonal injury or death To avoid property damage personal injury or death due to electrical shock this unit MUST have an uninterrupted unbroken electricalground The electrical ground circuit may consi...

Страница 10: ...former A transformer has been included in the transformer kit with the cased coil This unit is designed to operate on 24 VAC from provided transformer NEVER connect high voltage 120 208 240 VAC to the...

Страница 11: ...Figure 17 FOR 80 UPFLOW FURNACE 21 0 and 24 5 width cabinet CASED COIL TRANSFORMER MOUNTED TO TRANSFORMER BRACKET A Figure 18 11 5 1B INSTALLATION BRACKET B Furnace transformer should be removed from...

Страница 12: ...revent interference with the blower housing NOTE Extreme caution must be taken when installing the trans former to the partition plate and wiring the transformers so as to not damage the furnace contr...

Страница 13: ...e control cover make sure you do not pinch any wires 12 COMFORTNET SYSTEM 12 1 Overview The ComfortNet system is a system that includes a ComfortNet compatible cased coil and outdoor unit with a commu...

Страница 14: ...al components Use the following precautions during cased coil installation and servicing to protect the integrated control module from damage By putting the cased coil the control and the person at th...

Страница 15: ...are displayed a maximum of three times IfFAULTRECALLbuttonis pressedforlongerthan15seconds control goes back to Standby Mode 14 4 Network Troubleshooting The ComfortNet system is a fully communicatin...

Страница 16: ...l l e d a s a n o n co m m u n i ca ti n g tra d i ti o n a l s ys te m Ch e ck co m m u n i ca ti o n s w i ri n g d a ta 1 d a ta 2 w i re s Ch e ck w i re co n n e cti o n s a t te rm i n a l b l...

Страница 17: ...Check for possible short in 115 230 volt and 24 volt circuits Repair as necessary Replace the control board Populate shared data set using memory card Replace circuit board Rewrite data using the corr...

Страница 18: ...ow to use the mode display DISPLAY The display consists of 2 digits DISPLAY BUTTON LAYOUT The display buttons shown can be used to navigate and select items FAULT CODE HISTORY NAVIGATION This mode wil...

Страница 19: ...more than 2 sec Release Fault Recall between 2 to 5 sec Hold Fault Recall for more than 5 sec Flashing Display First Error Code Last Error Code Press Fault Recall for Error Code Press Fault Recall fo...

Страница 20: ...he most up to date wiring NOTE THESE INSTRUCTIONS ARE SPECIFICALLY FOR CHPE MODELS DO NOT ATTEMPT TO APPLY THESE DIAGRAMS TO ANY OTHER MODELS HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPL...

Страница 21: ...a blower unit or in filter grilles in your ceiling or walls The installer of your air conditioner or heat pump can tell you where your filter s are and how to clean or replace them Check your filter s...

Страница 22: ...22 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 23: ...23 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 24: ...ted in all product comments Please fill out the feedback form on the following link https daikincomfort com contact us You can also scan the QR code on the right to be directed to the feedback page Qu...

Отзывы: