BRC2E52C7 / BRC3E52C7
Installation manual
4P368041-1
–
2014.02
18
Field settings
Mode
No.
(Note
1)
FIRST
CODE
NO.
Description of the setting
SECOND CODE NO. (Note 2)
01
02
03
04
10 (20)
0
Filter Contamination -
Heavy/Light Setting for
when "Time to clean the
air filter" icon is shown
(when filter
contamination is heavy
the time to clean the air
filter is to be halved).
Ultra long
life filter
Light
±10.000 hrs.
Heavy
±5.000 hrs.
—
—
Long life
filter
±2.500 hrs.
± 1.250 hrs.
Standard
filter
±200 hrs.
± 100 hrs.
1
Long-life filter type (setting of the filter
sign indication time).
(Change setting when a ultra-long
filter is installed).
Long-life filter
Ultra-long life
filter
—
—
2
Thermostat sensor in the remote
controller.
Use combined
(with indoor
thermistor)
Do not use
Use
exclusively
—
3
Setting for when the filter sign is not
to be displayed.
Display
Do not display
—
—
11 (21)
0
Number of connected SkyAir
simultaneous operation indoor units
(setting for simultaneous operation
system).
Pair
Twin
Triple
Double
twin
12 (22)
1
External On/Off input from outside
(setting for when forced On/Off is to
be operated from somewhere else).
Forced OFF
On/Off
operation
Emergency
Forced
OFF
2
Thermostat differential changeover
(setting for when using a remote
sensor).
1°C
0.5°C
—
—
13 (23)
0
High air outlet velocity (for high
ceiling applications).
h
≤
2.7 m
2.7 m < h
≤
3.0 m
3.0 m <
h
≤
3.5 m
—
1
Selection of airflow direction (setting
for when a kit has been installed that
blocks the airflow).
4-way flow
3-way flow
2-way flow
—
3
Selection of airflow function (setting
for when using a decoration panel at
the outlet).
Equipped
Not equipped
—
—
4
Airflow direction range setting.
Upper
Normal
Lower
—
6
The external static pressure setting
(setting according to the connected
duct resistance).
Normal
High static
pressure
Low static
pressure
—
FHYK: follow the high ceiling setting.
Normal
High ceiling
—
—
15 (25)
3
Drain pump operation with
humidifying.
Equipped
Not equipped
—
—
1c
1
Thermostat sensor used for the
"Auto" operation mode and the
Setback function (room temperature
on detailed display).
Indoor
thermistor
(intake
temperature)
Remote
controller
thermistor
—
—
1c
12
External input B1.
Do not use
Use
—
—
1c
13
External input B2.
Do not use
Use
—
—
1e
2
Setback function.
Do not use
Heat only
Cool only
Cool
and
Heat