13 Configuration

Installer and user reference guide

23

BK+S
Wired remote controller
4P513689-1 – 2018.02

Key card contact logic

Window contact B1

Key card contact B2

Time

Action

Contact closed (window closed)

Contact closed (key card IN)

▪ —

▪ Delay timer<Time<Reset timer

▪ Time>Reset timer

▪ The unit operates normally.

▪ If  the  reset  timer  has  not

expired,  the  unit  returns  to  the
previous  state  before  opening
the contact.

▪ If  the  reset  timer  has  expired,

the  unit  returns  to  the 

"Default

Reset  Setting"

  (see 

"External

input 

interlock 

settings

overview" on page 21

).

Contact closed (window closed)

Contact open (key card OUT)

Time<Delay timer

Normal indoor unit operation.

Contact closed (window closed)

Contact open (key card OUT)

Time>Delay timer

Unit operation is forced off:

▪ Not  possible  to  turn  on/off  the

unit with the controller's ON/OFF
button.

▪ After  the  delay  timer  has

expired, the reset timer will start
counting.

INFORMATION

▪ The  "previous  state"  can  be  the  on/off  state,  operation

mode, cooling setpoint, and heating setpoint.

▪ When using the contacts, the fan speed as well as the

setback  cooling  and  heating  setpoint  can  be  changed
at any time, without losing changes.

▪ The fan speed is stored independently for the two main

operation  modes  (Heating  and  Cooling).  Separate  fan
speed  settings  are  saved  for  Heating  operation  mode
on  the  one  hand,  and  Cooling,  Dry  and  Fan  only
operation mode on the other hand.

▪ When closing the contact, changes made while the key

card  contact  is  open  and  the  delay  timer  has  not
expired (normal operation) will not be NOT saved.

Combination of window contact and key card contact logic

▪ The  window  contact  has  priority  over  the  delay  timer  of  the  key

card 

contact:

When the window contact is opened while the key card contact is
open,  the  delay  timer  will  immediately  expire  if  it  is  still  running.
The  reset  timer  will  immediately  start  counting  or  will  not  reset
when it was already running.

▪ The  reset  timer  functionality  of  the  key  card  contact  has  priority

over  the  window  contact  when  returning  to  the  previous  state:
When the key card contact is opened while the window contact is
open,  the  delay  timer  will  start  running.  When  the  delay  timer
expires  the  reset  timer  will  start  running.  When  the  reset  timer
expires,  the  previous  state  is  updated  to  the  "

Default  Reset

Setting

" state.

Example 1

1

You remove the key card.

Result: 

The  indoor  unit  continues  operating  normally  until  the

delay timer expires.

2

You open the window before the delay timer expires.

Result: 

The indoor unit stops immediately. It is not possible to

turn  the  unit  on  or  off,  the  delay  timer  stops  counting,  and  the
reset timer starts counting.

3

You insert the key card again.

Result: 

An  update  of  the  previous  state  occurs.  The  unit  is

forced off (see 

"Window contact logic" on page 22

).

IF

 the reset timer HAS NOT expired before inserting the key

card, the previous state is the same as the original state
because there was only a change to the original state.

IF

 the reset timer HAS expired before inserting the key card,

the previous state is the "

Default Reset Setting

" state.

4

You close the window.

Result: 

The  unit  reverts  to  the  previous  state.  The  previous

state depends on the expiration of the reset timer.

Example 2

1

You open the window.

Result: 

The unit stops immediately. It is not possible to turn the

unit on or off with the ON/OFF button, and the delay timer does
not start counting.

2

You remove the key card.

Result: 

The delay timer starts counting.

3

You close the window again.

Result: 

There is no change in state. It is as if you never opened

the window.

IF

 the delay timer HAS expired before closing the window, the

reset timer will have started counting. Closing the window has
no influence on the reset timer.

IF

 the delay timer HAS NOT expired before closing the window,

it will expire immediately and the reset timer will start counting.
When the reset timer expires, the previous state is updated to
the "Default Reset Setting" state.

4

You insert the key card again.

Result:

IF

 the reset timer HAS NOT expired before inserting the key

card, the unit returns to the state before the window was
opened (last "on" state);

IF

 the reset timer HAS expired before inserting the key card,

the unit goes to the "Default Reset Setting" state.

Force fan ON

About Force fan ON

Force  fan  ON  allows  you  to  force  fan  operation  of  individual  indoor
units.  In  this  way,  you  can  check  which  indoor  unit  number  was
assigned to which indoor unit.

Содержание BRC1H51W

Страница 1: ...Installer and user reference guide Wired remote controller English Installer and user reference guide Wired remote controller BRC1H51W BRC1H51K BRC1H51S...

Страница 2: ...Information 12 12 4 1 Information screen 12 12 4 2 Information menu 13 13 Configuration 13 13 1 Installer menu 13 13 1 1 About the installer menu 13 13 1 2 Screen settings 13 13 1 3 Status indicator s...

Страница 3: ...ls In places with temperatures 10 C and 50 C In places where the relative humidity is 95 In places where there is machinery that emits electromagnetic waves Electromagnetic waves may disturb the contr...

Страница 4: ...ng with a mobile device for use with the Daikin Control Assistant app Centralised control Indicates that the system is controlled by central control equipment optional accessory and that control of th...

Страница 5: ...g or cooling Dry In this mode the air humidity will be lowered with a minimal temperature decrease The temperature and fan speed are controlled automatically and cannot be controlled by the controller...

Страница 6: ...unit fan will automatically operate until the indoor temperature of the system rises to a certain level When hot air stays under the ceiling and your feet feel cold it is recommended to include a cir...

Страница 7: ...to confirm Result The indoor unit changes its fan speed and the controller returns to the home screen 6 4 Ventilation INFORMATION Ventilation settings can ONLY be made for heat reclaim ventilation un...

Страница 8: ...ntroller only allows for basic operation For advanced operation use the Daikin Control Assistant app 6 5 1 To make a Bluetooth connection Prerequisite You have a mobile device on which the Daikin Cont...

Страница 9: ...nsists of the following stages 1 Determining how you want to route the electrical wiring and nipping away a piece of the rear casing accordingly 2 Mounting the rear casing to the wall 3 Connecting the...

Страница 10: ...included NOTICE When wiring run the wiring away from the power supply wiring in order to avoid receiving electric noise external noise INFORMATION P1 and P2 have no polarity 10 3 2 To connect the ele...

Страница 11: ...ill cause the adapter to go in error The controller gets its power from the indoor unit It will start up as soon as it is connected For the controller to be operable therefore make sure the indoor uni...

Страница 12: ...de c Setpoint temperature Home screen mode is set with remote controller field setting R1 7 Home screen For more information see Remote controller field settings on page 18 Backlight The screen backli...

Страница 13: ...instructions on how to enter the information menu see 13 1 Installer menu on page 13 and Information on page 25 13 Configuration 13 1 Installer menu 13 1 1 About the installer menu In the installer m...

Страница 14: ...ons on how to make field settings see 13 1 4 Field settings on page 14 For an overview of remote controller field settings see Remote controller field settings on page 18 To set status indicator inten...

Страница 15: ...In the field settings tables find the mode numbers that apply to individual indoor units between brackets in the Mode column Second level Setting SW A setting is a settable parameter These are the se...

Страница 16: ...ng component 3 Use and to change the value of that field setting component 4 Press to confirm that value 5 In the first level select to move to the second level 6 In the second level navigate and sele...

Страница 17: ...tenant 02 Thermostat differential if the system contains a remote sensor set the increase decrease increments 1 C 0 5 C 13 23 00 High air outlet velocity set in case of high ceiling applications h 2...

Страница 18: ...ed 1 Standard 1 8 Backlight no operation timer 0 5 seconds 1 10 seconds 2 20 seconds 0 9 Status indicator faintness 0 0 OFF 1 1 2 2 3 3 4 5 5 7 6 9 7 11 8 13 9 15 10 17 11 20 9 10 Backlight faintness...

Страница 19: ...fine groups and or units in the first level and set or release addresses for those groups and or units in the second Address Description First level Group Group A group is a group of indoor units When...

Страница 20: ...utdoor units O U The Group address and AirNet address menu has two levels You define groups and or units in the first level and set and release an address for those groups and or units in the second A...

Страница 21: ...tal input adapter see the installation manual of the digital input adapter In case the digital input adapter does not function properly the external input interlock menu is not available in the instal...

Страница 22: ...ndoor unit s setpoint range and setpoint range limitation 22 C Reset Heat SP Default Reset Setting heating setpoint See indoor unit s setpoint range and setpoint range limitation 22 C INFORMATION When...

Страница 23: ...n the delay timer will start running When the delay timer expires the reset timer will start running When the reset timer expires the previous state is updated to the Default Reset Setting state Examp...

Страница 24: ...a controller displays Then NO status icon The indoor unit connected to that controller is Cooling Heating master a CONSTANT status icon The indoor unit connected to that controller is slave to a Cool...

Страница 25: ...indoor unit is released from its masterhood Result The controllers of all indoor units display a blinking changeover under centralised control icon Information About the information menu In the infor...

Страница 26: ...le cleaning the controller soak the cloth in neutral detergent diluted with water squeeze the cloth tightly and clean the surface Afterwards wipe dry with a dry cloth 14 2 About maintenance When the i...

Страница 27: ...is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin extranet authentication required 16 1 Connection diagram 16 1 1 Typical...

Страница 28: ...eference guide 28 BRC1H51W K S Wired remote controller 4P513689 1 2018 02 Group control controller digital inputs adapter BRP7A5 0 1 2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 16 1 3 Controller DIII central cont...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...4P513689 1 2018 02 Copyright 2018 Daikin...

Отзывы: