13 Configuration

Installer and user reference guide

21

BK+S
Wired remote controller
4P513689-1 – 2018.02

Address

Description

Second level

Define an address for the indoor/outdoor unit.

To SET an address, make sure 

 is selected.

Apply settings.

To RELEASE an address that was previously set, change 

 to 

 and then apply

settings.

External input interlock

About external input interlock

External  input  interlock  allows  for  the  integration  of  key  card  and
window contact logic into the system.

External input interlock is only available in case digital input adapter
BRP7A5*  is  part  of  the  system.  When  the  adapter  is  part  of  the
system:

▪ it is not possible to connect a second (slave) controller, and

▪ the  schedule  function  will  be  disabled  for  as  long  the  adapter  is

connected to the indoor unit.

Make  sure  that  the  digital  input  adapter  and  its  optional  contacts
(window contact B1 and key card contact B2) are correctly installed.
Confirm that the voltage free contact of the digital input adapter is in
the correct position. For instructions on how to install the digital input
adapter,  see  the  installation  manual  of  the  digital  input  adapter.
In  case  the  digital  input  adapter  does  not  function  properly,  the
external  input  interlock  menu  is  not  available  in  the  installer  menu.
In  case  a  centralised  controller  is  additionally  part  of  the  system,
external input interlock is controlled by the centralised controller. The
digital input adapter is then overruled.

To make external input interlock settings

Prerequisite: 

You are in the installer menu.

1

Navigate to the external input interlock menu.

2

Use 

 and 

 to navigate through the menu.

3

Press 

 to select a parameter.

4

With  a  parameter  selected,  use 

  and 

  to  change  that

parameter's value.

5

With  a  parameter  selected,  press 

  to  confirm  the  value  for

that parameter.

6

When  you  are  done  making  settings,  confirm  all  settings  by

selecting 

 and pressing 

.

Result: 

The system will restart and implement any changes made.

INFORMATION

For  an  overview  of  settable  parameters  and  what  they
mean,  see 

"External  input  interlock  settings  overview"  on

page 21

.

External input interlock settings overview

Parameter

Description

Possible values

Default value

B2

 Delay Timer

Timer that starts from as soon the
key card is removed. The unit
continues normal operation until
the timer expires.

0-10 minutes

"1 min"

Содержание BRC1H51W

Страница 1: ...Installer and user reference guide Wired remote controller English Installer and user reference guide Wired remote controller BRC1H51W BRC1H51K BRC1H51S...

Страница 2: ...Information 12 12 4 1 Information screen 12 12 4 2 Information menu 13 13 Configuration 13 13 1 Installer menu 13 13 1 1 About the installer menu 13 13 1 2 Screen settings 13 13 1 3 Status indicator s...

Страница 3: ...ls In places with temperatures 10 C and 50 C In places where the relative humidity is 95 In places where there is machinery that emits electromagnetic waves Electromagnetic waves may disturb the contr...

Страница 4: ...ng with a mobile device for use with the Daikin Control Assistant app Centralised control Indicates that the system is controlled by central control equipment optional accessory and that control of th...

Страница 5: ...g or cooling Dry In this mode the air humidity will be lowered with a minimal temperature decrease The temperature and fan speed are controlled automatically and cannot be controlled by the controller...

Страница 6: ...unit fan will automatically operate until the indoor temperature of the system rises to a certain level When hot air stays under the ceiling and your feet feel cold it is recommended to include a cir...

Страница 7: ...to confirm Result The indoor unit changes its fan speed and the controller returns to the home screen 6 4 Ventilation INFORMATION Ventilation settings can ONLY be made for heat reclaim ventilation un...

Страница 8: ...ntroller only allows for basic operation For advanced operation use the Daikin Control Assistant app 6 5 1 To make a Bluetooth connection Prerequisite You have a mobile device on which the Daikin Cont...

Страница 9: ...nsists of the following stages 1 Determining how you want to route the electrical wiring and nipping away a piece of the rear casing accordingly 2 Mounting the rear casing to the wall 3 Connecting the...

Страница 10: ...included NOTICE When wiring run the wiring away from the power supply wiring in order to avoid receiving electric noise external noise INFORMATION P1 and P2 have no polarity 10 3 2 To connect the ele...

Страница 11: ...ill cause the adapter to go in error The controller gets its power from the indoor unit It will start up as soon as it is connected For the controller to be operable therefore make sure the indoor uni...

Страница 12: ...de c Setpoint temperature Home screen mode is set with remote controller field setting R1 7 Home screen For more information see Remote controller field settings on page 18 Backlight The screen backli...

Страница 13: ...instructions on how to enter the information menu see 13 1 Installer menu on page 13 and Information on page 25 13 Configuration 13 1 Installer menu 13 1 1 About the installer menu In the installer m...

Страница 14: ...ons on how to make field settings see 13 1 4 Field settings on page 14 For an overview of remote controller field settings see Remote controller field settings on page 18 To set status indicator inten...

Страница 15: ...In the field settings tables find the mode numbers that apply to individual indoor units between brackets in the Mode column Second level Setting SW A setting is a settable parameter These are the se...

Страница 16: ...ng component 3 Use and to change the value of that field setting component 4 Press to confirm that value 5 In the first level select to move to the second level 6 In the second level navigate and sele...

Страница 17: ...tenant 02 Thermostat differential if the system contains a remote sensor set the increase decrease increments 1 C 0 5 C 13 23 00 High air outlet velocity set in case of high ceiling applications h 2...

Страница 18: ...ed 1 Standard 1 8 Backlight no operation timer 0 5 seconds 1 10 seconds 2 20 seconds 0 9 Status indicator faintness 0 0 OFF 1 1 2 2 3 3 4 5 5 7 6 9 7 11 8 13 9 15 10 17 11 20 9 10 Backlight faintness...

Страница 19: ...fine groups and or units in the first level and set or release addresses for those groups and or units in the second Address Description First level Group Group A group is a group of indoor units When...

Страница 20: ...utdoor units O U The Group address and AirNet address menu has two levels You define groups and or units in the first level and set and release an address for those groups and or units in the second A...

Страница 21: ...tal input adapter see the installation manual of the digital input adapter In case the digital input adapter does not function properly the external input interlock menu is not available in the instal...

Страница 22: ...ndoor unit s setpoint range and setpoint range limitation 22 C Reset Heat SP Default Reset Setting heating setpoint See indoor unit s setpoint range and setpoint range limitation 22 C INFORMATION When...

Страница 23: ...n the delay timer will start running When the delay timer expires the reset timer will start running When the reset timer expires the previous state is updated to the Default Reset Setting state Examp...

Страница 24: ...a controller displays Then NO status icon The indoor unit connected to that controller is Cooling Heating master a CONSTANT status icon The indoor unit connected to that controller is slave to a Cool...

Страница 25: ...indoor unit is released from its masterhood Result The controllers of all indoor units display a blinking changeover under centralised control icon Information About the information menu In the infor...

Страница 26: ...le cleaning the controller soak the cloth in neutral detergent diluted with water squeeze the cloth tightly and clean the surface Afterwards wipe dry with a dry cloth 14 2 About maintenance When the i...

Страница 27: ...is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin extranet authentication required 16 1 Connection diagram 16 1 1 Typical...

Страница 28: ...eference guide 28 BRC1H51W K S Wired remote controller 4P513689 1 2018 02 Group control controller digital inputs adapter BRP7A5 0 1 2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 16 1 3 Controller DIII central cont...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...4P513689 1 2018 02 Copyright 2018 Daikin...

Отзывы: