BRC1D517
Remote controller
4PW15195-1

Installation manual

5

Mode 

No.

Note 1

FIRST 
CODE 

NO.

Description of setting

SECOND CODE NO. Note 2

01

02

03

04

10(20)

0

Filter Contamination - Heavy/Light
(Setting for spacing time of display time 
to clean air filter)
(Setting for when filter contamination is 
heavy, and spacing time of display time to 
clean air filter is to be halved)

Ultra long 

life filter

Approx. 

10.000 

hrs.

Approx. 

5.000 

hrs.

Long life

 filter

Approx. 

2.500 

hrs.

Approx. 

1.250 

hrs.

Standard 

filter

Approx. 

200 hrs.

Approx. 

100 hrs.

1

Long-life filter type (setting of filter sign indication 
time). (Change setting when ultra-long filter is 
installed)

Long-life 

filter

Ultra-long life 

filter

2

Thermostat sensor in remote controller

Use

Not use

3

Spacing time of display time to clean air filter count 
(setting for when the filter sign is not to be displayed)

Display

Do not 

display

11(21)

0

Setting number of connected Sky Air simultaneous 
operation system indoor units (setting for 
simultaneous operations system)

Pair

Twin

Triple

Double twin

12(22)

1

ON/OFF input from outside (setting for when forced 
ON/OFF is to be operated from outside).

Forced OFF

ON/OFF 

operation

2

Thermostat differential changeover (setting for when 
using remote sensor).

1°C

0.5°C

13(23)

0

High air outlet velocity (for high ceiling applications).

2.7 m

>2.7

3.0 m

>3.0

3.5 m

1

Selection of air flow direction (setting for when a 
blocking pad kit has been installed).

4-way flow

3-way flow

2-way flow

3

Selection of air flow function (setting for when using 
a decoration panel for outlet).

Equipped

Not 

equipped

4

Air flow direction range setting.

Upper

Normal

Lower

6

Setting the external static pressure (setting
 according to the connected duct resistance) 
(for FHYK, follow the high ceiling setting)

Normal

(Normal)

High static 

pressure

(High ceiling)

Low static 

pressure

15(25)

3

Drain pump operation with humidifying.

Equipped

Not 

equipped

Light

Hea

vy

Содержание BRC1D517

Страница 1: ...Remote controller BRC1D517 INSTALLATION MANUAL...

Страница 2: ...1 1 1 4 4 1 2 2 1 2 3 3 S M S S M PCB 1 2 5 5 6 6 P2 P1 P2 P1 1 1 6 2 3 4 5 7 7 SETTING UNIT No GROUP c a 3 1 d e 4 5 6 2 7 b 8 8 1 2 2 2 2...

Страница 3: ...IES COULD RESULT IN ELECTRIC SHOCK SHORT CIRCUIT LEAKS FIRE OR OTHER DAMAGE TO THE EQUIPMENT BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR THE USE WITH THE EQUIPME...

Страница 4: ...controller 4 wired from the rear 5 wired from the top 6 notch the part for the wiring to pass through with nippers etc NOTE When wiring run the wiring away from the power supply wiring in order to avo...

Страница 5: ...ional accessories are mounted on the indoor unit the indoor unit setting may have to be changed Refer to the instruction manual for each optional accessory Refer to figure 7 Procedure Refer to figure...

Страница 6: ...the mode number inside the parentheses is selected indoor units can also be set individually 2 The SECOND CODE number is set to 01 when shipped from the factory 3 Do not make any settings not given in...

Страница 7: ...splay Do not display 11 21 0 Setting number of connected Sky Air simultaneous operation system indoor units setting for simultaneous operations system Pair Twin Triple Double twin 12 22 1 ON OFF input...

Страница 8: ...rmission level setting Level 2 Level 3 1 Leave home function Not permitted Permitted 2 Thermostat sensor in remote controller for limit operation and leave home function only Use Not use Mode No Note...

Страница 9: ...NOTES...

Страница 10: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN15195 1...

Отзывы: