Electrical installation
Installer reference guide
29
BEV2N-A
CO₂ Conveni-Pack: BEV2 unit
4P677928-1 – 2021.10
NOTICE
Be sure to keep the power line and transmission line apart from each other.
Transmission wiring and power supply wiring may cross, but may NOT run parallel.
1
Remove the service cover.
2
Connect the
transmission cable
:
▪
Take the transmission cable from the accessories of the indoor unit and
route the cable through the frames of both units.
▪
Remove the jumper from connector X70A on the indoor unit PCB and
connect the transmission cable to connector X70A.
▪
Connect the cable to connector X2A on the BEV unit PCB.
▪
Fix the cable with a small tie wrap (accessory).
3
Connect the
power supply cable
:
▪
Take the power supply cable from the accessories of the indoor unit and
route the cable through the frames of both units.
▪
Connect the end of the cable with the faston connectors to the indoor unit
terminal.
▪
Connect the other side of the power supply cable to the terminal of the
BEV2 unit.
▪
Fix the cable with a small tie wrap (accessory)
4
Reattach the service cover.
Connection to the indoor unit
X70A
d
c
a
b
g
f
e
a
Transmission cable feed-through hole
b
Transmission cable (indoor unit accessory)
c
Jumper
d
X70A connector
e
Faston connector
f
Power supply feed-through hole
g
Power supply cable