Troubleshooting
SiBE05-722ED
83
Service Diagnosis
4.16 Discharge Pipe Temperature Control
Error Code
F3
Method of Error
Detection
An error is determined with the temperature detected by the discharge pipe thermistor.
Error Decision
Conditions
If the temperature detected by the discharge pipe thermistor rises above
A
°C, the
compressor stops.
The error is cleared when the discharge pipe temperature has dropped below
B
°C.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Troubleshooting
Check No.01
Refer to P.99
Check No.12
Refer to P.101
Check No.14
Refer to P.102
A
(°C)
B
(°C)
(1) above 45 Hz (rising), above 40 Hz (dropping)
110
97
(2) 30 ~ 45 Hz (rising), 25 ~ 40 Hz (dropping)
105
92
(3) below 30 Hz (rising), below 25 Hz (dropping)
99
86
(R15825)
Caution
NG
OK
OK
OK
NG
NG
∗
Discharge pipe thermistor
∗
Outdoor heat exchanger thermistor
∗
Outdoor temperature thermistor
∗
Refrigerant shortage
∗
Four way valve
∗
Water mixed
∗
Stop valve
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant
line.
Check No. 12
Check the electronic
expansion valve.
Replace the
defective
thermistor(s).
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание BA-Series
Страница 12: ...SiBE05 722ED 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 18: ...SiBE05 722ED 7 Specifications Part 2 Specifications 1 Specifications 8 1 1 Cooling Only 8 1 2 Heat Pump 11 ...
Страница 64: ...SiBE05 722ED 53 Remote Controller Part 5 Remote Controller 1 Remote Controller 54 ...