SiBE05-722ED
Outdoor Unit
Printed Circuit Board Connector Wiring Diagram
20
2. Outdoor Unit
2.1
RK(X)S25/35E2V1B
Main PCB (PCB2)
Caution
Replace the PCB if you accidentally cut the jumpers other than J5 and J8.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
1) S10
Connector for filter PCB
2) S20
Connector for electronic expansion valve coil
3) S30
Connector for compressor
4) S40
Connector for overload protector
5) S70
Connector for fan motor
6) S80
Connector for four way valve coil
7) S90
Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
8) HC3, HC4
HL3, HN3
Connector for filter PCB
9) HR2
Connector for reactor
10)FU1, FU2
Fuse (3.15 A, 250 V)
11)LED A
LED for service monitor (green)
12)V1
Varistor
13)J5
Jumper for improvement of defrost performance
∗
Refer to page 117 for detail.
14)J8
Jumper for facility setting
∗
Refer to page 116 for detail.
15)SW1
Forced cooling operation ON/OFF button
∗
Refer to page 113 for detail.
2P143284-6
S90
LED A
S40
S10
S30
HC3
HN3
S20
S80
V1
FU1
HL3
HC4
HR2
FU2
J8
J5
S70
SW1