SiBE05-722ED
Trial Operation
Trial Operation and Field Settings
114
3. Trial Operation
Outline
Carry out the trial operation in accordance with the operation manual to ensure that all functions
and parts, such as flap movement, are working properly.
Trial operation should be carried out in either cooling or heating operation.
Detail
1. Measure the power supply voltage and make sure that it falls within the specified range.
2. In cooling operation, select the lowest programmable temperature (18°C); in heating
operation, select the highest programmable temperature (30°C).
Trial operation may be disabled in either operation mode depending on the room
temperature.
After trial operation is complete, set the temperature to a normal level (26°C ~ 28°C in
cooling, 20°C ~ 24°C in heating operation).
For protection, the system does not start for 3 minutes after it is turned off.
Detail
ARC433 Series
(1) Press the
ON/OFF
button to turn on the system.
(2) Press the center of the
TEMP
button and the
MODE
button at the same time.
(3) Press the
MODE
button twice.
(
T
appears on the display to indicate that trial operation is selected.)
(4) Press the
MODE
button and select operation mode.
(5) Trial operation terminates in approximately 30 minutes and switches into normal mode. To
quit a trial operation, press the
ON/OFF
button.
(2)
(1) (5)
(3)
(2) (3) (4)
(R9663)