SiBE01-503
Functions
Functions and Control
17
1.4
Automatic Operation
Outline
When the automatic mode is selected with the remote controller, the microcomputer determines
the operation mode from cooling and heating according to the room temperature and the
setpoint.
The unit automatically switches the operation mode to cooling or heating to maintain the room
temperature.
Details of the
Control
Target temperature equals setpoint plus correction value (c1
°
C, heating: –1
°
C)
Mode switching point and operation ON/OFF point are as follows.
Cooling
→
Heating: Room temperature – setpoint
≤
–
2
°
C
Heating
→
Cooling: Room temperature – setpoint
≥
+
2
°
C
Cooling thermostat ON : Room temperature – setpoint
≥
+
2
°
C
Cooling thermostat OFF: Room temperature – setpoint
≤
+
1
°
C
Heating thermostat ON : Room temperature – setpoint
≤
–
2
°
C
Heating thermostat OFF: Room temperature – setpoint
≥
–
1
°
C
Heating
→
Cooling
Cooling thermostat ON
+2˚C
+1˚C
0˚C
–1˚C
–2˚C
Cooling thermostat OFF
Cooling
Heating
Cooling
Compressor ON
Compressor OFF
(R4728)
Heating thermostat OFF
Cooling
→
Heating
Heating thermostat ON
Room temperature – setpoint
Содержание ARY20DV2
Страница 1: ...SiBE01 503 SPLIT Pair D Series Applied Models zNon Inverter Pair Heat Pump ...
Страница 5: ...SiBE01 503 iv Table of Contents Index i Drawings Flow Charts iii ...
Страница 10: ...SiBE01 503 List of Function 1 Part 1 List of Function 1 Functions 2 ...
Страница 13: ...Functions SiBE01 503 4 List of Function ...
Страница 14: ...SiBE01 503 Specifications 5 Part 2 Specifications 1 Specifications 6 ...
Страница 21: ...Printed Circuit Board Connector Wiring Diagram SiBE01 503 12 Printed Circuit Board Connector Wiring Diagram ...
Страница 35: ...Control Specification SiBE01 503 26 Functions and Control ...
Страница 59: ...Instructions SiBE01 503 50 System Configuration ...
Страница 79: ...Check SiBE01 503 70 Service Diagnosis ...
Страница 117: ...Others SiBE01 503 108 Others ...