SiENBE04-401A
Troubleshooting
Service Diagnosis
119
4.10 Input Over Current Detection
Remote control
Display
E8
Method of
Malfunction
Detection
An input over-current is detected by checking the input current value with the compressor
running.
Malfunction
Decision
Conditions
The following current with the compressor running continues for 2.5 seconds.
Cooling
•
Heating: Above 12A
Supposed
Causes
Over-current due to compressor failure
Over-current due to defective power transistor
Over-current due to defective outdoor unit PCB
Error detection due to outdoor unit PCB
Over-current due to short-circuit
Troubleshooting
Check No.7
Refer to P.141
Check No.8
Refer to P.141
Note:
If the model doesn’t have SPM, replace the outdoor unit PCB.
Replace the outdoor unit
PCB.
∗
Inverter checker
Part No.: 1225477
Correct the power supply or
replace the SPM.
(Replace the outdoor unit
PCB.)
(R2952)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Input current flowing
above its stop level?
NO
YES
Any LED off?
YES
NO
Check with the inverter checker (
∗
).
Turn off the power, and reconnect
the harnesses. Turn on the power
Turn off the power and disconnect
the harnesses U, V and W.
Get restarted and measure the
input current.
Check No. 8
Check the discharge pressure.
Check No. 7
Check the installation condition.
∗
An input over-current may result from wrong internal wiring. If the wires have been disconnected and
reconnected for part replacement, for example, and the system is interrupted by an input over-current,
take the following procedure.
Содержание ARKH20CAVMB
Страница 19: ...List of Functions SiENBE04 401A 10 List of Functions ...
Страница 20: ...SiENBE04 401A Specifications 11 Part 2 Specifications 1 Specifications 12 1 1 Cooling Only 12 1 2 Heat Pump 20 ...
Страница 45: ...Specifications SiENBE04 401A 36 Specifications ...
Страница 81: ...Control Specification SiENBE04 401A 72 Function and Control ...
Страница 111: ...Instruction SiENBE04 401A 102 System Configuration ...
Страница 155: ...Check SiENBE04 401A 146 Service Diagnosis ...
Страница 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 401A 216 Removal Procedure ...
Страница 226: ...SiENBE04 401A Others 217 Part 8 Others 1 Others 218 1 1 Test Run from the Remote Control 218 1 2 Jumper Settings 219 ...
Страница 229: ...Others SiENBE04 401A 220 Others ...
Страница 239: ...Wiring Diagrams SiENBE04 401A 230 Appendix ...