Daikin Trouble Shooting Guide

Past & Current Models

Daikin Fault Codes

System Fault Codes
Fault Code Definition

Supposed Causes

Split

Skyair

VRV

Package

HRV

U0

Shortage of refrigerant

Undercharged, EEV fault, faulty sensor

U1

Reverse or missing phase

Reversed or missing phase

U2

Power supply fault

Power supply fault, capacitor wiring error

U3

Check operation not executed Check operation not carried out at  

commissioning or after main PCB replaced

U4

Communication failure,  

between indoor & outdoor 

Wiring fault, defect of PCB, pump wired 

across communication wiring

U5

Communication failure,  

between r/controller & PCB

Wiring fault, defect of Remote  

controller & PCB

U6

Communication failure  

between indoor units

Wiring fault, defect of indoor PCB

U7

Communication failure,  

between outdoor PCB’s

Defect of outdoor PCB,  

wiring error between PCB’s

U7

Communication failure  

between outdoor units

Wiring error between outdoor units,  

defect of outdoor PCB

U8

Communication failure be-

tween remote controllers

Main/sub switch not set, wiring error,  

defect of remote controller

U9

System communication failed  Fault with other indoor unit, no power, A9

UA

Improper combination

Incorrect field setting, wiring, defect of PCB

UA

Incorrect field setting  
Wiring, defective PCB

Field setting incorrect (twin/triple), error in 

UA

Improper combination of  

Indoor/outdoor units

Excess of indoor units, incorrect PCB  

Setting, defective PCB

UC

Error in address setting

Duplicated central control address

UE

Communication failure  

between indoor central device

Wiring error between indoor unit & central 

control, defect of indoor PCB, setting error

UF

Wiring/piping mismatch

Wiring error indoor to outdoor, PCB defect

UH

System malfunction

Unaddressed indoor unit

UH

System malfunction

Mismatched indoor/outdoor, freeze protect

UJ

Communication failure

Defect of accessory device, wiring error

M1

Central controller failed

Failure of central controller PCB

M8

Communication failure  
between central & options

Communication failed between central 
controller & optional controllers

MA

Improper combination of  
optional controllers

Incorrect settings,  
faulty central controller

MC

Duplicated address

Duplicated central controller address

60

Overall alarm

Open circuit across J1-JC

64

Failed return air sensor

Sensor open/short circuit

65

Failed ambient sensor

Sensor open/short circuit

6A

Failure of damper system

Defect of damper motor, limit switch, PCB