BLOWER PERFORMANCE DATA
47
CFM
Rise
CFM
Rise
CFM
Rise
CFM
Rise
A-
505
675
540
63
720
63
A-
545
810
720
63
960
63
A
565
750
600
56
800
56
A
605
900
800
56
1065
56
A+
620
825
660
51
880
51
A+
665
990
880
51
1170
51
B-
540
720
610
55
810
56
B-
605
900
810
56
1075
56
B
600
800
675
50
900
50
B
670
1000
900
50
1195
50
B+
660
880
745
45
990
45
B+
735
1100
990
45
1315
46
C-
560
745
660
51
880
51
C-
650
970
900
50
1195
50
C
620
825
735
46
980
46
C
720
1075
1000
45
1330
45
C+
685
910
810
42
1075
42
C+
795
1185
1100
41
1465
41
D-
575
765
X
X
X
X
D-
665
990
X
X
X
X
D
640
850
X
X
X
X
D
735
1100
X
X
X
X
D+
700
935
X
X
X
X
D+
810
1210
X
X
X
X
CFM
Rise
CFM
Rise
CFM
Rise
CFM
Rise
A-
680
1015
720
63
960
63
A-
970
1170
915
61
1215
62
A
755
1125
800
56
1065
56
A
1080
1300
1015
55
1350
56
A+
830
1240
880
51
1170
51
A+
1185
1430
1115
50
1485
51
B-
725
1080
810
56
1075
56
B-
1045
1260
1015
55
1350
56
B
805
1200
900
50
1195
50
B
1160
1400
1125
50
1495
50
B+
885
1320
990
45
1315
46
B+
1280
1540
1240
45
1650
45
C-
755
1125
900
50
1195
50
C-
1085
1305
1125
50
1495
50
C
840
1250
1000
45
1330
45
C
1205
1450
1250
45
1665
45
C+
920
1375
1100
41
1465
41
C+
1325
1595
1375
41
1830
41
D-
800
1195
X
X
X
X
D-
1120
1350
X
X
X
X
D
890
1325
X
X
X
X
D
1245
1500
X
X
X
X
D+
980
1460
X
X
X
X
D+
1370
1650
X
X
X
X
CFM
Rise
CFM
Rise
A-
1150
1305
900
63
1195
63
A
1275
1450
1000
56
1330
56
A+
1405
1595
1100
51
1465
51
B-
1190
1350
1015
55
1350
56
B
1320
1500
1125
50
1495
50
B+
1450
1650
1240
45
1650
45
C-
1230
1395
1125
50
1495
50
C
1365
1550
1250
45
1665
45
C+
1500
1705
1375
41
1830
41
D-
1265
1440
X
X
X
X
D
1410
1600
X
X
X
X
D+
1550
1760
X
X
X
X
APGM53006041** - Rise Range: High Fire 35° - 65°
Tap Low Cool High Cool
Low Heat
High Heat
Tap Low Cool High Cool
Low Heat
High Heat
Low Fire 25° - 55°
APGM52406041** - Rise Range: 25° - 55°
APGM53608041** - Rise Range: 35° - 65°
APGM54210041** - Rise Range: 35° - 65°
Tap Low Cool High Cool
Low Heat
High Heat
Tap Low Cool High Cool
Low Heat
High Heat
APGM54810041** - Rise Range: 35° - 65°
Tap Low Cool High Cool
Low Heat
High Heat
X = Outside of Temperature Rise Range - Not Recommended.