Troubleshooting by Indication on the Remote Controller
Troubleshooting
205
Troubleshooting
2: Voltage measurement point
1: Refer to “Thermistor Resistance / Temperature Characteristics” table on P251.
2: Refer to “Pressure Sensor, Pressure / Voltage Characteristics” table on P254.
(V2819)
The suction
pipe1 temp. minus
low pressure saturation temp.
is 20 °C or higher.
Resistance is
normal when
measured with the
thermistor (R3T) for suction
pipe1 disconnected from
the outdoor unit PC
board.
*
1
Out of gas or refrigerant system
is clogged. Requires check of
refrigerant system.
Replace the thermistor. (R3T)
Replace the outdoor unit PC
board (A1P).
YES
YES
NO
NO
Out of gas, closing of stop valve
or refrigerant system is clogged.
Requires check of refrigerant
system.
Replace main outdoor unit PC
board (A1P).
YES
YES
Is
the low pressure
sensor correct?
Replace the low pressure
sensor.
NO
NO
Cooling
Low
pressure is 0.25
MPa or less.
The
voltage of
X18A pins (2) and
(3) on main outdoor unit
PC board (A1P) is 1.0 VDC or
less. (Low pressure sensor
output voltage)
*
2
NO
NO
YES
YES
Replace low pressure sensor.
Caution
Be sure to turn off power switch before connect or disconnect connector, or
parts damage may be occurred.
4
3
2
1
(V2809)
Red
Black
White
GND
*2 Measure voltage here.
Lo
w pressure sensor
Outside unit PC board A1P
+5V
X18A
Microcomputer
A/D input
Содержание ALTHERMA HT EKBUHAA6 V3
Страница 2: ......
Страница 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Страница 13: ...ESIE09 08A General Information 1 Part 1 General Information 1 Model Names of Indoor Outdoor Units Tanks 2 ...
Страница 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Страница 17: ...ESIE09 08A Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Unit 8 ...
Страница 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Страница 38: ...Functional Parts Layout ESIE09 08A 26 Refrigerant Circuit 2 6 EKHTSU 200 260 A AB AC Front view Tank sensor ...
Страница 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Страница 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Страница 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Страница 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Страница 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Страница 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Страница 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Страница 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Страница 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Страница 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Страница 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...
Страница 266: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08A 256 Appendix Inverter PC board C C W U V ...
Страница 288: ...3 Way Valve ESIE09 08A 278 Appendix ...