14 Technical data
Installer reference guide
89
ERLQ004~008CA + 08S18CB
Daikin Altherma – Low temperature split
4P401676-1 – 2015.02
Electrical specifications
ERLQ004~008CAV3
Power supply
Name
V3
Phase
1
Frequency
50 Hz
Voltage
230 V
Voltage range
Minimum
–10%
Maximum
+10%
Current
Nominal running current
Cooling
—
Heating
Starting current
Cooling
15.7 A
18 A
(1)
Heating
Maximum running current
Cooling
15.7 A
18 A
(3)
Heating
Z
max
—
Minimum S
sc
value
Equipment complying with EN/IEC 61000‑3‑12
(2)
Recommended fuses
16 A
20 A
Wiring connections
For power supply
Quantity
3
Remark
—
For connection with indoor
Quantity
3
Remark
No earth wire
Figure A: Starting current
Daikin inverter controlled compressor starting current always less
then or equal to maximal running current.
A
B
D
E
C
A
Running current
B
Time
C
Maximum
D
Example 1
E
Example 2
Standard on/off compressor starting current to maximum running
current
A
B
D
E
C
A
Running current
B
Time
C
Maximum
D
Example 1
E
Example 2
(1) See figure A.
(2) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16 A and ≤75 A
per phase.