2 About the documentation
Installer reference guide
6
ERLQ004~008CA + 08S18CB
Daikin Altherma – Low temperature split
4P401676-1 – 2015.02
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
Install power cables at least 1 metre away from televisions or radios
to prevent interference. Depending on the radio waves, a distance of
1 metre may not be sufficient.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical
components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Only applicable if the power supply is three‑phase, and the
compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a
momentary black out and the power goes on and off while
the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed
phase can break the compressor and other parts.
2
About the documentation
2.1
About this document
Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set
consists of:
▪
General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the indoor unit)
▪
Indoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the indoor unit)
▪
Outdoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the outdoor unit)
▪
Installer reference guide:
▪ Preparation of the installation, technical specifications, good
practices, reference data,…
▪ Format: Digital files on
http://www.daikineurope.com/support-
and-manuals/product-information/
▪
Addendum book for optional equipment:
▪ Additional info about how to install optional equipment
▪ Format: Paper (in the box of the indoor unit) + Digital files on
http://www.daikineurope.com/support-and-manuals/product-
information/
Latest revisions of the supplied documentation may be available on
the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages
are translations.
2.2
Installer reference guide at a
glance
Chapter
Description
General safety
precautions
Safety instructions that you must read
before installing
About the documentation
What documentation exists for the
installer
About the box
How to unpack the units and remove
their accessories
About the units and
options
▪ How to identify the units
▪ Possible combinations of units and
options
Application guidelines
Various installation setups of the system
Preparation
What to do and know before going
on‑site
Installation
What to do and know to install the
system
Configuration
What to do and know to configure the
system after it is installed
Commissioning
What to do and know to commission the
system after it is configured
Hand‑over to the user
What to give and explain to the user
Maintenance and service
How to maintain and service the units
Troubleshooting
What to do in case of problems
Disposal
How to dispose of the system
Technical data
Specifications of the system
Glossary
Definition of terms
Field settings table
Table to be filled in by the installer, and
kept for future reference
Note:
There is also an installer settings
table in the user reference guide. This
table has to be filled in by the installer
and handed over to the user.
Содержание Altherma ERLQ004-006-008CA
Страница 98: ...2 8...
Страница 105: ......
Страница 106: ......
Страница 107: ......
Страница 108: ...4P401676 1 2015 02 Copyright 2015 Daikin...