8 Configuration
Installer reference guide
38
ERLQ004~008CA + 08S18CB
Daikin Altherma – Low temperature split
4P401676-1 – 2015.02
7.10
Finishing the outdoor unit
installation
7.10.1
To finish the outdoor unit installation
1
Insulate and fix the refrigerant piping and interconnection cable
as follows:
f
b
a
e
d
c
a
Gas pipe
b
Gas pipe insulation
c
Interconnection cable
d
Liquid pipe
e
Liquid pipe insulation
f
Finishing tape
2
Install the service cover.
7.10.2
To close the outdoor unit
1
Close the switch box cover.
2
Close the service cover.
NOTICE
When closing the outdoor unit cover, make sure that the
tightening torque does NOT exceed 4.1 N•m.
7.11
Finishing the indoor unit
installation
7.11.1
To fix the user interface cover to the
indoor unit
1
Make sure that the front panel is removed from the indoor unit.
See
"7.2.3 To open the indoor unit" on page 22
.
2
Plug the user interface cover into the hinges.
3
Mount the front panel to the indoor unit.
7.11.2
To close the indoor unit
1
Close the switch box cover.
2
Reinstall the top plate.
3
Reinstall the front panel.
NOTICE
When closing the indoor unit cover, make sure that the
tightening torque does NOT exceed 4.1 N•m.
8
Configuration
8.1
Overview: Configuration
This chapter describes what you have to do and know to configure
the system after it is installed.
Why
If you do NOT configure the system correctly, it might NOT work as
expected. The configuration influences the following:
▪ The calculations of the software
▪ What you can see on and do with the user interface
How
You can configure the system using two different methods.
Method
Description
Configuring via the
user interface
First time – Quick wizard.
When you turn
ON the user interface for the first time (via
the indoor unit), a quick wizard starts to help
you configure the system.
Afterwards.
If necessary, you can make
changes to the configuration afterwards.
Configuring via the
PC configurator
You can prepare the configuration off-site on
PC and afterwards upload the configuration
to the system with the PC configurator.
See also:
"8.1.1 To connect the PC cable to
the switch box" on page 38
.
INFORMATION
When the installer settings are changed, the user interface
will request to confirm. When confirmed, the screen will
shortly turn OFF and "busy" will be displayed for several
seconds.
Accessing settings – Legend for tables
You can access the installer settings using two different methods.
However, NOT all settings are accessible via both methods. If so,
the corresponding table columns in this chapter are set to N/A (not
applicable).
Method
Column in tables
Accessing settings via the breadcrumb in the
menu structure
.
#
Accessing settings via the code in the
overview settings
.
Code
See also:
▪
"To access the installer settings" on page 39
▪
"8.5 Menu structure: Overview installer settings" on page 58
8.1.1
To connect the PC cable to the switch box
Prerequisite:
The EKPCCAB kit is required.
1
Connect the cable with USB connection to your PC.
2
Connect the plug of the cable to X10A on A1P of the switch box
of the indoor unit.
A1P
X10A