Restrictions
See
See
A
Room A (= room where indoor unit is installed)
B
Room B (= adjacent room)
a1
Bottom opening for natural ventilation
a2
Top opening for natural ventilation
PATTERN 1
For PATTERN 1 you only need to comply with the spacing guidelines described in
requirements of the indoor unit"
64].
PATTERN 2 and 3
For PATTERN 2 and 3, additionally to the spacing guidelines described in
"7.1.3 Installation site requirements of
64], you also need to comply with the minimum floor area requirements as described in the
following flow chart. The flow chart uses the following tables:
"16.5 Table 1 – Maximum refrigerant charge allowed
"16.6 Table 2 – Minimum floor area: indoor unit"
277] and
Minimum bottom opening area for natural ventilation: indoor unit"
277].
INFORMATION
Multiple indoor units.
If two or more indoor units are installed in a room, you must
consider the maximum refrigerant charge that can be released in the room when a
SINGLE leak occurs.
Example:
If two indoor units are installed in the room, each with
its own outdoor unit, then you have to consider the refrigerant charge of the largest
indoor-outdoor combination.