13
|
Maintenance and service
Installer reference guide
245
ERGA04~08E + 23E
Daikin Altherma 3 R F
4P629090-1C – 2022.08
▪
Checking if both parts of the magnetic filter/dirt separator are still screwed
tight (a).
▪
Emptying the dirt separator as follows:
1
Take off the magnetic sleeve (b).
2
Unscrew the drain cap (d).
3
Connect a drain hose to the bottom of the water filter so that the water and
dirt can be collected in a suitable container (bottle, sink...).
4
Open the drain valve for a couple of seconds (c).
Result:
Water and dirt will come out.
5
Close the drain valve.
6
Screw the drain cap back on.
7
Reattach the magnetic sleeve.
8
Check the pressure of the water circuit. If required, add water.
NOTICE
▪
When checking the magnetic filter/dirt separator for tightness, hold it firmly, so
as NOT to apply stress to the water piping.
▪
Do NOT isolate the magnetic filter/dirt separator by closing the shut‑off valves. To
properly empty the dirt separator, sufficient pressure is required.
▪
To prevent dirt from remaining in the dirt separator, ALWAYS take off the
magnetic sleeve.
▪
ALWAYS first unscrew the drain cap, and connect a drain hose to the bottom of
the water filter, then open the drain valve.
INFORMATION
For yearly maintenance, you do not have to remove the water filter from the unit to
clean it. But in case of trouble with the water filter, you might have to remove it so
that you can thoroughly clean it. Then you need to do as follows:
▪
"13.5.1 To remove the water filter"
▪
"13.5.2 To clean the water filter in case of trouble"
▪
"13.5.3 To install the water filter"
Water pressure relief valve
Open the valve and check if it operates correctly.
The water may be very hot!
Checkpoints are:
▪
The water flow coming from the relief valve is high enough, no blockage of the
valve or in between piping is suspected.
▪
Dirty water coming out of the relief valve:
-
open the valve until the discharged water does NOT contain dirt anymore
-
flush the system
To make sure this water originates from the tank, check after a tank heat up cycle.
It is recommended to do this maintenance more frequently.
Pressure relief valve hose
Check whether the pressure relief valve hose is positioned appropriately to drain
the water. See