Heating WD curve
Set weather-dependent heating for the main zone (if [2.4] = 1 or 2):
#
Code
Description
[2.5]
[1-00]
[1-01]
[1-02]
[1-03]
Set weather-dependent heating:
[1-03]
[1-02]
Ta
Tt
[1-00]
[1-01]
▪ T
t
: Target leaving water temperature
(main zone)
▪ T
a
: Outdoor temperature
▪ [1-00]:
Low
outdoor
ambient
temperature. –40°C~+5°C
▪ [1-01]:
High
outdoor
ambient
temperature. 10°C~25°C
▪ [1-02]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or drops below the
low
ambient
temperature.
[9‑01]°C~[9‑00]°C
Note:
This value should be higher
than [1‑03] as for low outdoor
temperatures
warmer
water
is
required.
▪ [1-03]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or rises above the
high
ambient
temperature.
[9‑01]°C~min(45, [9‑00])°C
Note:
This value should be lower than
[1‑02]
as
for
high
outdoor
temperatures less warm water is
required.
Cooling WD curve
Set weather-dependent cooling for the main zone (if [2.4] = 2):
#
Code
Description
[2.6]
[1-06]
[1-07]
[1-08]
[1-09]
Set weather-dependent cooling:
[1-09]
[1-08]
Ta
Tt
[1-06]
[1-07]
▪ T
t
: Target leaving water temperature
(main zone)
▪ T
a
: Outdoor temperature
▪ [1-06]:
Low
outdoor
ambient
temperature. 10°C~25°C
▪ [1-07]:
High
outdoor
ambient
temperature. 25°C~43°C
▪ [1-08]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or drops below the
low
ambient
temperature.
[9‑03]°C~[9‑02]°C
Note:
This value should be higher
than [1‑09] as for low outdoor
temperatures less cold water is
required.
▪ [1-09]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or rises above the
high
ambient
temperature.
[9‑03]°C~[9-02]°C
Note:
This value should be lower than
[1‑08]
as
for
high
outdoor
temperatures colder water is required.
Emitter type
Depending on the system water volume and the heater emitter type
of the main zone, the heat up or cooling down of the main zone can
take longer. This setting can compensate for a slow or a quick
heating/cooling system during the heat up/cool down cycle (cooling
only with EKHVCONV2 installed).
The target delta T for the main zone will depend on this setting.
Target delta T control is only possible in case only 1 zone is active.
Pump control will be different when both zones are active.
In room thermostat control, this setting will influence:
▪ the maximum modulation of the desired leaving water
temperature.
▪ the possibility for usage of the automatic cooling/heating
changeover based on the indoor ambient temperature (only with
EKHVCONV2 installed).
Therefore it is important to set this correctly and in accordance with
your system layout.
#
Code
Description
[2.7]
[2‑0C]
Emitter type
▪ 0: Underfloor heating
▪ 1: Fancoil unit
▪ 2: Radiator
The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows: