Operation manual

7

EK EK80ABV1

Daikin Altherma indoor unit

4P404418-1 – 2015.04

Automatic setback function

Setback function provides the possibility to lower the room
temperature. The setback function can for instance be activated
during the night because the temperature demands during night and
day are not the same.

The setback function is configured through field settings. Refer to

"4.15. Field settings" on page 19

 for a detailed description how to set

one or more field settings.

[2-00] Status: defines whether the setback function is turned ON
(1) or OFF (0)

[2-01] Start time: time at which setback is started

[2-02] Stop time: time at which setback is stopped

[5-02] Leaving water setback temperature (temperature drop)

4.4.

Emergency operation

[8-02] Emergency operation

During emergency mode, heating is only done by the heater kit,
not by the heat pump.

Activation of emergency mode is done by changing field setting
[8-02]=1.

Activating the emergency mode will stop the heat pump
operation. The pump of the indoor unit will be started, but
heating itself is done by the heater kit. If there are no error
conditions in leaving or returning water thermistors, the heater
kit can start to follow emergency operation.

4.5.

Space cooling operation ( )

Space cooling operation can be controlled in two different ways:

based on room temperature,

based on leaving water temperature.

The purpose of each operation and how the configuration is done, is
explained below.

Room temperature control

In this mode, cooling will be activated as required by the room
temperature set point. The set point can be set manually or through
the schedule timer.

Selecting space cooling operation

1

Use the 

 button to switch ON/OFF space cooling ( ).

Icon 

 appears on the display as well as the corresponding

actual room temperature.
The operation LED   lights up.

2

Use the 

 and 

 buttons to set the desired room

temperature.

Temperature range for cooling: 16°C~32°C (room temperature)
Refer to 

"4.12. Programming and consulting the schedule timer"

on page 13

 for setup of the schedule timer function.

3

Use the 

 and 

 buttons to select the leaving

water temperature which you want to be used to cool down your
system (for detailed information see 

"Leaving water temperature

control" on page 6

).

Leaving water temperature control

In this mode, cooling will be activated as required by the water
temperature set point. The set point can be set manually or through
the schedule timer.

Selecting space cooling operation

1

Use the 

 button to switch ON/OFF space cooling ( ).

Icon 

 appears on the display as well as the corresponding

water temperature set point.
The operation LED   lights up.

2

Use the 

 and 

 buttons to set the desired leaving

water temperature.

Temperature range for cooling: 20°C~5°C (leaving water
temperature)

Refer to 

"Programming space heating" on page 14

"Programming

space cooling" on page 15

"Programming domestic water heating"

on page 16

, and 

"Programming quiet mode" on page 17

 for setup of

the schedule timer function.

NOTE

Remark that the   icon will be flashing during
setback operation.

By default the setback function is enabled.

The setback function can be combined with the
automatic weather dependent set point operation.

Setback function is an automatic daily scheduled
function.

A

Normal leaving water temperature set point

B

Leaving water temperature, including the leaving water setback 
temperature

t

Time

T

Temperature

NOTE

Before activating emergency operation, be sure to
activate the heater kit. The heater will stay in
emergency mode until the field setting is set back
to default [8-02]=0.

[2-01]

[2-02]

B

A

T

t

65

°

C

60

°

C

5

°

C [5-02]

NOTE

When using room temperature control, space cooling
operation based on room temperature will have priority
over leaving water control.

Note that it is possible that the leaving water
temperature becomes lower than the set point if the
unit is controlled by room temperature.

NOTE

When an external room thermostat is installed,
the thermo ON/OFF is determined by the external
room thermostat. The remote controller is than
operated in the leaving control mode and is not
functioning as a room thermostat.

The remote controller ON/OFF status always has
priority over the external room thermostat!

Setback operation and weather dependent
setpoint are not available in cooling operation.

Содержание Altherma EKHVMRD50ABV1

Страница 1: ...OPERATION MANUAL EKHVMRD50ABV1 EKHVMRD80ABV1 EKHVMYD50ABV1 EKHVMYD80ABV1 Daikin Altherma indoor unit ...

Страница 2: ...wledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children shall be supervised to ensure that they do not play with the appliance 1 DEFINITIONS Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it Danger Indicates an imminently ha...

Страница 3: ...g The more detailed information of how the unit must be operated is explained in the chapter 4 Operation of the unit on page 3 The quick start up offers the user the possibility to start up the system before reading the entire manual Space heating operation NOTE An EKHVMRD and EKHVMYD indoor unit can only be connected to an EMRQ outdoor unit The installation of the indoor unit s is described in th...

Страница 4: ...eating only if domestic hot water tank option is installed Automatic storage daily water heat up once during night and or once during day Turn on field setting 1 00 and or 1 02 and then push the button See Automatic storage on page 8 The icon will display Hot water will be produced at next scheduled action When water heat up starts the icon will be blinking 1 second interval Manual storage one tim...

Страница 5: ...r to Field settings in the installation manual the weather dependent set point button will not be operable 26 INSPECTION TEST OPERATION BUTTON This button is used for installation purposes and changing field settings Refer to 4 15 Field settings on page 19 27 PROGRAMMING BUTTON This multi purpose button is used to program the controller The function of the button depends on the actual status of th...

Страница 6: ...aving water temperature which you want to be used to heat up your system for detailed information see Leaving water temperature control on page 6 Automatic setback function Setback function provides the possibility to lower the room temperature The setback function can for instance be activated during the night because the temperature demands during night and day are not the same The setback funct...

Страница 7: ...al room thermostat 1 Press the button 1 time to select weather dependent set point operation or 2 times when the remote controller room thermostat function is used Icon appears on the display as well as the shift value The shift value is not shown in case it is 0 2 Use the and buttons to set the shift value Range for the shift value 5 C to 5 C Icon will be displayed as long as the weather dependen...

Страница 8: ...edule timer function 3 Use the and buttons to select the leaving water temperature which you want to be used to cool down your system for detailed information see Leaving water temperature control on page 6 Leaving water temperature control In this mode cooling will be activated as required by the water temperature set point The set point can be set manually or through the schedule timer Selecting...

Страница 9: ...Therefore it is recommended to use this function b 04 Automatic maximum domestic hot water storage temperature default 70 C NOTE Any domestic water heating operation is impossible when the domestic hot water tank is not installed A Storage operation if activated B Reheat operation if activated C Disinfection operation if activated Field settings D Disinfection operation temperature 5 00 e g 70 C E...

Страница 10: ...estic water heating modes on page 8 Disinfection operation This mode will disinfect the domestic hot water tank by periodically heating the domestic water to a specific temperature During the operation of this mode the icon will be blinking rapidly with 0 5 second intervals The disinfection temperature set point is a field setting as are the retention time day and hour Refer to 4 15 Field settings...

Страница 11: ...t possible If you are using the remote controller room temperature control When the reheat temperature is reached the further heat up of the domestic hot water tank will be decided by the remote controller room thermostat in order to prevent the room temperature to drop too much If you are using the external room thermostat When the reheat temperature is reached the further heat up of the domestic...

Страница 12: ...stays enabled When pushing the button The schedule timer for space heating and domestic water heating along with the quiet mode will be stopped and will not start again The schedule timer icon will not be displayed anymore 1 Schedule timer 2 Setback function 3 When both setback function and schedule timer are enabled A Setback function t Time T Temperature set point Room temperature Leaving water ...

Страница 13: ...n can be used Reheat the reheat function can be activated next to or separate from the automatic storage operation if the user wants to keep the domestic hot water tank at the minimum reheat temperature Next to the standard domestic water heating operation modes it is also possible to freely program the domestic water heating operation through the schedule timer refer to Programming domestic water...

Страница 14: ...programmed for the same day and at the same time only the action with the highest action number will be executed Example You can always alter add or remove the programmed actions later NOTE If the auto restart function is disabled the schedule timer will not be activated when power returns to the unit after a power supply failure Press the button to enable the schedule timer again When power retur...

Страница 15: ...ature 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the remote controller off to select automatic temperature calculation for leaving water temperature Use the and buttons to set the appropriate shift value refer to 4 3 Space heating operation on page 5 for more information about weather dependent set point 12 Repeat steps 7 to 11 to program t...

Страница 16: ...ime 8 Use the and buttons to set the leaving water temperature 9 Use the and buttons to set the room temperature 10 Use the button to select to switch cooling and the remote controller off 11 Repeat steps 6 to 10 to program the other actions When all actions have been programmed make sure that the display shows the highest action number you would like to save 12 Press the button for 5 seconds to s...

Страница 17: ...ppears 7 Use the button to select the action number you would like to program or to modify 8 Use the and buttons to set the correct action time 9 Use the button to select or deselect as action 10 Repeat steps 7 to 9 to program the other actions of the selected mode When all actions have been programmed make sure that the display shows the highest action number you would like to save 11 Press the b...

Страница 18: ... program or to modify 7 Use the and buttons to set the correct action time 8 Use the button to select or deselect as action 9 Repeat steps 6 to 8 to program the other actions of the selected mode When all actions have been programmed make sure that the display shows the highest action number you would like to save 10 Press the button for 5 seconds to store the programmed actions If the button is p...

Страница 19: ...copied You can return to step 2 by pressing the button Deleting one or more programmed actions Deleting one or more programmed actions is done at the same time as storing the programmed actions When all actions for one day have been programmed make sure that the display shows the highest action number you would like to save By pressing the button for 5 seconds you store all actions except those wi...

Страница 20: ...on 3 will be displayed The current selected field setting code is indicated 2 with the set value displayed to the right 1 2 Press the button to select the appropriate field setting first code 3 Press the button to select the appropriate field setting second code 4 Press the button and button to change the set value of the select field setting 5 Save the new value by pressing the button 6 Repeat st...

Страница 21: ...eather dependent set point 00 Low ambient temperature Lo_A 10 20 5 1 C 01 High ambient temperature Hi_A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1 01 Disinfection operation day selection Fri Mon Sun 02 Disinfection operation start time 23 00 0 0...

Страница 22: ...ture limits 00 Installation related setting a 80 37 80 1 C 01 Installation related setting a 25 25 37 1 C 02 Installation related setting a 20 18 22 1 C 03 Installation related setting a 5 5 18 1 C 04 Not applicable Do not change the default value 0 d Domestic water heating retention times 00 Installation related setting a 10 5 20 1 01 Installation related setting a 30 10 60 5 02 Installation rela...

Страница 23: ...o not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qualified installer in accordance with the applicable legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is disposed off correctly you will help to prevent potential negative cons...

Страница 24: ...NOTES ...

Страница 25: ...NOTES ...

Страница 26: ...NOTES ...

Страница 27: ......

Страница 28: ...4P404418 1 2015 04 Copyright 2015 Daikin ...

Отзывы: