1 General safety precautions

Installer reference guide

4

ERLQ004~008CA + EHVH/X04+08S18+26CB

Daikin Altherma – Low temperature split

4P384973-1D – 2018.07

WARNING

Indicates  a  situation  that  could  result  in  death  or  serious
injury.

WARNING: FLAMMABLE MATERIAL

CAUTION

Indicates a situation that could result in minor or moderate
injury.

NOTICE

Indicates  a  situation  that  could  result  in  equipment  or
property damage.

INFORMATION

Indicates useful tips or additional information.

Symbol

Explanation

Before installation, read the installation and
operation manual, and the wiring instruction sheet.

Before performing maintenance and service tasks,
read the service manual.

For more information, see the installer and user
reference guide.

1.2

For the installer

1.2.1

General

If  you  are  NOT  sure  how  to  install  or  operate  the  unit,  contact  your
dealer.

NOTICE

Improper  installation  or  attachment  of  equipment  or
accessories  could  result  in  electric  shock,  short-circuit,
leaks,  fire  or  other  damage  to  the  equipment.  Only  use
accessories,  optional  equipment  and  spare  parts  made  or
approved by Daikin.

WARNING

Make  sure  installation,  testing  and  applied  materials
comply  with  applicable  legislation  (on  top  of  the
instructions described in the Daikin documentation).

CAUTION

Wear  adequate  personal  protective  equipment  (protective
gloves,  safety  glasses,…)  when  installing,  maintaining  or
servicing the system.

WARNING

Tear apart and throw away plastic packaging bags so that
nobody,  especially  children,  can  play  with  them.  Possible
risk: suffocation.

DANGER: RISK OF BURNING

▪ Do  NOT  touch  the  refrigerant  piping,  water  piping  or

internal parts during and immediately after operation. It
could  be  too  hot  or  too  cold.  Give  it  time  to  return  to
normal  temperature.  If  you  must  touch  it,  wear
protective gloves.

▪ Do NOT touch any accidental leaking refrigerant.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

CAUTION

Do NOT touch the air inlet or aluminium fins of the unit.

NOTICE

▪ Do  NOT  place  any  objects  or  equipment  on  top  of  the

unit.

▪ Do NOT sit, climb or stand on the unit.

NOTICE

Works  executed  on  the  outdoor  unit  are  best  done  under
dry weather conditions to avoid water ingress.

In  accordance  with  the  applicable  legislation,  it  might  be  necessary
to provide a logbook with the product containing at least: information
on maintenance, repair work, results of tests, stand-by periods,…

Also,  at  least,  following  information  MUST  be  provided  at  an
accessible place at the product:

▪ Instructions for shutting down the system in case of an emergency

▪ Name and address of fire department, police and hospital

▪ Name,  address  and  day  and  night  telephone  numbers  for

obtaining service

In Europe, EN378 provides the necessary guidance for this logbook.

1.2.2

Installation site

▪ Provide  sufficient  space  around  the  unit  for  servicing  and  air

circulation.

▪ Make  sure  the  installation  site  withstands  the  unit's  weight  and

vibration.

▪ Make  sure  the  area  is  well  ventilated.  Do  NOT  block  any

ventilation openings.

▪ Make sure the unit is level.

Do NOT install the unit in the following places:

▪ In potentially explosive atmospheres.

▪ In  places  where  there  is  machinery  that  emits  electromagnetic

waves.  Electromagnetic  waves  may  disturb  the  control  system,
and cause malfunction of the equipment.

▪ In  places  where  there  is  a  risk  of  fire  due  to  the  leakage  of

flammable  gases  (example:  thinner  or  gasoline),  carbon  fibre,
ignitable dust.

▪ In  places  where  corrosive  gas  (example:  sulphurous  acid  gas)  is

produced. Corrosion of copper pipes or soldered parts may cause
the refrigerant to leak.

1.2.3

Refrigerant

If applicable. See the installation manual or installer reference guide
of your application for more information.

NOTICE

Make  sure  refrigerant  piping  installation  complies  with
applicable  legislation.  In  Europe,  EN378  is  the  applicable
standard.

NOTICE

Make  sure  the  field  piping  and  connections  are  NOT
subjected to stress.

Содержание Altherma EHVH/X04S18CB

Страница 1: ...Installer reference guide Daikin Altherma Low temperature split English Installer reference guide Daikin Altherma Low temperature split ERLQ004 006 008CA EHVH X04S18CB EHVH X08S18 26CB...

Страница 2: ...ircuit requirements 25 6 4 2 Formula to calculate the expansion vessel pre pressure 26 6 4 3 To check the water volume and flow rate 26 6 4 4 Changing the pre pressure of the expansion vessel 27 6 4 5...

Страница 3: ...ioning 74 9 4 1 To check the minimum flow rate 75 9 4 2 Air purge function 75 9 4 3 To perform a test run 76 9 4 4 To perform an actuator test run 76 9 4 5 Underfloor heating screed dryout 76 10 Hand...

Страница 4: ...shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire CAUTION Do NOT touch the air inlet or aluminium fins of the unit NOTICE Do NOT place...

Страница 5: ...fer to the nameplate of the unit It states the type of refrigerant and necessary amount The unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require a...

Страница 6: ...ompatible with the inverter resistant to high frequency electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when laying power wiring Do NOT connect wiring of...

Страница 7: ...units and options Application guidelines Various installation setups of the system Preparation What to do and know before going on site Installation What to do and know to install the system Configur...

Страница 8: ...ccessories from the indoor unit 1 Remove the screws at the top of the unit 2 Remove the top panel 3 Remove the screws at the front of the unit 4 Push on the button on the bottom of the front plate 5 R...

Страница 9: ...ndoor unit with integrated tank H H Heating only X Heating cooling 04 Capacity class S Integrated tank material Stainless steel 18 Integrated tank volume CB Model series 3V Backup heater model 4 3 Com...

Страница 10: ...d in heating only systems For installation instructions see the installation manual of the room thermostat and addendum book for optional equipment Remote sensor for wireless thermostat EKRTETS You ca...

Страница 11: ...contains application guidelines for Setting up the space heating cooling system Setting up an auxiliary heat source for space heating Setting up the domestic hot water tank Setting up the energy meter...

Страница 12: ...ion is decided by the external thermostat Number of water temperature zones A 2 1 8 Code 7 02 0 1 LWT zone Main Setting Value External room thermostat for the main zone A 2 2 4 Code C 05 1 Thermo ON O...

Страница 13: ...separation between heating or cooling demand Benefits Cooling Heat pump convectors provide besides heating capacity also excellent cooling capacity Efficiency Under floor heating has the best perform...

Страница 14: ...1 7 Code C 07 0 LWT control Unit operation is decided based on the leaving water temperature Number of water temperature zones A 2 1 8 Code 7 02 0 1 LWT zone Main Benefits Compared with under floor he...

Страница 15: ...in heating and the lowest design temperature in cooling CAUTION When there is more than one leaving water zone you must ALWAYS install a mixing valve station in the main zone to decrease in heating in...

Страница 16: ...room thermostat requests heating the indoor unit or the auxiliary boiler starts operating depending on the outdoor temperature status of the changeover to external heat source When the permission is...

Страница 17: ...iler NOTICE Make sure the auxiliary contact has enough differential or time delay to prevent frequent changeover between indoor unit and auxiliary boiler If the auxiliary contact is an outdoor tempera...

Страница 18: ...during the night when there is lower space heating demand 5 4 3 Setup and configuration DHW tank For large DHW consumptions you can heat up the DHW tank several times during the day To heat up the DHW...

Страница 19: ...methods to determine the consumed energy Calculating Measuring INFORMATION You cannot combine calculating the consumed energy example for backup heater and measuring the consumed energy example for o...

Страница 20: ...es the rest i e indoor unit backup heater and optional booster heater Setup Connect power meter 1 to X5M 7 and X5M 8 Connect power meter 2 to X5M 9 and X5M 10 Power meter types Power meter 1 Single or...

Страница 21: ...uts b Backup heater c Booster heater Pi t DI4 DI3 DI1 a b Pi Power input t Time DI Digital inputs power limitation levels a Power limitation active b Actual power input Setup Demand PCB option EKRP1AH...

Страница 22: ...t a remote outdoor sensor option EKRSCA1 Setup For installation instructions see the installation manual of the remote outdoor sensor Configuration Select outdoor sensor A 2 2 B When the power saving...

Страница 23: ...no trouble Note If the sound is measured under actual installation conditions the measured value might be higher than the sound pressure level mentioned in Sound spectrum in the data book due to envi...

Страница 24: ...event of a water leak water cannot cause any damage to the installation space and surroundings Do NOT install the unit in places such as In places where a mineral oil mist spray or vapour may be prese...

Страница 25: ...ly use materials that are compatible with water used in the system and with the materials used in the indoor unit Field supply components Water pressure and temperature Check that all components in th...

Страница 26: ...he expansion vessel pre pressure The pre pressure Pg of the vessel depends on the installation height difference H Pg 0 3 H 10 bar 6 4 3 To check the water volume and flow rate The indoor unit has an...

Страница 27: ...e pressure Inappropriate setting of the expansion vessel pre pressure will lead to malfunction of the system Changing the pre pressure of the expansion vessel should be done by releasing or increasing...

Страница 28: ...r unit is designed to receive an input signal by which the unit switches into forced off mode At that moment the outdoor unit compressor will not operate Whether the power supply is interrupted or not...

Страница 29: ...ctors 3V 1 230 V 2 GND 9W 1 230 V 2 GND 2 bridges 3 230 V 3 GND 1 bridge 3 400 V 4 GND 7 Installation 7 1 Overview Installation This chapter describes what you have to do and know on site to install t...

Страница 30: ...eparation on page 22 7 3 2 Precautions when mounting the outdoor unit INFORMATION Also read the precautions and requirements in the following chapters General safety precautions Preparation 7 3 3 To p...

Страница 31: ...Maximum snowfall height b EKFT008CA option kit INFORMATION If you install the U beams in combination with the low sound cover EKLN08A1 different installation instructions apply for the U beams See the...

Страница 32: ...rain water flowing over the footpath so that it does NOT become slippery in case of ambient freezing temperatures If you install the unit on a frame install a waterproof plate within 150 mm of the bot...

Страница 33: ...onsists of the following stages 1 Installing the indoor unit 7 4 2 Precautions when mounting the indoor unit INFORMATION Also read the precautions and requirements in the following chapters General sa...

Страница 34: ...charge additional refrigerant it is recommended to open the refrigerant stop valve after charging 7 5 3 Guidelines when connecting the refrigerant piping Take the following guidelines into account whe...

Страница 35: ...s required when handling the valve c d a b a Service port and service port cap b Valve stem c Field piping connection d Stem cap Keep both stop valves open during operation Do NOT apply excessive forc...

Страница 36: ...possibility of moisture being present in the refrigerant piping for example water may have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed 7 6...

Страница 37: ...echarging refrigerant Example When relocating the system After a leak Charging additional refrigerant Before charging additional refrigerant make sure the outdoor unit s external refrigerant piping is...

Страница 38: ...charge in the system expressed as tonnes CO2 equivalent is used to determine the maintenance intervals Follow the applicable legislation Formula to calculate the greenhouse gas emissions GWP value of...

Страница 39: ...ation piping tapping points etc connected to the tank is subjected to this high pressure To prevent this a pressure relief valve needs to be installed The overpressure prevention depends on the correc...

Страница 40: ...ctrical wiring Before connecting the electrical wiring Make sure The refrigerant piping is connected and checked The water piping is connected Typical workflow Connecting the electrical wiring typical...

Страница 41: ...ch box cover 2 1 2 3 Strip insulation 20 mm from the wires a b a Strip wire end to this point b Excessive strip length may cause electrical shock or leakage 4 Open the wire clamp 5 Connect the interco...

Страница 42: ...nterconnection cable main power supply b Normal kWh rate power supply c Preferential power supply contact 2 Fix the cables with cable ties to the cable tie mountings INFORMATION In case of preferentia...

Страница 43: ...N 1 2 3 4 6 7 8 5 X6M X7M 6 kW 1 230 V 9W 1 2 3 4 6 7 8 5 X6M X7M 6 kW 3 230 V 9W F1B L1 L2 L3 L1 L2 L3 1 2 3 4 6 7 8 5 X6M X7M 6 kW 3N 400 V 9W 9 kW 3N 400 V 9W F1B L1 L2 L3 L1 L2 L3 1 2 3 4 6 7 8 5...

Страница 44: ...lplate The PCB is mounted in the faceplate of the user interface Be careful NOT to damage it At the indoor unit In the room 3 Use the 2 screws in the accessory bag to fix the wallplate of the user int...

Страница 45: ...tings 7 9 13 To connect the alarm output 1 Connect the alarm output cable to the appropriate terminals as shown in the illustration below X1M X2M 29 X1M YC Y1 Y2 Y3 Y4 A4P X2M a a Installation of EKRP...

Страница 46: ...t contact INFORMATION The preferential kWh rate power supply contact is connected to the same terminals X5M 3 4 as the safety thermostat It is only possible for the system to have EITHER preferential...

Страница 47: ...on page 47 8 5 Menu structure Overview installer settings on page 73 8 1 1 To connect the PC cable to the switch box Prerequisite The EKPCCAB kit is required 1 Connect the cable with USB connection t...

Страница 48: ...Busy and will NOT be possible to operate 3 The quick wizard will guide you 4 For proper operation of the system the local data on the two user interfaces must be the same If this is NOT the case both...

Страница 49: ...displayed for several seconds 8 2 Basic configuration 8 2 1 Quick wizard Language time and date Code Description A 1 N A Language 1 N A Time and date 8 2 2 Quick wizard Standard Backup heater configur...

Страница 50: ...ontinued Code Description A 2 1 8 7 02 continuation 1 2 LWT zones 2 leaving water temperature zones The zone with the lowest leaving water temperature in heating is called the main leaving water tempe...

Страница 51: ...prepare domestic hot water 0 No NOT installed Default for EHBH X 1 Yes Installed Default for EHVH X Remark For EHVH X the domestic hot water tank is by default installed Do NOT change this setting A...

Страница 52: ...1 Thermo ON OFF See Contact type main Connected on the indoor unit X2M 1a 2 H C request default See Contact type main Connected on the indoor unit X2M 1a and 2a Code Description A 2 2 B C 08 External...

Страница 53: ...connect up to 2 power meters with different pulse frequencies When only 1 or no power meter is used select No to indicate the corresponding pulse input is NOT used Code Description A 2 2 8 D 08 Option...

Страница 54: ...does NOT depend on the outdoor ambient temperature according a schedule The scheduled actions consists of desired shift actions either preset or custom Remark This value can only be set in leaving wa...

Страница 55: ...ter temperature is NOT weather dependent i e does NOT depend on the outdoor ambient temperature according a schedule The scheduled actions are On or OFF Remark This value can only be set in leaving wa...

Страница 56: ...when turning off the modulation you can set the desired leaving water temperature on the user interface Moreover with the modulation turned on the desired leaving water temperature is lowered or rais...

Страница 57: ...able legislation Code Description A 4 5 6 0E Maximum setpoint The maximum temperature that users can select for the domestic hot water You can use this setting to limit the temperature at the hot wate...

Страница 58: ...the room temperatures in heating Code Description Leaving water temperature range for the main leaving water temperature zone the leaving water temperature zone with the lowest leaving water temperatu...

Страница 59: ...5 C default 35 C A 3 2 1 3 3 09 Minimum temp cooling 15 C 25 C default 15 C Room temperature step ONLY applicable in room thermostat control and when the temperature is displayed in C Code Description...

Страница 60: ...rotection by the unit is possible In case of then the following applies One leaving water temperature zone When the leaving water temperature home page is OFF and the outdoor ambient temperature drops...

Страница 61: ...o used in automatic heating cooling changeover Automatic heating cooling changeover ONLY applicable for EHBX and EHVX The end user sets the desired operation mode on the user interface Heating Cooling...

Страница 62: ...y during day Code Description 7 4 3 2 6 0B 30 C min 50 6 0E C default 45 C Reheat The desired reheat tank temperature is used in reheat mode of scheduled reheat mode The guaranteed minimum tank temper...

Страница 63: ...00 TDHW Domestic hot water temperature TU User set point temperature as set on the user interface t Time Example setpoint TU maximum heat pump temperature 6 01 THP MAX 6 01 t 6 00 HP 5 10 20 30 40 43...

Страница 64: ...door temperature 4 02 or F 01 Range 0 95 minutes default 95 8 02 Anti recycling time t 1 0 1 0 8 01 8 02 8 00 1 Heat pump domestic water heating mode 1 active 0 not active 2 Hot water request for heat...

Страница 65: ...he disinfection function occurred due to domestic hot water tapping following actions are recommended When the Domestic hot water Type Reheat or Reheat sched is selected it is recommended to program t...

Страница 66: ...nected The purpose of this function is to determine based on the outdoor temperature possibility 1 or on energy prices possibility 2 which heating source can will provide the space heating either the...

Страница 67: ...ater is still and only heated by the indoor unit The permission signal for the auxiliary boiler is located on the EKRP1HB digital I O PCB When it is activated the contact X1 X2 is closed and open when...

Страница 68: ...door temperature is lower than setting 5 03 the domestic hot water will not be heated with the backup heater Code Description N A 5 03 Space heating priority temperature Defines the outdoor temperatur...

Страница 69: ...er the outdoor unit power supply can be interrupted internally by indoor unit control during stand still conditions no space heating cooling nor domestic hot water demand The final decision to allow p...

Страница 70: ...first before the backup heater is limited 1 BSH Depending on the power limitation level the backup heater will be limited first before the booster heater is limited 2 BUH Depending on the power limit...

Страница 71: ...w to continue operation when flow abnormality occurs This functionality is only valid in specific conditions where it is preferable to keep the pump active when Ta 4 C pump will be activated for 10 mi...

Страница 72: ...ion Energy metering Consumed elec Produced energy Error information Error history Contact helpdesk number Version User interface Indoor unit Outdoor unit User settings Display Temperature lock Set sch...

Страница 73: ...off contact Unit control method Number of LWT zones Pump operation mode Power saving possible User interface location Options DHW operation DHW tank type Contact type main Contact type add Digital I...

Страница 74: ...he domestic hot water tank if applicable Between the gas boiler and the local supply panel only applicable in case of hybrid system The system is properly earthed and the earth terminals are tightened...

Страница 75: ...y changes the pump speed and switches the position of the 3 way valve between the space heating and the domestic hot water heating mode Typical workflow Purging the air from the system should consist...

Страница 76: ...d the domestic hot water control are turned OFF via the user interface 3 Go to A 7 4 Installer settings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and pres...

Страница 77: ...ank step is programmed OR when 20 consecutive steps have been executed To perform an underfloor heating screed dryout INFORMATION Preferential kWh rate power supply cannot be used in combination with...

Страница 78: ...service work touch a metal part of the unit in order to eliminate static electricity and to protect the PCB 11 2 1 Opening the indoor unit CAUTION The front panel is heavy Be careful NOT to jam your...

Страница 79: ...s a stainless steel cylinder containing an aluminium anode We recommend to use a non chloride based disinfectant approved for use with water intended for human consumption NOTICE When using means for...

Страница 80: ...e is too low If the water temperature is too low the unit uses the backup heater to reach the minimum water temperature first 15 C Check and make sure that The power supply to the backup heater is cor...

Страница 81: ...A 8 Installer settings Overview settings 5 01 Possible causes Corrective action There is air in the system Purge air manually or automatically See the air purge function in the Commissioning chapter...

Страница 82: ...E7 00 OU Malfunction of outdoor unit fan motor Please contact your dealer E8 00 OU Power input overvoltage Please contact your dealer EA 00 OU Cool heat switchover problem Please contact your dealer H...

Страница 83: ...bnormal increase outlet water temperature 8H 03 Overheating water circuit thermostat A1 00 Zero cross detection problem Power reset required Please contact your dealer Error code Detailed error code D...

Страница 84: ...ems mainly occurred during space heating operation Check the space heating circuit Error code Detailed error code Description 7H 06 The water flow problems mainly occurred during cooling defrost opera...

Страница 85: ...s close the gas stop valve and stop forced cooling a c b d d e a Gas stop valve b Closing direction c Hexagonal wrench d Valve cap e Liquid stop valve 13 3 To start and stop forced cooling Confirm tha...

Страница 86: ...CuT 7 9CuT 7 9CuT 12 7CuT 12 7CuT 7 9CuT 6 4CuT 12 7CuT 12 7CuT 12 7CuT 12 7CuT 6 4CuT 7 9CuT 7 9CuT 4 0CuT 4 0CuT 4 0CuT 4 0CuT 7 9CuT 7 9CuT 7 9CuT 6 4CuT 6 4CuT M P P 6 4CuT 3TW60815 1 OUTDOOR UNIT...

Страница 87: ...fill valve Field installed Shut off valve with drain fill valve Backup heater 3 way valve Plate heat exchanger Refrigerant inlet Evaporator Condenser Refrigerant outlet Pump Drain cap Manometer Expans...

Страница 88: ...M1F Fan motor MR30 MR306 MR307 MR4 Magnetic relay MRM10 MRM20 Magnetic relay MR30_A MR30_B Connector N Neutral PCB1 Printed circuit board main PCB2 Printed circuit board inverter PCB3 Printed circuit...

Страница 89: ...ireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wirele...

Страница 90: ...ied by PCB English Translation 230 V AC supplied by PCB 230 V AC supplied by PCB Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrica...

Страница 91: ...ore main X2M 1 4 add X2M 1a 4 main X2M 1 2 3 4 add X2M 1a 2a 3 4 main X2M 1 2 4 add X2M 1a 2a 4 NC valve X2M 5 7 NO valve X2M 6 7 2 core 2 core 2 core 2 core 2 core 2 core signal 5 core 3 core 4 or 3...

Страница 92: ...0626 1 A External static pressure B Water flow rate C Operation range Operation area is extended to lower flow rates only in case the unit operates with heat pump only Not in startup no backup heater...

Страница 93: ...ain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenan...

Страница 94: ...S18CB3V HBH16CB3V HVH16S18CB3V HBX04CB3V HVX04S18CB3V HBX08CB3V HVX08S18CB3V HBX11CB3V HVX11S18CB3V HBX16CB3V HVX16S18CB3V HBH08CB9W HVH08S26CB9W HBH11CB9W HVH11S26CB9W HBH16CB9W HVH16S26CB9W HBX08CB9...

Страница 95: ...1 C 35 C 7 7 1 2 1 08 Set weather dependent cooling Leaving water value for low ambient temp for LWT main zone cooling WD curve R W 9 03 9 02 C step 1 C 22 C 7 7 1 2 1 09 Set weather dependent coolin...

Страница 96: ...Secondary rtrn 2 Disinf shunt A 2 2 B C 08 R W 0 No 1 Outdoor sensor 2 Room sensor Capacities A 2 3 1 6 02 R W 0 10kW step 0 2kW 3kW 1 0kW 2 A 2 3 2 6 03 R W 0 10kW step 0 2kW 3kW A 2 3 3 6 04 R W 0 1...

Страница 97: ...Saturday 7 Sunday A 4 4 3 2 02 R W 0 23 hour step 1 hour 23 A 4 4 4 2 03 R W E 07 1 55 80 C step 5 C 70 C E 07 1 60 C 60 C A 4 4 5 2 04 R W E 07 1 5 60 min step 5 min 10 min E 07 1 40 60 min step 5 mi...

Страница 98: ...d A 8 1 05 R W 0 Disabled 1 Enabled A 8 1 06 R W 10 25 C step 1 C 20 C A 8 1 07 R W 25 43 C step 1 C 35 C A 8 1 08 R W 9 03 9 02 C step 1 C 22 C A 8 1 09 R W 9 03 9 02 C step 1 C 18 C A 8 1 0A R W 0 N...

Страница 99: ...2 4 A 8 5 0E 1 A 8 6 00 R W 2 20 C step 1 C 2 C A 8 6 01 R W 0 10 C step 1 C 2 C The temperature difference determining the heat pump OFF temperature What is the requested limit for DI2 What is the r...

Страница 100: ...6 C step 0 5 C 1 C A 8 9 0D R W 0 8 step 1 0 100 1 4 80 50 5 8 80 50 6 A 8 9 0E 6 A 8 A 00 0 A 8 A 01 0 5 3 6 What is the maximum desired LWT for add zone in cooling What is the desired delta T in hea...

Страница 101: ...Type 1 1 Type 2 A 8 E 03 R O 0 No BUH 1 1 step 2 2 steps A 8 E 04 R O 0 No 1 Yes A 8 E 05 R W 0 No 1 1 Yes 2 A 8 E 06 R O 0 No 1 Yes A 8 E 07 R W 0 6 0 Type 1 1 1 Type 2 2 A 8 E 08 R W 0 Disabled 6 1...

Страница 102: ...A 8 F 05 0 A 8 F 06 0 A 8 F 09 R W 0 Disabled 1 Enabled A 8 F 0A 0 A 8 F 0B R W 0 No 1 Yes A 8 F 0C R W 0 No 1 Yes A 8 F 0D R W 0 Continuous 1 Sample 2 Request Close shut off valve during thermo OFF C...

Страница 103: ......

Страница 104: ...4P384973 1D 2018 07 Copyright 2015 Daikin...

Отзывы: