1 Troubleshooting
Service manual
21
EBLQ+EDLQ011~W1 + EBLQ+EDLQ011~0W1
+ EK(2)CB EKMB9W1
Daikin Altherma – Monobloc
ESIE18-04 – 2019.02
Possible cause:
Faulty hydro PCB.
2
Check if the user interface functions correctly. See
Possible cause:
Faulty user interface.
3
Check if the power supply is conform with the regulations. See
Possible cause:
▪ Faulty or disturbance of the power supply (imbalance
>10%),
▪ Power drop,
▪ Short circuit.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
1.4.58
U7-00 – Transmission abnormality
between outdoor main microcomputer -
sub microcomputer
Trigger
Effect
Reset
Communication
abnormality between
outdoor unit and
outdoor unit.
Unit will stop
operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
1
Perform a check of the main PCB. See
.
Possible cause:
Faulty main PCB.
2
Perform a check of the inverter PCB. See
.
Possible cause:
Faulty power module = inverter PCB.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
1.4.59
U8-01 – Lost LAN adapter connection
Trigger
Effect
Reset
Communication
abnormality between
indoor unit and LAN
adapter.
Unit will NOT stop
operating.
Automatic reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
1
Perform a check of the LAN adapter wiring. See
"3.4 Manuafacturer components" on page 98
.
Possible cause:
Faulty wiring of the LAN adapter.
2
Perform a check of the LAN adapter PCB. See
.
Possible cause:
Faulty LAN adapter PCB.
3
Perform a check of the hydro PCB. See
.
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
1.4.60
UA-00 – Indoor/outdoor combination
abnormality
Trigger
Effect
Reset
Signal transmission
between outdoor and
indoor unit
abnormality. Improper
combination of
outdoor and indoor
unit.
Unit will stop
operating.
Power reset via
outdoor unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
INFORMATION
In case of preferential kWh rate, the indoor unit also needs
a power reset.
1
Check for improper combination of the indoor unit and the
outdoor unit. See the combination table in the Databook for
more information.
2
Perform a check of the power supply, connections, wiring,…
between the outdoor unit, indoor unit and domestic hot water
tank. See
Possible cause:
Faulty wiring between the outdoor unit,
indoor unit and domestic hot water tank.
3
Perform a check of the main PCB. See
.
Possible cause:
Faulty main PCB.
4
Perform a check of the hydro PCB. See
.
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the
problem is still present, contact the helpdesk.
1.4.61
UA-16 – Extension/hydro communication
problem
Trigger
Effect
Reset
Communication
abnormality between
hydro PCB and
extension PCB.
Unit will not stop
operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed
order.
INFORMATION
In case of preferential kWh rate, the indoor unit also needs
a power reset.
1
Check the wiring between the hydro PCB and the extension
PCB. See