5/8
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
A.6.C
R/W
0: Manual
1: Automatic
└─ Overview settings
A.8
[0-00]
R/W
[9-05]~min(45, [9-06])°C, step: 1°C
35⁰C
A.8
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
45⁰C
A.8
[0-02]
R/W
10~25°C, step: 1°C
15⁰C
A.8
[0-03]
R/W
-40~5°C, step: 1°C
-10⁰C
A.8
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
8⁰C
A.8
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
12⁰C
A.8
[0-06]
R/W
25~43°C, step: 1°C
35⁰C
A.8
[0-07]
R/W
10~25°C, step: 1°C
20⁰C
A.8
[0-0B]
R/W
35~[6-0E]°C, step: 1°C
55⁰C
A.8
[0-0C]
R/W
45~[6-0E]°C, step: 1°C
60⁰C
A.8
[0-0D]
R/W
10~25°C, step: 1°C
15⁰C
A.8
[0-0E]
R/W
-40~5°C, step: 1°C
-10⁰C
A.8
[1-00]
R/W
-40~5°C, step: 1°C
-10°C
A.8
[1-01]
R/W
10~25°C, step: 1°C
15°C
A.8
[1-02]
R/W
[9-01]~[9-00], step: 1°C
45°C
A.8
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
35°C
A.8
[1-04]
R/W
0: Disabled
1: Enabled
A.8
[1-05]
R/W
0: Disabled
1: Enabled
A.8
[1-06]
R/W
10~25°C, step: 1°C
20°C
A.8
[1-07]
R/W
25~43°C, step: 1°C
35°C
A.8
[1-08]
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
A.8
[1-09]
R/W
[9-03]~[9-02]°C, step: 1°C
18°C
A.8
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
A.8
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.8
[2-01]
R/W
0: No
1
: Yes
A.8
[2-02]
R/W
0~23 hour, step: 1 hour
23
A.8
[2-03]
R/W
55~75°C, step: 5°C
70°C
A.8
[2-04]
R/W
5~60 min, step: 5 min
10 min
A.8
[2-05]
R/W
4~16°C, step: 1°C
16°C
A.8
[2-06]
R/W
0: Disabled
1: Enabled
A.8
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
A.8
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
A.8
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
A.8
[3-00]
R/W
0: No
1: Yes
A.8
[3-01]
0
A.8
[3-02]
1
A.8
[3-03]
4
A.8
[3-04]
2
A.8
[3-05]
1
A.8
[3-06]
R/W
18~30°C, step: A.3.2.4
30°C
A.8
[3-07]
R/W
12~18°C, step: A.3.2.4
16°C
A.8
[3-08]
R/W
25~35°C, step: A.3.2.4
35°C
A.8
[3-09]
R/W
15~25°C, step: A.3.2.4
15°C
A.8
[4-00]
R/W
0~2
0: Disabled
1: Enabled
A.8
[4-01]
R/W
0~2
0: None
1: BSH
2: BUH
A.8
[4-02]
R/W
14~35°C, step: 1°C
35
°C
What is the BUH operation mode?
Which electric heater has priority?
Below which outdoor temperature is heating allowed?
--
--
What is the maximum desired room temperature in heating?
What is the mimimum desired room temperature in heating?
What is the maximum desired room temperature in cooling?
What is the minimum desired room temperature in cooling?
Adjust the offset on the measured room temperature
What is the required offset on the measured outdoor temp.?
Is auto restart of the unit allowed?
--
--
--
When should the disinfection function start?
What is the disinfection target temperature?
How long must the tank temperature be maintained?
Room antifrost temperature
Room frost protection
Adjust the offset on the measured room temperature
High ambient temp. for LWT main zone cooling WD curve.
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
What is the averaging time for the outdoor temp?
When should the disinfection function be executed?
Should the disinfection function be executed?
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Weather dependent cooling of the main leaving water temperature zone.
Weather dependent cooling of the additional leaving water temperature zone.
Low ambient temp. for LWT main zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Low ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
(*1) *B*CAV3/CAW1_
(*2) *D*CAV3/CAW1_
(*3) *B*CA3*_(*4) *D*CA3*
4P522033-1A - 2018.06