11 Maintenance and service
Installer reference guide
71
EBLQ+EDLQ011~0W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
10.1
About locking and unlocking
If required, it is possible to lock the buttons of the main user
interface, making it impossible for the user to operate it. For the user
to be able to change setpoint temperatures, the simplified user
interface or an external room thermostat is then required.
You can use the following locking modes:
▪ Function lock: Locks a specific function to prevent people from
changing its settings.
▪ Button lock: Locks all buttons to prevent users from changing
settings.
Possible function locks
Lock
If active, people cannot…
Room On/OFF
Turn ON or OFF the room
temperature control.
LWT On/OFF
Turn ON or OFF the leaving
water temperature (main +
additional) control.
Tank On/OFF
Turn ON or OFF the domestic
hot water control.
Temperature up/down
Adjust temperatures.
Quiet mode
Use quiet mode.
Holiday
Use holiday mode.
Operation mode
Set the space operation mode.
User settings
Change settings in [7]:
> User
settings.
To check if locking is active
1
Press
to go to one of the home pages.
2
If is displayed, button lock is active.
Note:
If you are on a home page and try to use a function that is
locked, is displayed for 1 second.
To activate or deactivate a function lock
1
Press
to go to the menu structure.
2
Press
for more than 5 seconds.
3
Select a function and press
.
4
Select Lock or Unlock, and press
.
To activate or deactivate button lock
1
Press
to go to one of the home pages.
2
Press
for more than 5 seconds.
11
Maintenance and service
NOTICE
Maintenance MUST be done by an authorized installer or
service agent.
We recommend performing maintenance at least once a
year. However, applicable legislation might require shorter
maintenance intervals.
NOTICE
In Europe, the
greenhouse gas emissions
of the total
refrigerant charge in the system (expressed as tonnes CO
2
equivalent) is used to determine the maintenance intervals.
Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000
11.1
Overview: Maintenance and
service
This chapter contains information about:
▪ The yearly maintenance of the outdoor unit
▪ The inspection of the backup heater switch box.
▪ The inspection of the control box switch box.
11.2
Maintenance safety precautions
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
NOTICE: Risk of electrostatic discharge
Before performing any maintenance or service work, touch
a metal part of the unit in order to eliminate static electricity
and to protect the PCB.
11.2.1
Opening the outdoor unit
See
"7.2.2 To open the outdoor unit" on page 28
and
"7.2.3 To open
the switch box cover of the outdoor unit" on page 29
.
11.2.2
Opening the control box
See
"7.2.5 To open the control box" on page 29
.
11.2.3
Opening the option box
See
"7.2.6 To open the option box" on page 29
.
11.3
Checklist for yearly maintenance
of the outdoor unit
Check the following at least once a year:
▪ Heat exchanger
The heat exchanger of the outdoor unit can get blocked up due to
dust, dirt, leaves, etc. It is recommended to clean the heat
exchanger yearly. A blocked heat exchanger can lead to too low
pressure or too high pressure leading to worse performance.
▪ Water pressure
▪ Water filter
▪ Water pressure relief valve
▪ Pressure relief valve of the domestic hot water tank
▪ Switch box
▪ Booster heater of the domestic hot water tank
Heat exchanger
The heat exchanger of the outdoor unit can get blocked up due to
dust, dirt, leaves, etc. It is recommended to clean the heat
exchanger yearly. A blocked heat exchanger can lead to too low
pressure or too high pressure leading to worse performance.
Water pressure
Keep water pressure above 1 bar. If it is lower, add water.
Water filter
Clean the water filter.
NOTICE
Handle the water filter with care. Do NOT use excessive
force when you reinsert the water filter so as NOT to
damage the water filter mesh.