0 EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1A – 09.2010
Installation manual
41
9
Heating and cooling set point ranges
00
Heating set point upper limit
55
37~55
1
°C
01
Heating set point lower limit
25
15~37
1
°C
02
Cooling set point upper limit
22
18~22
1
°C
03
Cooling set point lower limit
5
5~18
1
°C
04
Overshoot setting
(a)
1
1~4
1
°C
C
Setup on EKRP1HB digital I/O PCB
00
Solar priority mode setting
0
0/1
1
—
01
Alarm output logic
0
0/1
—
—
02
Bivalent operation status
0
0/1
—
—
03
Bivalent ON temperature
0
–25~25
1
°C
04
Bivalent hysteresis
3
2~10
1
°C
D
Benefit kWh rate power supply/local shift value weather dependent
00
Switching off heaters
0
0/1/2/3
—
—
01
Unit connection to benefit kWh rate power supply
0 (OFF)
0/1/2
—
—
02
Not applicable. Do not change the default value.
0
—
—
—
03
Local shift value weather dependent
0
0/1/2/3/4
—
—
E
Unit information readout
00
Software version
Read
only
—
—
—
01
EEPROM version
Read
only
—
—
—
02
Unit model identification
Read
only
—
—
—
03
Liquid refrigerant temperature
Read
only
—
—
°C
04
Inlet water temperature
Read
only
—
—
°C
F
Option setup
00
Pump operation
0
0/1
—
—
01
Space cooling permission temperature
20
10~35
1
°C
02
Bottom plate heater ON temperature
3
3~10
1
°C
03
Bottom plate heater hysteresis
5
2~5
1
°C
04
Functionality of X14A.
1
0/1
—
—
(a) Only possible to modify the first 3 minutes after power ON.
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date
Value
4PW64602-1A.book Page 41 Thursday, September 23, 2010 10:40 AM