Installation manual
10
0 EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1A – 09.2010
General precautions on indoor installation location
The EKCB unit is to be wall mounted in an indoor location that meets
the following requirements:
■
The space around the unit is adequate for servicing. Refer to
"7.3. Service space" on page 10.
■
The space around the unit allows for sufficient air circulation.
■
The installation surface is a flat and vertical non-combustible
wall, capable of supporting the operation weight of the unit (refer
to the "Technical specifications" on page 47).
■
During normal operation the control box may produce sound
which could be observed as noise. The sound origin can be
contactor activation. Therefore it is advisable to install the
control box on a firm wall and not in nor close to a sound
sensitive environment (e.g. bedroom).
■
Do not install the unit in places with high humidity (e.g.
bathroom).
■
The equipment is not intended for use in a potentially explosive
atmosphere.
■
Do not install the unit in places often used as work place.
In case of construction works (e.g. grinding works) where a lot of
dust is created, the unit must be covered.
■
Do not place any objects or equipment on top of the unit.
7.
D
IMENSIONS
AND
SERVICE
SPACE
7.1.
Dimensions of outdoor unit
Unit of measurement: mm
7.2.
Dimensions of indoor unit
Unit of measurement: mm
7.3.
Service space
The space around the unit is adequate for servicing and the minimum
space for air inlet and air outlet is available. (Refer to the figure
below).
Unit of measurement: mm
The installation space required on this drawing is for full load heating
operation without considering possible ice accumulation.
If the location of the installation is in a cold climate, then all
dimensions above should be >500 mm to avoid accumulation of ice
in between the outdoor unit and the nearest walls.
■
The connection piping outlet direction in the installation shown in
the figure is frontward or downward.
■
When routing the piping backward, secure space of
≥
250 mm on
the right side of the unit.
7.4.
Service space of indoor unit
Unit of measurement: mm
CAUTION
If the installation is equipped with a domestic hot water
tank (optional), please refer to the domestic hot water tank
installation manual.
806
122
1189
22
107
84
20
360
1170
390
100
412
NOTICE
The wall height on the air outlet side (marked with grey
arrow in the figure above) must be less than 1200 mm.
NOTICE
(*) If shut off valves are directly installed on the water inlet
and outlet, increase installation space at the rear of the
unit to a minimum of 300 mm.
>350
>150
*
(>300)
>150
>50
50
50
100
50
600
4PW64602-1A.book Page 10 Thursday, September 23, 2010 10:40 AM