6 Troubleshooting

Operation manual

14

EWSAH/X06(U)DA9W

Daikin Altherma 3 WS

4P675761-2 – 2021.10

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

WARNING

▪ The  refrigerant  inside  the  unit  is  mildly  flammable,  but

normally  does  NOT  leak.  If  the  refrigerant  leaks  in  the
room  and  comes  in  contact  with  fire  from  a  burner,  a
heater,  or  a  cooker,  this  may  result  in  fire,  or  the
formation of a harmful gas.

▪ Turn  OFF  any  combustible  heating  devices,  ventilate

the room, and contact the dealer where you purchased
the unit.

▪ Do  NOT  use  the  unit  until  a  service  person  confirms

that the part from which the refrigerant leaked has been
repaired.

6

Troubleshooting

Contact

For  the  symptoms  listed  below,  you  can  try  to  solve  the  problem
yourself. For any other problem, contact your installer. You can find
the contact/helpdesk number via the user interface.

1

Go to [8.3]: 

Information

 > 

Dealer information

.

6.1

To display the help text in case of a
malfunction

In  case  of  a  malfunction,  the  following  will  appear  on  the  home
screen depending on the severity:

: Error

: Malfunction

You  can  get  a  short  and  a  long  description  of  the  malfunction  as
follows:

1

Press the left dial to open the main menu and go to

Malfunctioning

.

Result: 

A short description of the error and the error

code is displayed on the screen.

2

Press   in the error screen.

Result: 

A long description of the error is displayed

on the screen.

6.2

Symptom: You are feeling too cold
(hot) in your living room

Possible cause

Corrective action

The desired room temperature is
too low (high).

Increase (decrease) the desired
room temperature. See 

"3.4.2 To

change the desired room
temperature"

 [

4

 7].

If the problem recurs daily, do
one of the following:

▪ Increase  (decrease)  the  room

temperature  preset  value.  See
the user reference guide.

▪ Adjust  the  room  temperature

schedule.  See 

"3.7  Schedule

screen: Example"

 [

4

 9].

The desired room temperature
cannot be reached.

Increase the desired leaving
water temperature in accordance
with the heat emitter type. See

"3.4.3 To change the desired
leaving water temperature"

 [

4

 7].

The weather-dependent curve is
set incorrectly.

Adjust the weather-dependent
curve. See the user reference
guide.

6.3

Symptom: The water at the tap is
too cold

Possible cause

Corrective action

You ran out of domestic hot
water because of unusually high
consumption.

If you immediately need domestic
hot water, activate the DHW tank

Powerful operation

. However,

this consumes extra energy. See

"3.5.4 Using DHW powerful
operation"

 [

4

 8].

If the problems recurs daily, do
one of the following:

▪ Increase 

the 

DHW 

tank

temperature  preset  value.  See
the user reference guide.

▪ Adjust 

the 

DHW 

tank

temperature 

schedule.

Example: 

Program 

to

additionally 

heat 

up 

the

DHW  tank  to  a  preset  value
(

Eco  setpoint

  =  lower  tank

temperature)  during  the  day.
See 

"3.7  Schedule  screen:

Example"

 [

4

 9].

The desired DHW tank
temperature is too low.

6.4

Symptom: Heat pump failure

When  the  heat  pump  fails  to  operate,  the  backup  heater  can  serve
as  an  emergency  heater.  It  then  takes  over  the  heat  load  either
automatically or by manual interaction.

▪ When 

Emergency

  is  set  to 

Automatic

  and  a  heat  pump  failure

occurs,  the  backup  heater  automatically  takes  over  the  domestic
hot water production and space heating.

▪ When 

Emergency

  is  set  to 

Manual

  and  a  heat  pump  failure

occurs, the domestic hot water heating and space heating stops.

To  manually  recover  it  via  the  user  interface,  go  to  the

Malfunctioning

  main  menu  screen  and  confirm  whether  the

backup heater can take over the heat load or not.

Содержание Altherma 3 WS

Страница 1: ...Operation manual Daikin Altherma 3 WS English Operation manual Daikin Altherma 3 WS EWSAH06DA9W EWSAH06UDA9W EWSAX06DA9W EWSAX06UDA9W...

Страница 2: ...ables If NOT request him to do so Keep the documentation for future reference Target audience End users Documentation set This document is part of a documentation set The complete set consists of Gene...

Страница 3: ...on 3 1 User interface Overview The user interface has the following components a b c a Status indicator b LCD screen c Dials and buttons Status indicator The LEDs of the status indicator light up or b...

Страница 4: ...een with schedule 3 2 1 Home screen Press the button to go back to the home screen You see an overview of the unit configuration and the room and setpoint temperatures Only symbols applicable for your...

Страница 5: ...ning Space heating cooling a Selected submenu Possible actions on this screen Go through the list Enter the submenu Enable disable breadcrumbs Submenu Description 0 or Malfunctioning Restriction Only...

Страница 6: ...3 3 Turning operation ON or OFF 3 3 1 Visual indication Certain functionalities of the unit can be enabled or disabled separately If a functionality is disabled the corresponding temperature icon in...

Страница 7: ...etween heating and cooling based on the outdoor temperature Restricted per month according to the Operation mode schedule 4 2 To restrict automatic changeover according to a schedule Conditions You se...

Страница 8: ...domestic water entering the DHW tank example 15 C At 00 00 the DHW tank is programmed to heat up the water to a preset value example Comfort 60 C During the morning you consume hot water and the DHW t...

Страница 9: ...e and proceed User pin code The User pin code is 0000 0000 User Advanced user pin code The Advanced user pin code is 1234 Additional menu items for the user are now visible 1234 Advanced user 3 7 Sche...

Страница 10: ...ogrammed action In this example Monday is the first day you programmed Thus the last programmed action is valid up to the first action of next Monday To copy the schedule to the other weekdays 1 Selec...

Страница 11: ...ename Select 3 optional To delete the current schedule name browse through the character list until is displayed then press to remove the previous character Repeat for each character of the schedule n...

Страница 12: ...D curve type 7 User settings Language Time date Holiday Quiet Electricity price Gas price 8 Information Energy data Malfunction history Dealer information Sensors Actuators Operation modes About Conne...

Страница 13: ...scheduled action Example When you have a party or when you are leaving for a couple of hours For longer periods You can use the holiday mode Tips about DHW tank temperature Use a weekly schedule for y...

Страница 14: ...cause Corrective action The desired room temperature is too low high Increase decrease the desired room temperature See 3 4 2 To change the desired room temperature 47 If the problem recurs daily do o...

Страница 15: ...mitters 2 If hydraulic balancing is not sufficient change the pump limitation settings 9 0D and 9 0E if applicable Various malfunctions Check if or is displayed on the home screen of the user interfac...

Страница 16: ...4P675761 2 2021 10 Copyright 2021 Daikin 4P675761 2 0000000V Verantwortung f r Energie und Umwelt...

Отзывы: