3 Operation

Operation manual

8

EWSAH/X06(U)DA9W

Daikin Altherma 3 WS

4P675761-2 – 2021.10

1

Go to [2]: 

Main zone

 or [3]: 

Additional zone

.

Main zone

2

Additional zone

3

2

Adjust the desired leaving water temperature.

+

35

°C

2

a

b

Main zone

+

45

°C

3

a

b

Additional zone

a

 Actual leaving water temperature

b

 Desired leaving water temperature

3.5

Domestic hot water control

3.5.1

Reheat mode

In  reheat  mode,  the  DHW  tank  continuously  heats  up  to  the
temperature  shown  on  the  home  screen  (example:  50°C)  when  the
temperature drops below a certain value.

t

60°C

00:00

07:00

50°C

15°C

40°C

14:00

21:00

1

2

3

4

Tt

T

t

DHW tank temperature

t

Time

INFORMATION

When  the  DHW  tank  mode  is  reheat,  the  risk  for  capacity
shortage  and  comfort  problem  is  significant.  In  case  of
frequent  reheat  operation,  space  heating/cooling  function
is regularly interrupted.

3.5.2

Scheduled mode

In  scheduled  mode,  the  DHW  tank  produces  hot  water
corresponding  to  a  schedule.  The  best  time  to  allow  the  tank  to
produce hot water is at night, because the space heating demand is
lower.

Example: 

t

60°C

00:00

07:00

50°C

15°C

40°C

14:00

21:00

1

2

3

4

5

Tt

T

t

DHW tank temperature

t

Time

▪ Initially,  the  DHW  tank  temperature  is  the  same  as  the

temperature  of  the  domestic  water  entering  the  DHW  tank
(example: 

15°C

).

▪ At 00:00 the DHW tank is programmed to heat up the water to a

preset value (example: 

Comfort

 = 

60°C

).

▪ During  the  morning,  you  consume  hot  water  and  the  DHW  tank

temperature decreases.

▪ At 14:00 the DHW tank is programmed to heat up the water to a

preset value (example: 

Eco

 = 

50°C

). Hot water is available again.

▪ During  the  afternoon  and  evening,  you  consume  hot  water  again

and the DHW tank temperature decreases again.

▪ At 00:00 the next day, the cycle repeats.

3.5.3

Sch reheat mode

In  scheduled  +  reheat  mode,  the  domestic  hot  water  control  is  the
same  as  in  scheduled  mode.  However,  when  the  DHW  tank
temperature drops below a preset value (=reheat tank temperature –
hysteresis  value;  example:  35°C),  the  DHW  tank  heats  up  until  it
reaches  the  reheat  set  point  (example:  45°C).  This  ensures  that  a
minimum amount of hot water is available at all times.

Example: 

t

Tt

60°C

00:00

07:00

50°C

45°C

15°C

14:00

21:00

35°C

1

2

4

5

3

T

t

Domestic hot water tank temperature

t

Time

3.5.4

Using DHW powerful operation

About powerful operation

Powerful operation

 allows the domestic hot water to be heated by

the  backup  heater.  Use  this  mode  on  days  when  there  is  more  hot
water usage than usual.

To check if powerful operation is active

If 

 is displayed on the home screen, powerful operation is active.

Activate or deactivate 

Powerful operation

 as follows:

1

Go to [5.1]: 

Tank

 > 

Powerful operation

Содержание Altherma 3 WS

Страница 1: ...Operation manual Daikin Altherma 3 WS English Operation manual Daikin Altherma 3 WS EWSAH06DA9W EWSAH06UDA9W EWSAX06DA9W EWSAX06UDA9W...

Страница 2: ...ables If NOT request him to do so Keep the documentation for future reference Target audience End users Documentation set This document is part of a documentation set The complete set consists of Gene...

Страница 3: ...on 3 1 User interface Overview The user interface has the following components a b c a Status indicator b LCD screen c Dials and buttons Status indicator The LEDs of the status indicator light up or b...

Страница 4: ...een with schedule 3 2 1 Home screen Press the button to go back to the home screen You see an overview of the unit configuration and the room and setpoint temperatures Only symbols applicable for your...

Страница 5: ...ning Space heating cooling a Selected submenu Possible actions on this screen Go through the list Enter the submenu Enable disable breadcrumbs Submenu Description 0 or Malfunctioning Restriction Only...

Страница 6: ...3 3 Turning operation ON or OFF 3 3 1 Visual indication Certain functionalities of the unit can be enabled or disabled separately If a functionality is disabled the corresponding temperature icon in...

Страница 7: ...etween heating and cooling based on the outdoor temperature Restricted per month according to the Operation mode schedule 4 2 To restrict automatic changeover according to a schedule Conditions You se...

Страница 8: ...domestic water entering the DHW tank example 15 C At 00 00 the DHW tank is programmed to heat up the water to a preset value example Comfort 60 C During the morning you consume hot water and the DHW t...

Страница 9: ...e and proceed User pin code The User pin code is 0000 0000 User Advanced user pin code The Advanced user pin code is 1234 Additional menu items for the user are now visible 1234 Advanced user 3 7 Sche...

Страница 10: ...ogrammed action In this example Monday is the first day you programmed Thus the last programmed action is valid up to the first action of next Monday To copy the schedule to the other weekdays 1 Selec...

Страница 11: ...ename Select 3 optional To delete the current schedule name browse through the character list until is displayed then press to remove the previous character Repeat for each character of the schedule n...

Страница 12: ...D curve type 7 User settings Language Time date Holiday Quiet Electricity price Gas price 8 Information Energy data Malfunction history Dealer information Sensors Actuators Operation modes About Conne...

Страница 13: ...scheduled action Example When you have a party or when you are leaving for a couple of hours For longer periods You can use the holiday mode Tips about DHW tank temperature Use a weekly schedule for y...

Страница 14: ...cause Corrective action The desired room temperature is too low high Increase decrease the desired room temperature See 3 4 2 To change the desired room temperature 47 If the problem recurs daily do o...

Страница 15: ...mitters 2 If hydraulic balancing is not sufficient change the pump limitation settings 9 0D and 9 0E if applicable Various malfunctions Check if or is displayed on the home screen of the user interfac...

Страница 16: ...4P675761 2 2021 10 Copyright 2021 Daikin 4P675761 2 0000000V Verantwortung f r Energie und Umwelt...

Отзывы: