7 Configuration

Installation manual

30

EBBH/X11+16DF

Daikin Altherma 3 R W

4P643600-1B – 2021.10

▪ When 

Emergency

  is  set  to 

Manual

  and  a  heat  pump  failure

occurs, the domestic hot water heating and space heating stops.

To  manually  recover  it  via  the  user  interface,  go  to  the

Malfunctioning

  main  menu  screen  and  confirm  whether  the

backup heater and/or booster heater can take over the heat load
or not.

▪ Alternatively, when 

Emergency

 is set to:

auto  SH  reduced/DHW  on

,  space  heating  is  reduced  but

domestic hot water is still available.

auto  SH  reduced/DHW  off

,  space  heating  is  reduced  and

domestic hot water is NOT available.

auto  SH  normal/DHW  off

,  space  heating  operates  as

normally but domestic hot water is NOT available.

Similarly  as  in 

Manual

  mode,  the  unit  can  take  the  full  load  with

the backup heater and/or booster heater if the user activates this
via the 

Malfunctioning

 main menu screen.

To keep energy consumption low, we recommend to set 

Emergency

to 

auto SH reduced/DHW off

 if the house is unattended for longer

periods.

#

Code

Description

[9.5.1]

[4-06]

▪ 0: 

Manual

▪ 1: 

Automatic

▪ 2: 

auto SH reduced/DHW on

▪ 3: 

auto SH reduced/DHW off

▪ 4: 

auto SH normal/DHW off

INFORMATION

The  auto  emergency  setting  can  be  set  in  the  menu
structure of the user interface only.

INFORMATION

If [4‑03]=1 or 3, then 

Emergency

 = 

Manual

 is not applicable

for the booster heater.

INFORMATION

If a heat pump failure occurs and 

Emergency

 is not set to

Automatic

  (setting  1),  the  room  frost  protection  function

and  the  underfloor  heating  screed  dryout  function  will
remain  active  even  if  the  user  does  NOT  confirm
emergency operation.

Number of zones

The  system  can  supply  leaving  water  to  up  to  2  water  temperature
zones. During configuration, the number of water zones must be set.

INFORMATION

Mixing  station.

  If  your  system  layout  contains  2  LWT

zones,  you  need  to  install  a  mixing  station  in  front  of  the
main LWT zone.

#

Code

Description

[4.4]

[7‑02]

▪ 0: 

Single zone

Only  one  leaving  water  temperature
zone:

a

a

 Main LWT zone

[4.4]

[7‑02]

▪ 1: 

Dual zone

Two leaving water temperature zones.
The  main  leaving  water  temperature
zone  consists  of  the  higher  load  heat
emitters  and  a  mixing  station  to
achieve  the  desired  leaving  water
temperature. In heating:

a

b

c

a

 Additional LWT zone: Highest

temperature

b

 Main LWT zone: Lowest temperature

c

 Mixing station

NOTICE

NOT configuring the system in the following way can cause
damage  to  the  heat  emitters.  If  there  are  2  zones,  it  is
important that in heating:

▪ the  zone  with  the  lowest  water  temperature  is

configured as the main zone, and

▪ the  zone  with  the  highest  water  temperature  is

configured as the additional zone.

NOTICE

If  there  are  2  zones  and  the  emitter  types  are  wrongly
configured, water of high temperature can be sent towards
a  low  temperature  emitter  (underfloor  heating).  To  avoid
this:

▪ Install an aquastat/thermostatic valve to avoid too high

temperatures towards a low temperature emitter.

▪ Make sure you set the emitter types for the main zone

[2.7]  and  for  the  additional  zone  [3.7]  correctly  in
accordance with the connected emitter.

NOTICE

An  overpressure  bypass  valve  can  be  integrated  in  the
system.  Keep  in  mind  that  this  valve  might  not  be  shown
on the illustrations.

All manuals and user guides at all-guides.com

Содержание Altherma 3 R W Series

Страница 1: ...eu Installation manual Daikin Altherma 3 R W English Installation manual Daikin Altherma 3 R W EBBH11DF6V EBBH11DF9W EBBH16DF6V EBBH16DF9W EBBX11DF6V EBBX11DF9W EBBX16DF6V EBBX16DF9W All manuals and u...

Страница 2: ...om o previsto em 10 11 12 13 14 15 16 17 18 under iagttagelse af bestemmelserne i enligt villkoren i gitt i henhold til bestemmelsene i noudattaen m r yksi za dodr en ustanoven p edpisu prema odredbam...

Страница 3: ...tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin Minim ln tepl...

Страница 4: ...uration wizard Time and date 29 7 2 3 Configuration wizard System 29 7 2 4 Configuration wizard Backup heater 31 7 2 5 Configuration wizard Main zone 31 7 2 6 Configuration wizard Additional zone 32 7...

Страница 5: ...ns in this manual for correct installation of the unit See 4 1 1 Installation site requirements of the indoor unit 46 Special requirements for R32 see 4 1 2 Special requirements for R32 units 47 WARNI...

Страница 6: ...from the heat emitters or collectors 3 About the box 3 1 Indoor unit At delivery the unit MUST be checked for damage Any damage MUST be reported immediately to the claims agent of the carrier Bring t...

Страница 7: ...stallation patterns 48 WARNING Do NOT pierce or burn Do NOT use means to accelerate the defrosting process or to clean the equipment other than those recommended by the manufacturer Be aware that R32...

Страница 8: ...t b Chimney c1 Bottom opening for natural ventilation c2 Top opening for natural ventilation Hrelease Actual release height 1a 2a Without chimney From floor to top of the unit minimum 1 95 m 1b 2b Wit...

Страница 9: ...release height without chimney START PATTERN 1 PATTERN 2 PATTERN 2 Conditions ventilation openings If you want to take advantage of the floor area of the adjacent room you must provide 2 openings one...

Страница 10: ...nditions ventilation openings on previous page See table 3 For H1 Can the maximum chimney length be respected and is the chimney practically feasible See table 2 Do you need a chimney or not i e does...

Страница 11: ...6 98 6 48 6 10 5 89 4 5 16 32 14 76 13 42 12 26 11 23 10 34 9 54 8 84 8 20 7 64 7 13 5 20 14 18 23 16 57 15 13 13 87 12 76 11 78 10 91 10 13 9 43 8 80 5 5 24 37 22 05 20 05 18 31 16 78 15 44 14 25 13...

Страница 12: ...rrect table For intermediate refrigerant charges use the table with the higher value Example If the refrigerant charge is 4 3 kg use the table of 4 8 kg For intermediate floor areas use the column wit...

Страница 13: ...the unoccupied room If the opening starts from the floor the height of the opening must be 20 mm a2 Top opening for natural ventilation between room A and the outside Must be a permanent opening that...

Страница 14: ...all the front panel NOTICE When closing the indoor unit cover make sure that the tightening torque does NOT exceed 4 1 N m 4 3 Mounting the indoor unit 4 3 1 To install the indoor unit 1 Fix the wall...

Страница 15: ...Piping diameter Liquid piping 9 5 mm 3 8 Gas piping 15 9 mm 5 8 Piping temper grade and thickness Outer diameter Temper grade Thickness t a 9 5 mm 3 8 Annealed O 0 8 mm t 15 9 mm 5 8 Annealed O 1 0 m...

Страница 16: ...rate in the installation is guaranteed in all conditions For this purpose use the overpressure bypass valve delivered with the unit and respect the minimum water volume If operation is Then the minimu...

Страница 17: ...agnetic filter and one on the backup heater are open 5 4 3 To fill the domestic hot water tank See the installation manual of the domestic hot water tank 5 4 4 To insulate the water piping The piping...

Страница 18: ...e outdoor sensor Addendum book for optional equipment Wires 2 0 75 mm 9 B 1 1 External sensor Outdoor 9 B 2 Ext amb sensor offset 9 B 3 Averaging time Item Description Remote indoor sensor See Install...

Страница 19: ...anual of the wireless room thermostat Addendum book for optional equipment Wired room thermostat without multi zoning base unit Installation manual of the wired room thermostat Addendum book for optio...

Страница 20: ...Wh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indoor unit is required if preferential kWh rate power supply is inte...

Страница 21: ...he user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipme...

Страница 22: ...rent for a NC normally closed valve and a NO normally open valve B C A A B C A A M2S NO NC C 5 6 X2M C 21 28 X2M C 5 6 X2M C 21 29 X2M B X2M 3 Fix the cable with cable ties to the cable tie mountings...

Страница 23: ...413 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y1 X2M 1 2 3 A4P 1 2 Wires connected to...

Страница 24: ...ivalent 1 Open the following see 4 2 1 To open the indoor unit 413 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the changeover to external heat source cable to the appropriate termina...

Страница 25: ...with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the safe...

Страница 26: ...follows B C A A X5M 4 X5M 3 S4S X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 C B X5M X5M 3 4 5 6 9 10 13 14 2 Fix the cables with cable ties to the cable tie mountings In case of high voltage Smart Grid con...

Страница 27: ...e mountings If necessary bundle excessive cable length with a cable tie 7 Configuration INFORMATION Cooling is only applicable in case of Reversible models Heating only models conversion kit EKHBCONV...

Страница 28: ...he most used commands To change the user permission level You can change the user permission level as follows 1 Go to B User profile User profile B 2 Enter the applicable pin code for the user permiss...

Страница 29: ...g according to the actual installation Code Description 9 2 1 E 05 a E 06 a E 07 a No DHW No tank installed EKHWS E small volume Tank with booster heater installed at the side of the tank with a volum...

Страница 30: ...t function will remain active even if the user does NOT confirm emergency operation Number of zones The system can supply leaving water to up to 2 water temperature zones During configuration the numb...

Страница 31: ...0A 0 Relay 1 1 Relay 1 Relay 1 2 2 Relay 1 Relay 2 3 Relay 1 Relay 2 Emergency Relay 1 2 INFORMATION Settings 9 3 3 and 9 3 5 are linked Changing one setting influences the other If you change one che...

Страница 32: ...er can shift the water temperature up or down by a maximum of 10 C Schedule Indicates if the desired leaving water temperature is according to a schedule Influence of the LWT setpoint mode 2 4 is as f...

Страница 33: ...during storage comfort to prioritize the domestic hot water preparation When the tank temperature rises above this value domestic hot water preparation and space heating cooling are executed sequentia...

Страница 34: ...l ambient temperatures Examples Weather dependent curve when slope is selected X1 X2 c d e Y1 Y2 Y3 Y4 a b Weather dependent curve when offset is selected Y1 Y2 Y3 Y4 X1 X2 a b c d e Item Description...

Страница 35: ...mperatures At cold outdoor temperatures Slope Offset OK Cold OK Hot Cold OK Cold Cold Cold Hot Hot OK Hot Cold Hot Hot To fine tune the weather dependent curve 2 points curve The following table descr...

Страница 36: ...tpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor Ext amb sensor offset Ave...

Страница 37: ...r unit is properly mounted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel...

Страница 38: ...orm an operation test run Conditions Make sure all operation is disabled Go to C Operation and turn off Space heating cooling and Tank operation 1 Set the user permission level to Installer See To cha...

Страница 39: ...r on site mode see Commissioning room frost protection will be automatically disabled for 12 hours after the first power on If the screed dryout still needs to be performed after the first 12 hours of...

Страница 40: ...r C Field installed a1 Space heating cooling Water IN screw connection 1 Thermistors a2 Space heating cooling Water OUT screw connection 1 R1T Heat exchanger Water OUT b1 Gas refrigerant IN heating mo...

Страница 41: ...OFF thermostat wireless ON OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired ON O...

Страница 42: ...xing kit Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid...

Страница 43: ...ace Only for Human Comfort Interface Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for...

Страница 44: ...4P643600 1B 2021 10 Copyright 2021 Daikin 4P643600 1 B 0000000X Verantwortung f r Energie und Umwelt All manuals and user guides at all guides com...

Отзывы: