background image

8 Commissioning

Installation manual

38

EBBH/X11+16DF

Daikin Altherma 3 R W

4P643600-1B – 2021.10

Underfloor screed dryout function

The  underfloor  screed  dryout  function  is  started  (if
necessary).

8.2.1

To check the minimum flow rate

1

Check the hydraulic configuration to find out which
space heating loops can be closed by mechanical,
electronic, or other valves.

2

Close all space heating loops that can be closed.

3

Start the pump test run (see 

"8.2.4 To perform an

actuator test run"

 [

4

 38]).

4

Read out the flow rate

(a)

 and modify the bypass valve

setting to reach the minimum required flow rate + 2 l/
min.

(a)

During pump test run, the unit can operate below the minimum
required flow rate.

If operation is…

Then the minimum required

flow rate is…

Cooling

16 l/min

Heating/defrost

22 l/min

Domestic hot water production

8.2.2

To perform an air purge

Conditions: 

Make  sure  all  operation  is  disabled.  Go  to  [C]:

Operation

  and  turn  off 

Space  heating/cooling

  and 

Tank

operation.

1

Set the user permission level to Installer. See 

"To

change the user permission level"

 [

4

 28].

2

Go to [A.3]: 

Commissioning

 > 

Air purge

.

3

Select 

OK

 to confirm.

Result: 

The air purge starts. It stops automatically

when air purge cycle is finished.

To stop the air purge manually:

1

Go to 

Stop air purge

.

2

Select 

OK

 to confirm.

Air purging heat emitters or collectors

We  recommend  to  purge  air  with  the  unit's  air  purge  function  (see
above).  However,  if  you  purge  air  from  the  heat  emitters  or
collectors, mind the following:

WARNING

Air  purging  heat  emitters  or  collectors.

  Before  you

purge  air  from  heat  emitters  or  collectors,  check  if 

  or

 is displayed on the home screen of the user interface.

▪ If not, you can purge air immediately.

▪ If  yes,  make  sure  that  the  room  where  you  want  to

purge air is sufficiently ventilated. 

Reason:

 Refrigerant

might leak into the water circuit, and subsequently into
the room when you purge air from the heat emitters or
collectors.

8.2.3

To perform an operation test run

Conditions: 

Make  sure  all  operation  is  disabled.  Go  to  [C]:

Operation

  and  turn  off 

Space  heating/cooling

  and 

Tank

operation.

1

Set the user permission level to 

Installer

. See 

"To

change the user permission level"

 [

4

 28].

2

Go to [A.1]: 

Commissioning

 > 

Operation test

run

.

3

Select a test from the list. 

Example: 

Heating

.

4

Select 

OK

 to confirm.

Result: 

The test run starts. It stops automatically

when ready (±30 min).

To stop the test run manually:

1

In the menu, go to 

Stop test run

.

2

Select 

OK

 to confirm.

INFORMATION

If  the  outdoor  temperature  is  outside  the  range  of
operation,  the  unit  may  NOT  operate  or  may  NOT  deliver
the required capacity.

To monitor leaving water and tank temperatures

During test run, the correct operation of the unit can be checked by
monitoring its leaving water temperature (heating/cooling mode) and
tank temperature (domestic hot water mode).

To monitor the temperatures:

1

In the menu, go to 

Sensors

.

2

Select the temperature information.

8.2.4

To perform an actuator test run

Conditions: 

Make  sure  all  operation  is  disabled.  Go  to  [C]:

Operation

  and  turn  off 

Space  heating/cooling

  and 

Tank

operation.

Purpose

Perform an actuator test run to confirm the operation of the different
actuators.  For  example,  when  you  select 

Pump

,  a  test  run  of  the

pump will start.

1

Set the user permission level to Installer. See 

"To

change the user permission level"

 [

4

 28].

2

Go to [A.2]: 

Commissioning

 > 

Actuator test run

.

3

Select a test from the list. 

Example: 

Pump

.

4

Select 

OK

 to confirm.

Result: 

The actuator test run starts. It stops

automatically when ready (±30 min).

To stop the test run manually:

1

In the menu, go to 

Stop test run

.

2

Select 

OK

 to confirm.

Possible actuator test runs

Booster heater

 test

Backup heater 1

 test

Backup heater 2

 test

Pump

 test

INFORMATION

Make  sure  that  all  air  is  purged  before  executing  the  test
run. Also avoid disturbances in the water circuit during the
test run.

Shut off valve

 test

Diverter  valve

  test  (3-way  valve  for  switching  between  space

heating and tank heating)

Bivalent signal

 test

Alarm output

 test

C/H signal

 test

DHW pump

 test

All manuals and user guides at all-guides.com

Содержание Altherma 3 R W Series

Страница 1: ...eu Installation manual Daikin Altherma 3 R W English Installation manual Daikin Altherma 3 R W EBBH11DF6V EBBH11DF9W EBBH16DF6V EBBH16DF9W EBBX11DF6V EBBX11DF9W EBBX16DF6V EBBX16DF9W All manuals and u...

Страница 2: ...om o previsto em 10 11 12 13 14 15 16 17 18 under iagttagelse af bestemmelserne i enligt villkoren i gitt i henhold til bestemmelsene i noudattaen m r yksi za dodr en ustanoven p edpisu prema odredbam...

Страница 3: ...tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin Minim ln tepl...

Страница 4: ...uration wizard Time and date 29 7 2 3 Configuration wizard System 29 7 2 4 Configuration wizard Backup heater 31 7 2 5 Configuration wizard Main zone 31 7 2 6 Configuration wizard Additional zone 32 7...

Страница 5: ...ns in this manual for correct installation of the unit See 4 1 1 Installation site requirements of the indoor unit 46 Special requirements for R32 see 4 1 2 Special requirements for R32 units 47 WARNI...

Страница 6: ...from the heat emitters or collectors 3 About the box 3 1 Indoor unit At delivery the unit MUST be checked for damage Any damage MUST be reported immediately to the claims agent of the carrier Bring t...

Страница 7: ...stallation patterns 48 WARNING Do NOT pierce or burn Do NOT use means to accelerate the defrosting process or to clean the equipment other than those recommended by the manufacturer Be aware that R32...

Страница 8: ...t b Chimney c1 Bottom opening for natural ventilation c2 Top opening for natural ventilation Hrelease Actual release height 1a 2a Without chimney From floor to top of the unit minimum 1 95 m 1b 2b Wit...

Страница 9: ...release height without chimney START PATTERN 1 PATTERN 2 PATTERN 2 Conditions ventilation openings If you want to take advantage of the floor area of the adjacent room you must provide 2 openings one...

Страница 10: ...nditions ventilation openings on previous page See table 3 For H1 Can the maximum chimney length be respected and is the chimney practically feasible See table 2 Do you need a chimney or not i e does...

Страница 11: ...6 98 6 48 6 10 5 89 4 5 16 32 14 76 13 42 12 26 11 23 10 34 9 54 8 84 8 20 7 64 7 13 5 20 14 18 23 16 57 15 13 13 87 12 76 11 78 10 91 10 13 9 43 8 80 5 5 24 37 22 05 20 05 18 31 16 78 15 44 14 25 13...

Страница 12: ...rrect table For intermediate refrigerant charges use the table with the higher value Example If the refrigerant charge is 4 3 kg use the table of 4 8 kg For intermediate floor areas use the column wit...

Страница 13: ...the unoccupied room If the opening starts from the floor the height of the opening must be 20 mm a2 Top opening for natural ventilation between room A and the outside Must be a permanent opening that...

Страница 14: ...all the front panel NOTICE When closing the indoor unit cover make sure that the tightening torque does NOT exceed 4 1 N m 4 3 Mounting the indoor unit 4 3 1 To install the indoor unit 1 Fix the wall...

Страница 15: ...Piping diameter Liquid piping 9 5 mm 3 8 Gas piping 15 9 mm 5 8 Piping temper grade and thickness Outer diameter Temper grade Thickness t a 9 5 mm 3 8 Annealed O 0 8 mm t 15 9 mm 5 8 Annealed O 1 0 m...

Страница 16: ...rate in the installation is guaranteed in all conditions For this purpose use the overpressure bypass valve delivered with the unit and respect the minimum water volume If operation is Then the minimu...

Страница 17: ...agnetic filter and one on the backup heater are open 5 4 3 To fill the domestic hot water tank See the installation manual of the domestic hot water tank 5 4 4 To insulate the water piping The piping...

Страница 18: ...e outdoor sensor Addendum book for optional equipment Wires 2 0 75 mm 9 B 1 1 External sensor Outdoor 9 B 2 Ext amb sensor offset 9 B 3 Averaging time Item Description Remote indoor sensor See Install...

Страница 19: ...anual of the wireless room thermostat Addendum book for optional equipment Wired room thermostat without multi zoning base unit Installation manual of the wired room thermostat Addendum book for optio...

Страница 20: ...Wh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indoor unit is required if preferential kWh rate power supply is inte...

Страница 21: ...he user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipme...

Страница 22: ...rent for a NC normally closed valve and a NO normally open valve B C A A B C A A M2S NO NC C 5 6 X2M C 21 28 X2M C 5 6 X2M C 21 29 X2M B X2M 3 Fix the cable with cable ties to the cable tie mountings...

Страница 23: ...413 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y1 X2M 1 2 3 A4P 1 2 Wires connected to...

Страница 24: ...ivalent 1 Open the following see 4 2 1 To open the indoor unit 413 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the changeover to external heat source cable to the appropriate termina...

Страница 25: ...with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the safe...

Страница 26: ...follows B C A A X5M 4 X5M 3 S4S X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 C B X5M X5M 3 4 5 6 9 10 13 14 2 Fix the cables with cable ties to the cable tie mountings In case of high voltage Smart Grid con...

Страница 27: ...e mountings If necessary bundle excessive cable length with a cable tie 7 Configuration INFORMATION Cooling is only applicable in case of Reversible models Heating only models conversion kit EKHBCONV...

Страница 28: ...he most used commands To change the user permission level You can change the user permission level as follows 1 Go to B User profile User profile B 2 Enter the applicable pin code for the user permiss...

Страница 29: ...g according to the actual installation Code Description 9 2 1 E 05 a E 06 a E 07 a No DHW No tank installed EKHWS E small volume Tank with booster heater installed at the side of the tank with a volum...

Страница 30: ...t function will remain active even if the user does NOT confirm emergency operation Number of zones The system can supply leaving water to up to 2 water temperature zones During configuration the numb...

Страница 31: ...0A 0 Relay 1 1 Relay 1 Relay 1 2 2 Relay 1 Relay 2 3 Relay 1 Relay 2 Emergency Relay 1 2 INFORMATION Settings 9 3 3 and 9 3 5 are linked Changing one setting influences the other If you change one che...

Страница 32: ...er can shift the water temperature up or down by a maximum of 10 C Schedule Indicates if the desired leaving water temperature is according to a schedule Influence of the LWT setpoint mode 2 4 is as f...

Страница 33: ...during storage comfort to prioritize the domestic hot water preparation When the tank temperature rises above this value domestic hot water preparation and space heating cooling are executed sequentia...

Страница 34: ...l ambient temperatures Examples Weather dependent curve when slope is selected X1 X2 c d e Y1 Y2 Y3 Y4 a b Weather dependent curve when offset is selected Y1 Y2 Y3 Y4 X1 X2 a b c d e Item Description...

Страница 35: ...mperatures At cold outdoor temperatures Slope Offset OK Cold OK Hot Cold OK Cold Cold Cold Hot Hot OK Hot Cold Hot Hot To fine tune the weather dependent curve 2 points curve The following table descr...

Страница 36: ...tpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor Ext amb sensor offset Ave...

Страница 37: ...r unit is properly mounted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel...

Страница 38: ...orm an operation test run Conditions Make sure all operation is disabled Go to C Operation and turn off Space heating cooling and Tank operation 1 Set the user permission level to Installer See To cha...

Страница 39: ...r on site mode see Commissioning room frost protection will be automatically disabled for 12 hours after the first power on If the screed dryout still needs to be performed after the first 12 hours of...

Страница 40: ...r C Field installed a1 Space heating cooling Water IN screw connection 1 Thermistors a2 Space heating cooling Water OUT screw connection 1 R1T Heat exchanger Water OUT b1 Gas refrigerant IN heating mo...

Страница 41: ...OFF thermostat wireless ON OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired ON O...

Страница 42: ...xing kit Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid...

Страница 43: ...ace Only for Human Comfort Interface Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for...

Страница 44: ...4P643600 1B 2021 10 Copyright 2021 Daikin 4P643600 1 B 0000000X Verantwortung f r Energie und Umwelt All manuals and user guides at all guides com...

Отзывы: