6 Electrical installation

Installation manual

19

ELBH/X12E
Daikin Altherma 3 R MT W
4P708482-1 – 2023.03

WARNING

The backup heater MUST have a dedicated power supply
and MUST be protected by the safety devices required by
the applicable legislation.

CAUTION

If the indoor unit has a tank with a built‑in electrical booster
heater, use a dedicated power circuit for the backup heater
and booster heater. NEVER use a power circuit shared by
another  appliance.  This  power  circuit  MUST  be  protected
with the required safety devices according to the applicable
legislation.

CAUTION

To  guarantee  the  unit  is  completely  earthed,  ALWAYS
connect  the  backup  heater  power  supply  and  the  earth
cable.

The backup heater capacity can vary, depending on the indoor unit
model.  Make  sure  that  the  power  supply  is  in  accordance  with  the
backup heater capacity, as listed in the table below.

Backup

heater type

Backup

heater

capacity

Power

supply

Maximum

running

current

Z

max

*6V

2 kW

1N~ 230 V

(a)

9 A

4 kW

1N~ 230 V

(a)

17 A

(b)(c)

0.22 Ω

6 kW

1N~ 230 V

(a)

26 A

(b)(c)

0.22 Ω

2 kW

3~ 230 V

(d)

5 A

4 kW

3~ 230 V

(d)

10 A

6 kW

3~ 230 V

(d)

15 A

*9W

3 kW

3N~ 400 V

4 A

6 kW

3N~ 400 V

9 A

9 kW

3N~ 400 V

13 A

(a)

6V3

(b)

Electrical equipment complying with EN/IEC 61000-3-12
(European/International Technical Standard setting the limits for
harmonic currents produced by equipment connected to public
low-voltage systems with input current >16 A and ≤75 A per
phase).

(c)

This equipment complies with EN/IEC 61000‑3‑11 (European/
International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage
supply systems for equipment with rated current ≤75 A) provided
that the system impedance Z

sys

 is less than or equal to Z

max

 at the

interface point between the user's supply and the public system. It
is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with
a system impedance Z

sys

 less than or equal to Z

max

.

(d)

6T1

Connect the backup heater power supply as follows:

a

b

X6M

F1B

Q1DI

a

Factory-mounted cable connected to the contactor of the
backup heater, inside the switch box (K5M)

b

Field wiring (see table below)

Model (power

supply)

Connections to backup heater power

supply

*6V (6V3: 1N~ 230 V)

1N~, 50 Hz

230 V AC

SWB

4
3

6
5

2
1

K5M

(14) 8
(13) 7

Q1DI

1

2

3

4

5

6

7

8

F1B

I

I

I

I

N

L

X6M

BRN

GRY

BLU1

BLU2

*6V (6T1: 3~ 230 V)

SWB

3~, 50 Hz

230 V AC

4
3

6
5

2
1

K5M

(14) 8
(13) 7

1

2

3

4

5

6

7

8

F1B

I

I

I

I

Q1DI

L1 L2 L3

X6M

BRN

GRY

BLU1

BLU2

*9W (3N~ 400 V)

3N~, 50 Hz

400 V AC

SWB

Q1DI

L1 L2 L3 N

1

2

3

4

5

6

7

8

F1B

I

I

I

I

X6M

2
1

K5M

4
3

6
5

(14) 8
(13) 7

BRN

GRY

BLK

BLU

F1B 

Overcurrent fuse (field supply). Recommended fuse:
4‑pole; 20 A; curve 400 V; tripping class C.

K5M

Safety contactor (in the switch box)

Q1DI

Earth leakage circuit breaker (field supply)

SWB

Switch box

X6M

Terminal (field supply)

Содержание Altherma 3 R MT W

Страница 1: ...Installation manual Daikin Altherma 3 R MT W English Installation manual Daikin Altherma 3 R MT W ELBH12E 6V ELBH12E 9W ELBX12E 6V ELBX12E 9W 1 2 3 9 A B C Z 1 2 3 9 https daikintechnicaldatahub eu...

Страница 2: ...To access the most used commands 26 7 2 Configuration wizard 27 7 2 1 Configuration wizard Language 27 7 2 2 Configuration wizard Time and date 27 7 2 3 Configuration wizard System 27 7 2 4 Configurat...

Страница 3: ...ance or an operating electric heater WARNING DO NOT reuse refrigerant piping that has been used with any other refrigerant Replace the refrigerant pipes or clean thoroughly WARNING Follow the service...

Страница 4: ...ct the backup heater power supply and the earth cable INFORMATION Details of type and rating of fuses or rating of circuit breakers are described in 6 Electrical installation 415 Commissioning see 8 C...

Страница 5: ...it at a minimum distance of 1 m from other heat sources 80 C e g electrical heater oil heater chimney and combustible materials Otherwise the unit may be damaged or in extreme cases catch fire Mind th...

Страница 6: ...minimum 1 95 m 1b 2b With chimney From floor to top of the chimney 3a Installation with chimney connected to the outside The release height is not relevant There are no requirements to the minimum fl...

Страница 7: ...charge and the given release height without chimney START PATTERN 1 PATTERN 2 PATTERN 2 Conditions ventilation openings If you want to take advantage of the floor area of the adjacent room you must p...

Страница 8: ...nv min and with the Conditions ventilation openings on previous page See table 3 For H1 Can the maximum chimney length be respected and is the chimney practically feasible See table 2 Do you need a ch...

Страница 9: ...m 7 00 m 6 39 m 6 01 m 5 76 m 5 54 m 5 33 m 5 13 m 4 95 m 4 78 m 3 45 kg 9 59 m 8 68 m 7 89 m 7 20 m 6 60 m 6 12 m 5 88 m 5 65 m 5 45 m 5 26 m 5 08 m 3 65 kg 10 73 m 9 71 m 8 83 m 8 06 m 7 39 m 6 80 m...

Страница 10: ...xample If the refrigerant charge is 3 5 kg use the table of 3 65 kg For intermediate floor areas use the column with the lower value Example If the floor area is 7 25 m use the column of 6 00 m For in...

Страница 11: ...m from the floor of the unoccupied room If the opening starts from the floor the height of the opening must be 20 mm a2 Top opening for natural ventilation between room A and the outside Must be a per...

Страница 12: ...he switch box 3 Reinstall the front panel NOTICE When closing the indoor unit cover make sure that the tightening torque does NOT exceed 4 1 N m 4 3 Mounting the indoor unit 4 3 1 To install the indoo...

Страница 13: ...use annealed material Piping diameter Liquid piping 6 4 mm 1 4 Gas piping 15 9 mm 5 8 Piping temper grade and thickness Outer diameter Temper grade Thickness t a 6 4 mm 1 4 Annealed O 0 8 mm t 15 9 m...

Страница 14: ...eck that the minimum flow rate in the installation is guaranteed in all conditions For this purpose use the differential pressure bypass valve delivered with the unit and respect the minimum water vol...

Страница 15: ...f valve and the DHW tank It is recommended to install a pressure reducing valve on the cold water inlet in accordance with the applicable legislation It is recommended to install an expansion vessel o...

Страница 16: ...connect the electricity meters 420 Domestic hot water pump See 6 3 5 To connect the domestic hot water pump 420 Alarm output See 6 3 6 To connect the alarm output 421 Space cooling heating operation c...

Страница 17: ...optional equipment Wires 2 GND Maximum running current 13 A 9 4 Booster heater Item Description LAN adapter See Installation manual of the LAN adapter Addendum book for optional equipment Wires 2 0 75...

Страница 18: ...applicable load of 15 V DC 10 mA 9 8 Benefit kWh power supply Connect X11Y to X11YB N L 5 6 B C A A 10 9 S1S 1 2 3 1N 50 Hz 230 V AC 6 3 A C B 5 6 1 2 3 X11YA X11YB X11Y X5M X1A X2M X1M X5M X2M c b a...

Страница 19: ...age systems with input current 16 A and 75 A per phase c This equipment complies with EN IEC 61000 3 11 European International Technical Standard setting the limits for voltage changes voltage fluctua...

Страница 20: ...pen valve B C A A B C A A M2S NO NC C 5 6 X2M C 21 28 X2M C 5 6 X2M C 21 29 X2M B X2M 3 Fix the cable with cable ties to the cable tie mountings 6 3 4 To connect the electricity meters Wires 2 per met...

Страница 21: ...ion below 7 9 YC Y1 X2M 1 2 3 A4P 1 2 Wires connected to the alarm output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required B C A A 7 Y1 C B X2M X2M A4P A4P a 7 9 Y1 YC X1M a Instal...

Страница 22: ...pen the indoor unit 411 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below B C A...

Страница 23: ...5M X5M 3 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessar...

Страница 24: ...Connect the wiring as follows B C A A X5M 4 X5M 3 S4S X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 C B X5M X5M 3 4 5 6 9 10 13 14 2 Fix the cables with cable ties to the cable tie mountings In case of high...

Страница 25: ...t Grid pulse meter C B X5M X5M 3 4 13 14 3 Connect the high voltage wiring as follows B C A A L N L N X10M 1 X10M 2 X10M 3 X10M 4 2 1 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid cont...

Страница 26: ...staller settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column...

Страница 27: ...ON By default daylight savings time is enabled and clock format is set to 24 hours These settings can be changed during initial configuration or via the menu structure 7 2 User settings Time date 7 2...

Страница 28: ...ot water is NOT available Similarly as in Manual mode the unit can take the full load with the backup heater and or booster heater if the user activates this via the Malfunctioning main menu screen To...

Страница 29: ...p heater is adapted to be connected to most common European electricity grids The type of backup heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Voltage For a 6V model this...

Страница 30: ...ambient temperature for cooling In Weather dependent mode the desired leaving water temperature depends on the outdoor ambient temperature Code Description 2 4 N A Setpoint mode Fixed WD heating fixed...

Страница 31: ...stop to tank heating even if the setpoint has NOT been reached Only program a storage stop when tank heating is absolutely undesirable Code Description 5 2 6 0A Comfort setpoint 30 C 6 0E C Eco setpoi...

Страница 32: ...the next temperature Confirm changes and proceed 7 3 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or decre...

Страница 33: ...er dependent curve Zone Go to Main zone Heating 2 5 Main zone Heating WD curve Main zone Cooling 2 6 Main zone Cooling WD curve Additional zone Heating 3 5 Additional zone Heating WD curve Additional...

Страница 34: ...acts The used external room thermostat can send a separate heating cooling thermo ON OFF condition 7 4 2 Additional zone Ext thermostat type Only applicable in external room thermostat control For mor...

Страница 35: ...iority temperature Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor Ext amb senso...

Страница 36: ...ounted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor uni...

Страница 37: ...un Conditions Make sure all operation is disabled Go to C Operation and turn off Space heating cooling and Tank operation 1 Set the user permission level to Installer See To change the user permission...

Страница 38: ...site mode see Commissioning room frost protection will be automatically disabled for 12 hours after the first power on If the screed dryout still needs to be performed after the first 12 hours of powe...

Страница 39: ...e heating cooling Water IN screw connection 1 Thermistors a2 Space heating cooling Water OUT screw connection 1 R1T Heat exchanger Water OUT b1 Gas refrigerant IN heating mode condenser R2T Backup hea...

Страница 40: ...FF thermostat wired On OFF thermostat wireless ON OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF...

Страница 41: ...e mixing kit Bizone mixing kit Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For hi...

Страница 42: ...10 Technical data Installation manual 42 ELBH X12E Daikin Altherma 3 R MT W 4P708482 1 2023 03 Electrical connection diagram For more details please check the unit wiring...

Страница 43: ......

Страница 44: ...4P708482 1 2023 03 Copyright 2023 Daikin 4P708482 1 0000000R Verantwortung f r Energie und Umwelt...

Отзывы: