background image

6 Electrical installation

Installation manual

15

ELBH/X12E
Daikin Altherma 3 R MT W
4P708482-1 – 2023.03

a

b

a

Space heating/cooling – Water OUT (screw connection,
1")

b

Space heating/cooling – Water IN (screw connection, 1")

2

Screw the indoor unit nuts on the shut-off valves.

3

Connect the field piping on the shut-off valves.

4

In case of connection with the optional domestic hot water tank,
see the installation manual of the domestic hot water tank.

NOTICE

Install air purge valves at all local high points.

NOTICE

Differential

 

pressure  bypass  valve

  (delivered  as

accessory).  We  recommend  to  install  the  differential
pressure bypass valve in the space heating water circuit.

▪ Mind  the  minimum  water  volume  when  choosing  the

installation  location  of  the  differential  pressure  bypass
valve  (at  the  indoor  unit,  or  at  the  collector).  See

"5.3.1 To check the water volume and flow rate"

 [

4

 14].

▪ Mind  the  minimum  flow  rate  when  adjusting  the

differential  pressure  bypass  valve  setting.  See

"5.3.1  To  check  the  water  volume  and  flow  rate"

  [

4

  14]

and 

"8.2.1 To check the minimum flow rate"

 [

4

 37].

NOTICE

In case an optional domestic hot water tank is installed: A
pressure  relief  valve  (field  supply)  with  an  opening
pressure  of  maximum  10  bar  (=  1  MPa)  must  be  installed
on the domestic cold water inlet connection in accordance
with the applicable legislation.

NOTICE

In case an optional domestic hot water tank is installed:

▪ A  drain  device  and  pressure  relief  device  must  be

installed  on  the  cold  water  inlet  connection  of  the
domestic hot water cylinder.

▪ To avoid back siphonage, it is recommended to install a

non-return valve on the water inlet of the domestic hot
water tank in accordance with the applicable legislation.
Make sure it is NOT between the pressure relief valve
and the DHW tank.

▪ It is recommended to install a pressure reducing valve

on  the  cold  water  inlet  in  accordance  with  the
applicable legislation.

▪ It is recommended to install an expansion vessel on the

cold  water  inlet  in  accordance  with  the  applicable
legislation.

▪ It is recommended to install the pressure relief valve on

a higher position than the top of the domestic hot water
tank.  Heating  of  the  domestic  hot  water  tank  causes
water  to  expand  and  without  pressure  relief  valve  the
water pressure inside the tank can rise above the tank
design  pressure.  Also  the  field  installation  (piping,
tapping points, etc.) connected to the tank is subjected
to this high pressure. To prevent this, a pressure relief
valve  needs  to  be  installed.  The  overpressure
prevention depends on the correct operation of the field
installed  pressure  relief  valve.  If  this  is  NOT  working
correctly,  overpressure  will  deform  the  tank  and  water
leakage may occur. To confirm good operation, regular
maintenance is required.

5.4.2

To fill the water circuit

To  fill  the  water  circuit,  use  a  field  supply  filling  kit.  Make  sure  you
comply with the applicable legislation.

NOTICE

Pump.

 To prevent blocking of the pump rotor, commission

the unit as quickly as possible after filling the water circuit.

INFORMATION

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

5.4.3

To fill the domestic hot water tank

See the installation manual of the domestic hot water tank.

5.4.4

To insulate the water piping

The  piping  in  the  complete  water  circuit  MUST  be  insulated  to
prevent  condensation  during  cooling  operation  and  reduction  of  the
heating and cooling capacity.

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

6

Electrical installation

DANGER: RISK OF ELECTROCUTION

Содержание Altherma 3 R MT W

Страница 1: ...Installation manual Daikin Altherma 3 R MT W English Installation manual Daikin Altherma 3 R MT W ELBH12E 6V ELBH12E 9W ELBX12E 6V ELBX12E 9W 1 2 3 9 A B C Z 1 2 3 9 https daikintechnicaldatahub eu...

Страница 2: ...To access the most used commands 26 7 2 Configuration wizard 27 7 2 1 Configuration wizard Language 27 7 2 2 Configuration wizard Time and date 27 7 2 3 Configuration wizard System 27 7 2 4 Configurat...

Страница 3: ...ance or an operating electric heater WARNING DO NOT reuse refrigerant piping that has been used with any other refrigerant Replace the refrigerant pipes or clean thoroughly WARNING Follow the service...

Страница 4: ...ct the backup heater power supply and the earth cable INFORMATION Details of type and rating of fuses or rating of circuit breakers are described in 6 Electrical installation 415 Commissioning see 8 C...

Страница 5: ...it at a minimum distance of 1 m from other heat sources 80 C e g electrical heater oil heater chimney and combustible materials Otherwise the unit may be damaged or in extreme cases catch fire Mind th...

Страница 6: ...minimum 1 95 m 1b 2b With chimney From floor to top of the chimney 3a Installation with chimney connected to the outside The release height is not relevant There are no requirements to the minimum fl...

Страница 7: ...charge and the given release height without chimney START PATTERN 1 PATTERN 2 PATTERN 2 Conditions ventilation openings If you want to take advantage of the floor area of the adjacent room you must p...

Страница 8: ...nv min and with the Conditions ventilation openings on previous page See table 3 For H1 Can the maximum chimney length be respected and is the chimney practically feasible See table 2 Do you need a ch...

Страница 9: ...m 7 00 m 6 39 m 6 01 m 5 76 m 5 54 m 5 33 m 5 13 m 4 95 m 4 78 m 3 45 kg 9 59 m 8 68 m 7 89 m 7 20 m 6 60 m 6 12 m 5 88 m 5 65 m 5 45 m 5 26 m 5 08 m 3 65 kg 10 73 m 9 71 m 8 83 m 8 06 m 7 39 m 6 80 m...

Страница 10: ...xample If the refrigerant charge is 3 5 kg use the table of 3 65 kg For intermediate floor areas use the column with the lower value Example If the floor area is 7 25 m use the column of 6 00 m For in...

Страница 11: ...m from the floor of the unoccupied room If the opening starts from the floor the height of the opening must be 20 mm a2 Top opening for natural ventilation between room A and the outside Must be a per...

Страница 12: ...he switch box 3 Reinstall the front panel NOTICE When closing the indoor unit cover make sure that the tightening torque does NOT exceed 4 1 N m 4 3 Mounting the indoor unit 4 3 1 To install the indoo...

Страница 13: ...use annealed material Piping diameter Liquid piping 6 4 mm 1 4 Gas piping 15 9 mm 5 8 Piping temper grade and thickness Outer diameter Temper grade Thickness t a 6 4 mm 1 4 Annealed O 0 8 mm t 15 9 m...

Страница 14: ...eck that the minimum flow rate in the installation is guaranteed in all conditions For this purpose use the differential pressure bypass valve delivered with the unit and respect the minimum water vol...

Страница 15: ...f valve and the DHW tank It is recommended to install a pressure reducing valve on the cold water inlet in accordance with the applicable legislation It is recommended to install an expansion vessel o...

Страница 16: ...connect the electricity meters 420 Domestic hot water pump See 6 3 5 To connect the domestic hot water pump 420 Alarm output See 6 3 6 To connect the alarm output 421 Space cooling heating operation c...

Страница 17: ...optional equipment Wires 2 GND Maximum running current 13 A 9 4 Booster heater Item Description LAN adapter See Installation manual of the LAN adapter Addendum book for optional equipment Wires 2 0 75...

Страница 18: ...applicable load of 15 V DC 10 mA 9 8 Benefit kWh power supply Connect X11Y to X11YB N L 5 6 B C A A 10 9 S1S 1 2 3 1N 50 Hz 230 V AC 6 3 A C B 5 6 1 2 3 X11YA X11YB X11Y X5M X1A X2M X1M X5M X2M c b a...

Страница 19: ...age systems with input current 16 A and 75 A per phase c This equipment complies with EN IEC 61000 3 11 European International Technical Standard setting the limits for voltage changes voltage fluctua...

Страница 20: ...pen valve B C A A B C A A M2S NO NC C 5 6 X2M C 21 28 X2M C 5 6 X2M C 21 29 X2M B X2M 3 Fix the cable with cable ties to the cable tie mountings 6 3 4 To connect the electricity meters Wires 2 per met...

Страница 21: ...ion below 7 9 YC Y1 X2M 1 2 3 A4P 1 2 Wires connected to the alarm output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required B C A A 7 Y1 C B X2M X2M A4P A4P a 7 9 Y1 YC X1M a Instal...

Страница 22: ...pen the indoor unit 411 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below B C A...

Страница 23: ...5M X5M 3 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessar...

Страница 24: ...Connect the wiring as follows B C A A X5M 4 X5M 3 S4S X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 C B X5M X5M 3 4 5 6 9 10 13 14 2 Fix the cables with cable ties to the cable tie mountings In case of high...

Страница 25: ...t Grid pulse meter C B X5M X5M 3 4 13 14 3 Connect the high voltage wiring as follows B C A A L N L N X10M 1 X10M 2 X10M 3 X10M 4 2 1 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid cont...

Страница 26: ...staller settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column...

Страница 27: ...ON By default daylight savings time is enabled and clock format is set to 24 hours These settings can be changed during initial configuration or via the menu structure 7 2 User settings Time date 7 2...

Страница 28: ...ot water is NOT available Similarly as in Manual mode the unit can take the full load with the backup heater and or booster heater if the user activates this via the Malfunctioning main menu screen To...

Страница 29: ...p heater is adapted to be connected to most common European electricity grids The type of backup heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Voltage For a 6V model this...

Страница 30: ...ambient temperature for cooling In Weather dependent mode the desired leaving water temperature depends on the outdoor ambient temperature Code Description 2 4 N A Setpoint mode Fixed WD heating fixed...

Страница 31: ...stop to tank heating even if the setpoint has NOT been reached Only program a storage stop when tank heating is absolutely undesirable Code Description 5 2 6 0A Comfort setpoint 30 C 6 0E C Eco setpoi...

Страница 32: ...the next temperature Confirm changes and proceed 7 3 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or decre...

Страница 33: ...er dependent curve Zone Go to Main zone Heating 2 5 Main zone Heating WD curve Main zone Cooling 2 6 Main zone Cooling WD curve Additional zone Heating 3 5 Additional zone Heating WD curve Additional...

Страница 34: ...acts The used external room thermostat can send a separate heating cooling thermo ON OFF condition 7 4 2 Additional zone Ext thermostat type Only applicable in external room thermostat control For mor...

Страница 35: ...iority temperature Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor Ext amb senso...

Страница 36: ...ounted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor uni...

Страница 37: ...un Conditions Make sure all operation is disabled Go to C Operation and turn off Space heating cooling and Tank operation 1 Set the user permission level to Installer See To change the user permission...

Страница 38: ...site mode see Commissioning room frost protection will be automatically disabled for 12 hours after the first power on If the screed dryout still needs to be performed after the first 12 hours of powe...

Страница 39: ...e heating cooling Water IN screw connection 1 Thermistors a2 Space heating cooling Water OUT screw connection 1 R1T Heat exchanger Water OUT b1 Gas refrigerant IN heating mode condenser R2T Backup hea...

Страница 40: ...FF thermostat wired On OFF thermostat wireless ON OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF...

Страница 41: ...e mixing kit Bizone mixing kit Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For hi...

Страница 42: ...10 Technical data Installation manual 42 ELBH X12E Daikin Altherma 3 R MT W 4P708482 1 2023 03 Electrical connection diagram For more details please check the unit wiring...

Страница 43: ......

Страница 44: ...4P708482 1 2023 03 Copyright 2023 Daikin 4P708482 1 0000000R Verantwortung f r Energie und Umwelt...

Отзывы: