6.5.4 BBR16 power limitation
INFORMATION
Restriction:
BBR16 settings are only visible when the language of the user interface is
set to Swedish.
NOTICE
2 weeks to change.
After you activated BBR16, you only have 2 weeks to change its
settings (
BBR16 activation
and
BBR16 power limit
). After 2 weeks, the unit
freezes these settings.
Note:
This is different from the permanent power limitation, which is always
changeable.
Use the BBR16 power limitation when you must comply with BBR16 regulations
(Swedish energy regulations).
You can combine the BBR16 power limitation with the other kW power
consumption controls. If you do so, the unit uses the most restrictive control.
P
i
t
BBR16
a
b
P
i
Power input
t
Time
BBR16
BBR16 limit level
a
Power limitation active
b
Actual power input
Setup and configuration
▪
No additional equipment needed.
▪
Set the power consumption control settings in [9.9] via the user interface (see
224]):
-
Activate BBR16
-
Set the desired power limitation level
6.5.5 Smart Grid capacity limitation due to buffering
Smart Grid limitation for buffering is only possible if a Smart Grid is installed and
Recommended on
mode is active.
You can combine
Recommended on
mode capacity limitation with other power
consumption controls. If you do so, the unit uses the most restrictive control.
INFORMATION
In case Smart Grid
Forced off
mode is active, the outdoor unit compressor and
electrical heaters will NOT operate.
Setup and configuration
See
"9.3.10 To connect a Smart Grid"
135] and