4 Unit installation
Installation manual
13
EBSH/X(B)11+16P30+50DF
Daikin Altherma 3 R ECH
₂
O
4P663483-1A – 2021.11
PATTERN 3
No
Yes
START PATTERN 3
A
You can install the unit in room A if you lead the chimney outside
the building.
3a
You CANNOT install the unit in the room. Place the unit in a larger
room.
3b
See table 3:
Is it possible to lead a chimney
outside the building respecting the maximum
chimney length?
Tables for PATTERN 1, 2 and 3
Table 1: Minimum floor area
For intermediate refrigerant charges, use the row with the higher value.
Example:
If the refrigerant charge is 4.3 kg, use the row of 4.5 kg.
Minimum floor area (m²)
Charge (kg)
Release height without chimney (m)
1.89 (Unit=300 l)
1.90 (Unit=500 l)
3.8
12.37
12.18
4
13.71
13.49
4.5
17.35
17.08
5
21.42
21.08
5.5
25.92
25.51
5.8
28.82
28.37
Table 2: Minimum release height
Take the following into account:
• For intermediate floor areas, use the column with the lower value.
Example:
If the floor area is 22.50 m², use the column of 20.00 m².
• For intermediate refrigerant charges, use the row with the higher value.
Example:
If the refrigerant charge is 4.3 kg, use the row of 4.5 kg.
• (*): The release height of the unit without chimney (for 300 l units: 1.89 m; for 500 l units: 1.90 m) is already higher than the minimum
required release height. => OK (no chimney needed).
Minimum release height (m)
Charge (kg)
Floor area (m²)
5.00
10.00
15.00
20.00
25.00
3.8
3.30
2.10
(*)
(*)
(*)
4
3.47
2.21
(*)
(*)
(*)
4.5
3.91
2.49
2.03
(*)
(*)
5
4.34
2.77
2.26
1.96
(*)
5.5
4.78
3.04
2.49
2.15
1.93
5.8
5.04
3.21
2.62
2.27
2.03