4 Installation

Installation manual

10

EABH/9W

Daikin Altherma 3 H W

4P644479-1 – 2020.12

b

a

X2M

X1M

X5M

d

b+c

a

c

a, b, c

Field wiring (see table below)

d

Factory-mounted cable for power supply of backup heater

INFORMATION

When  installing  field  supply  or  option  cables,  foresee
sufficient  cable  length.  This  will  make  it  possible  to  open
the  switch  box  and  gain  access  to  other  components
during service.

Routing

Possible cables (depending on unit type
and installed options)

a

Low voltage

▪ Preferential power supply contact

▪ User interface (option)

▪ Power  consumption  digital  inputs  (field

supply)

▪ Outdoor  ambient  temperature  sensor

(option)

▪ Indoor 

ambient 

temperature 

sensor

(option)

▪ Electrical meters (field supply)

▪ Safety thermostat (field supply)

b

High voltage power
supply

▪ Interconnection cable

▪ Normal kWh rate power supply

▪ Preferential kWh rate power supply

c

High voltage control
signal

▪ Heat pump convector (option)

▪ Room thermostat (option)

▪ Shut-off valve (field supply)

▪ Domestic hot water pump (field supply)

▪ Alarm output

▪ Changeover  to  external  heat  source

control

▪ Space cool/heat operation control

d

High voltage power
supply (factory-
mounted cable)

▪ Power supply for backup heater

CAUTION

Do NOT push or place redundant cable length in the unit.

4.4.3

To connect the main power supply

1

Connect the main power supply.

In case of normal kWh rate power supply

X2M

X1M

1 2 3

1 2 3
1 2 3

1 2 3

X1A

X11YB

X11YA X11Y

1 2 3

a

a

Interconnection cable (=main power supply)

In case of preferential kWh rate power supply

Connect X11Y to X11YB.

X5M

X2M

X1M

1 2 3

1 2

N L

N L

3

S1S

a

b

c

X11YA

X1A

X11YB X11Y

910

5

1 2 3

6

a

Interconnection cable (=main power supply)

b

Normal kWh rate power supply

c

Preferential power supply contact

2

Fix the cables with cable ties to the cable tie mountings.

INFORMATION

In  case  of  preferential  kWh  rate  power  supply,  connect
X11Y  to  X11YB.  The  necessity  of  separate  normal  kWh
rate  power  supply  to  indoor  unit  (b)  X2M/5+6  depends  on
the type of preferential kWh rate power supply.

Separate connection to the indoor unit is required:

▪ if  preferential  kWh  rate  power  supply  is  interrupted

when active, OR

▪ if no power consumption of the indoor unit is allowed at

the preferential kWh rate power supply when active.

INFORMATION

The  preferential  kWh  rate  power  supply  contact  is
connected to the same terminals (X5M/9+10) as the safety
thermostat.  Thus,  the  system  can  have  EITHER
preferential  kWh  rate  power  supply  OR  a  safety
thermostat.

Содержание Altherma 3 H W

Страница 1: ...Installation manual Daikin Altherma 3 H W English Installation manual Daikin Altherma 3 H W EABH16DF6V EABH16DF9W EABX16DF6V EABX16DF9W...

Страница 2: ...y odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17 18 19...

Страница 3: ...pendent curve 18 5 2 8 Configuration wizard Tank 19 5 3 Settings menu 19 5 3 1 Main zone 19 5 3 2 Additional zone 19 5 3 3 Information 20 5 4 Menu structure Overview installer settings 21 6 Commission...

Страница 4: ...5 35 C Domestic hot water production 5 35 C INFORMATION Cooling is only applicable in case of Reversible models Heating only models conversion kit EKHBCONV Mind the measurement guidelines Maximum hei...

Страница 5: ...above the heat exchanger coil The booster heater must be located above the heat exchanger coil NOTICE Performance Performance data for third party tanks CANNOT be provided and performance CANNOT be g...

Страница 6: ...Overview 1 2 3 1 4 4 1 Front panel 2 Switch box cover 3 Switch box 4 User interface panel Open 1 Remove the front panel 2 2 1 3 2 If you have to connect electrical wiring remove the switch box cover...

Страница 7: ...he drain hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable legislation 1 Co...

Страница 8: ...circuit against freezing Add glycol to the water Glycol lowers the freezing point of the water Install freeze protection valves Freeze protection valves drain the water from the system before it can...

Страница 9: ...se freeze protection valves to drain the water from the system before it can freeze Install freeze protection valves field supply at all lowest points of the field piping Normally closed valves locate...

Страница 10: ...y factory mounted cable Power supply for backup heater CAUTION Do NOT push or place redundant cable length in the unit 4 4 3 To connect the main power supply 1 Connect the main power supply In case of...

Страница 11: ...er phase c This equipment complies with EN IEC 61000 3 11 European International Technical Standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply...

Страница 12: ...ck the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Connect the electricity meters cable to the appropriate terminals as shown in the...

Страница 13: ...tat normally closed cable to the appropriate terminals as shown in the illustration below X5M 9 10 2 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install the...

Страница 14: ...be displayed Accessing settings Legend for tables You can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding ta...

Страница 15: ...st be set on the user interface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Domestic hot water The following setting...

Страница 16: ...nd the zone with the highest water temperature is configured as the additional zone NOTICE If there are 2 zones and the emitter types are wrongly configured water of high temperature can be sent towar...

Страница 17: ...T in heating 0 Underfloor heating Maximum 55 C Variable 1 Fancoil unit Maximum 55 C Variable 2 Radiator Maximum 65 C Fixed 8 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 T...

Страница 18: ...n 3 1 N A 0 No 1 Yes 5 2 7 Detailed screen with weather dependent curve When weather dependent WD operation is active the desired leaving water or tank temperature is determined automatically dependin...

Страница 19: ...t up until the storage comfort temperature has been reached It is the higher desired temperature when a storage comfort action is scheduled Additionally a storage stop can be programmed This feature p...

Страница 20: ...44479 1 2020 12 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 5 3 3 Information Dealer information The installer can fill in his contact numb...

Страница 21: ...librium temperature Operation 9 4 Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running t...

Страница 22: ...tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification labe...

Страница 23: ...evel 414 2 Go to A 2 Commissioning Actuator test run 3 Select a test from the list Example Pump 4 Select OK to confirm Result The actuator test run starts It stops automatically when ready 30 min To s...

Страница 24: ...in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can find the complete doc...

Страница 25: ...diagram Indoor unit 3D120613A R2T R1T B1PW B1L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e Shut...

Страница 26: ...t pump convector Safety thermostat Safety thermostat Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless...

Страница 27: ...ater pump output DHW pump Domestic hot water pump Electrical meters Electricity meters For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load English Translation Norma...

Страница 28: ...thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation 2 core 2 core communication 2x0 75...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...4P644479 1 2020 12 Copyright 2018 Daikin 4P644479 1 0000000W Verantwortung f r Energie und Umwelt...

Отзывы: