10 Technical data

Installation manual

34

ETBH/9W

Daikin Altherma 3 H HT W

4P644727-1 – 2021.02

10.2

Wiring diagram: Indoor unit

See  the  internal  wiring  diagram  supplied  with  the  unit  (on  the  inside  of  the  indoor  unit  switch  box  cover).  The  abbreviations  used  are  listed
below.

Notes to go through before starting the unit

English

Translation

Notes to go through before
starting the unit

Notes to go through before
starting the unit

X1M

Main terminal

X2M

Field wiring terminal for AC

X5M

Field wiring terminal for DC

X6M

Backup heater power supply
terminal

X7M, X8M

Booster heater power supply
terminal

X10M

Smart grid terminal

Earth wiring

Field supply

1

Several wiring possibilities

Option

Not mounted in switch box

Wiring depending on model

PCB

Note 1: Connection point of the
power supply for the BUH/BSH
should be foreseen outside the
unit.

Note 1: Connection point of the
power supply for the backup
heater/booster heater should be
foreseen outside the unit.

Backup heater power supply

Backup heater power supply

 6T1 (3~, 230 V, 6 kW)

 6T1 (3~, 230 V, 6 kW)

 6V3 (1N~, 230 V, 6 kW)

 6V3 (1N~, 230 V, 6 kW)

 6WN/9WN (3N~, 400 V, 6/9

kW)

 6WN/9WN (3N~, 400 V, 6/9

kW)

User installed options

User installed options

 Remote user interface

 User interface used as room

thermostat

 Ext. indoor thermistor

 External indoor thermistor

 Ext outdoor thermistor

 External outdoor thermistor

 Digital I/O PCB

 Digital I/O PCB

 Demand PCB

 Demand PCB

 Safety thermostat

Safety thermostat

 Smart Grid

Smart grid

 WLAN module

WLAN module

 WLAN cartridge

WLAN cartridge

 Bizone mixing kit

Bizone mixing kit

 Domestic hot water tank

 Domestic hot water tank

Main LWT

Main leaving water temperature

 On/OFF thermostat (wired)

 On/OFF thermostat (wired)

 On/OFF thermostat (wireless)

 On/OFF thermostat (wireless)

 Ext. thermistor

 External thermistor

 Heat pump convector

 Heat pump convector

Add LWT

Additional leaving water
temperature

 On/OFF thermostat (wired)

 On/OFF thermostat (wired)

 On/OFF thermostat (wireless)

 On/OFF thermostat (wireless)

 Ext. thermistor

 External thermistor

 Heat pump convector

 Heat pump convector

Position in switch box

English

Translation

Position in switch box

Position in switch box

Legend

A1P

Main PCB

A2P

* On/OFF thermostat (PC=power circuit)

A3P

* Heat pump convector

A4P

* Digital I/O PCB

A8P

* Demand PCB

A11P

MMI (= user interface connected to the
indoor unit) – Main PCB

A14P

* User interface PCB

A15P

* Receiver PCB (wireless On/OFF thermostat)

A20P

* WLAN module

A30P

* Bizone mixing kit PCB

B1PW

Water pressure sensor

BSK (A3P)

Solar pump station relay

CN* (A4P)

* Connector

DS1(A8P)

* DIP switch

F1B

# Overcurrent fuse backup heater

F2B

# Overcurrent fuse booster heater

F1U, F2U (A4P)

* Fuse 5 A 250 V for digital I/O PCB

K1A, K2A

* High voltage Smart grid relay

K1M, K2M

Contactor backup heater

K3M

* Contactor booster heater

K5M

Safety contactor backup heater

K*R (A1P-A4P)

Relay on PCB

M2P

# Domestic hot water pump

M2S

# 2-way valve for cooling mode

M3S

* 3-way valve for floorheating/domestic hot

water

PC (A15P)

* Power circuit

PHC1 (A4P)

* Optocoupler input circuit

Q1L

Thermal protector backup heater

Q2L

* Thermal protector booster heater

Q4L

# Safety thermostat

Q*DI

# Earth leakage circuit breaker

R1H (A2P)

* Humidity sensor

R1T (A2P)

* Ambient sensor On/OFF thermostat

R2T (A2P)

* External sensor (floor or ambient)

R5T

Domestic hot water thermistor

R6T

* External indoor or outdoor ambient

thermistor

S1S

# Preferential kWh rate power supply contact

S2S

# Electrical meter pulse input 1

S3S

# Electrical meter pulse input 2

S4S

# Smart grid feed-in

S6S~S9S

* Digital power limitation inputs

S10S-S11S

# Low voltage Smart grid contact

SS1 (A4P)

* Selector switch

TR1

Power supply transformer

X6M

# Backup heater power supply terminal strip

Содержание Altherma 3 H HT W ETBH16EF6V

Страница 1: ...https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H HT W English Installation manual Daikin Altherma 3 H HT W ETBH16EF6V ETBH16EF9W ETBX16EF6V ETBX16EF9W...

Страница 2: ...yny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17 18 1...

Страница 3: ...21 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configuration wizard Main zone 24 7 2 6 Configuration wizard Additional zone 25 7 2 7 Configuration wizard Tank 25 7 3 Weather dependent curve 26 7...

Страница 4: ...trical device Possible consequence Electric shock or fire In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is possi...

Страница 5: ...heating operation 5 30 C Space cooling operation 5 35 C Domestic hot water production 5 35 C INFORMATION Cooling is only applicable in case of Reversible models Heating only models conversion kit EKHB...

Страница 6: ...1 2 3 2 5 Optional Remove the user interface panel NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 3 3 1 2 X14Y X1...

Страница 7: ...the applicable legislation 1 Connect a drain tube field supply to the drain pan connector as follows a a Drain pan connector It is recommended to use a tundish to collect the water 5 Piping installat...

Страница 8: ...at the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached a flow error 7H will be generated no heating or operation See the installer referen...

Страница 9: ...out of the freeze protection valves Freeze protection by glycol About freeze protection by glycol Adding glycol to the water lowers the freezing point of water WARNING Ethylene glycol is toxic WARNIN...

Страница 10: ...ning temperature of the freeze protection valve If lower freeze protection valves can open during cooling operation For more information see the installer reference guide 5 2 4 To fill the domestic ho...

Страница 11: ...1 External sensor Outdoor 9 B 2 Ext amb sensor offset 9 B 3 Averaging time Item Description Remote indoor sensor See Installation manual of the remote indoor sensor Addendum book for optional equipmen...

Страница 12: ...the wired room thermostat digital or analogue to the multi zoning base unit You need to connect the multi zoning base unit to the outdoor unit For cooling heating operation you also need to implement...

Страница 13: ...lation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model Make...

Страница 14: ...y SWB Switch box X6M Terminal field supply NOTICE Do NOT cut or remove the backup heater power supply cable 6 3 3 To connect the shut off valve INFORMATION Shut off valve usage example In case of one...

Страница 15: ...llustration below B C A A 6 5 4 3 S3S S2S C B X5M 5 6 3 4 X5M 3 Fix the cable with cable ties to the cable tie mountings 6 3 5 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump outpu...

Страница 16: ...r unit 45 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y2 X2M 1 2...

Страница 17: ...ital inputs cable to the appropriate terminals as shown in the illustration below B C A A 1 2 4 5 S6S S7S S8S S9S 3 C B A8P X801M a 5 4 3 2 1 a Installation of EKRP1AHTA is required 3 Fix the cable wi...

Страница 18: ...the Smart Grid relay kit EKRELSG The 2 incoming Smart Grid contacts can activate the following Smart Grid modes Smart Grid contact Smart Grid operation mode 1 2 0 0 Free running Smart Grid contact Sm...

Страница 19: ...Smart Grid relay kit installation STEP 2 Low voltage connections STEP 3 High voltage connections 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 a b Coil sides of relays c d C...

Страница 20: ...ser interface for the first time via the unit the configuration wizard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the...

Страница 21: ...g the dial 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0 1 2 3 4 Turn the left dial to select the second part of the setting 00 01 15 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 1 5 Turn the right dial to...

Страница 22: ...05 Thermistor type 0 Automatic 1 Type 1 5 8 6 0E Maximum tank temperature 60 C 75 C Emergency When the heat pump fails to operate the backup heater and or booster heater can serve as an emergency hea...

Страница 23: ...e system filled with glycol 0 No 1 Yes Booster heater capacity The capacity of the booster heater must be set for the energy metering and or power consumption control feature to work properly When mea...

Страница 24: ...m 55 C Variable 2 Radiator Maximum 70 C Fixed 10 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 This means that for a same leaving water temperature setpoint the average emit...

Страница 25: ...ration is allowed 1 Schedule reheat The domestic hot water tank is heated according to a schedule and between the scheduled heat up cycles reheat operation is allowed 2 Schedule only The domestic hot...

Страница 26: ...ing Additional zone Cooling Tank only available to installers INFORMATION To operate weather dependent correctly configure the setpoint of the main zone additional zone or tank See 7 3 4 Using weather...

Страница 27: ...Go to setpoint mode Set the setpoint mode to 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather dependent...

Страница 28: ...st protection However the room frost protection is only possible if C 2 Space heating cooling On Code Description 2 A C 05 External room thermostat type for the main zone 1 1 contact The used external...

Страница 29: ...temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor...

Страница 30: ...nted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit...

Страница 31: ...toring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In the menu go to Sensors 2 Select the temperature information 8 2...

Страница 32: ...sult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 9 Hand over to the user O...

Страница 33: ...ing diagram Indoor unit 3D120613B R2T R1T B1PW B1L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e S...

Страница 34: ...ireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wir...

Страница 35: ...ntinuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid For LV smartgrid For l...

Страница 36: ...ce Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ...4P644727 1 2021 02 Copyright 2021 Daikin 4P644727 1 0000000S Verantwortung f r Energie und Umwelt...

Отзывы: