7 Configuration

Installation manual

24

ETBH/9W

Daikin Altherma 3 H HT W

4P644727-1 – 2021.02

INFORMATION

If  [4‑0A]=3  and  emergency  mode  is  active,  the  power
usage  of  the  backup  heater  is  maximal  and  equal  to
2×[6‑03]+[6‑04].

INFORMATION

Only for systems with integrated domestic hot water tank: If
the  storage  temperature  setpoint  is  higher  than  50°C,
Daikin  recommends  NOT  to  disable  the  backup  heater
second  step  because  it  will  have  a  big  impact  on  the
required time for the unit to heat up the domestic hot water
tank.

Capacity step 1

#

Code

Description

[9.3.4]

[6‑03]

▪ The  capacity  of  the  first  step  of  the

backup heater at nominal voltage.

Additional capacity step 2

#

Code

Description

[9.3.5]

[6‑04]

▪ The  capacity  difference  between  the

second  and  first  step  of  the  backup
heater  at  nominal  voltage.  Nominal
value  depends  on  backup  heater
configuration.

7.2.5

Configuration wizard: Main zone

The most important settings for the main leaving water zone can be
set here.

Emitter type

Heating  up  or  cooling  down  the  main  zone  can  take  longer.  This
depends on:

▪ The water volume of the system

▪ The heater emitter type of the main zone

The  setting 

Emitter  type

  can  compensate  for  a  slow  or  a  quick

heating/cooling system during the heat up/cool down cycle. In room
thermostat  control, 

Emitter 

type

  influences  the  maximum

modulation  of  the  desired  leaving  water  temperature,  and  the
possibility  for  usage  of  the  automatic  cooling/heating  changeover
based on the indoor ambient temperature.

It is important to set 

Emitter type

 correctly and in accordance with

your system layout. The target delta T for the main zone depends on
it.

#

Code

Description

[2.7]

[2‑0C]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:

Description

Space heating

setpoint range

Target delta T in

heating

0: 

Underfloor

heating

Maximum 55°C

Variable

1: 

Fancoil unit

Maximum 55°C

Variable

2: 

Radiator

Maximum 70°C

Fixed 10°C

NOTICE

Average 

emitter 

temperature

 

Leaving 

water

temperature – (Delta T)/2

This  means  that  for  a  same  leaving  water  temperature
setpoint,  the  average  emitter  temperature  of  radiators  is
lower  than  that  of  underfloor  heating  because  of  a  bigger
delta T.

Example radiators: 40–10/2=

35°C

Example underfloor heating: 40–5/2=

37.5°C

To compensate, you can:

▪ Increase 

the 

weather-dependent 

curve 

desired

temperatures [2.5].

▪ Enable  leaving  water  temperature  modulation  and

increase the maximum modulation [2.C].

Control

Define how the operation of the unit is controlled.

Control

In this control...

Leaving water

Unit operation is decided based on the leaving
water temperature regardless the actual room
temperature and/or heating or cooling demand
of the room.

External room
thermostat

Unit operation is decided by the external
thermostat or equivalent (e.g. heat pump
convector).

Room thermostat

Unit operation is decided based on the ambient
temperature of the dedicated Human Comfort
Interface (BRC1HHDA used as room
thermostat).

#

Code

Description

[2.9]

[C‑07]

▪ 0: 

Leaving water

▪ 1: 

External room thermostat

▪ 2: 

Room thermostat

Setpoint mode

Define the setpoint mode:

Fixed

: the desired leaving water temperature does not depend on

the outdoor ambient temperature.

▪ In 

WD heating, fixed cooling

 mode, the desired leaving water

temperature:

▪ depends on the outdoor ambient temperature for heating

▪ does  NOT  depend  on  the  outdoor  ambient  temperature  for

cooling

▪ In 

Weather 

dependent

  mode,  the  desired  leaving  water

temperature depends on the outdoor ambient temperature.

#

Code

Description

[2.4]

N/A

Setpoint mode

:

Fixed

WD heating, fixed cooling

Weather dependent

When  weather  dependent  operation  is  active,  low  outdoor
temperatures  will  result  in  warmer  water  and  vice  versa.  During
weather  dependent  operation,  the  user  can  shift  the  water
temperature up or down by a maximum of 10°C.

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Influence of the LWT setpoint mode [2.4] is as follows:

▪ In 

Fixed

  LWT  setpoint  mode,  the  scheduled  actions  consist  of

desired leaving water temperatures, either preset or custom.

Содержание Altherma 3 H HT W ETBH16EF6V

Страница 1: ...https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H HT W English Installation manual Daikin Altherma 3 H HT W ETBH16EF6V ETBH16EF9W ETBX16EF6V ETBX16EF9W...

Страница 2: ...yny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17 18 1...

Страница 3: ...21 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configuration wizard Main zone 24 7 2 6 Configuration wizard Additional zone 25 7 2 7 Configuration wizard Tank 25 7 3 Weather dependent curve 26 7...

Страница 4: ...trical device Possible consequence Electric shock or fire In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is possi...

Страница 5: ...heating operation 5 30 C Space cooling operation 5 35 C Domestic hot water production 5 35 C INFORMATION Cooling is only applicable in case of Reversible models Heating only models conversion kit EKHB...

Страница 6: ...1 2 3 2 5 Optional Remove the user interface panel NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 3 3 1 2 X14Y X1...

Страница 7: ...the applicable legislation 1 Connect a drain tube field supply to the drain pan connector as follows a a Drain pan connector It is recommended to use a tundish to collect the water 5 Piping installat...

Страница 8: ...at the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached a flow error 7H will be generated no heating or operation See the installer referen...

Страница 9: ...out of the freeze protection valves Freeze protection by glycol About freeze protection by glycol Adding glycol to the water lowers the freezing point of water WARNING Ethylene glycol is toxic WARNIN...

Страница 10: ...ning temperature of the freeze protection valve If lower freeze protection valves can open during cooling operation For more information see the installer reference guide 5 2 4 To fill the domestic ho...

Страница 11: ...1 External sensor Outdoor 9 B 2 Ext amb sensor offset 9 B 3 Averaging time Item Description Remote indoor sensor See Installation manual of the remote indoor sensor Addendum book for optional equipmen...

Страница 12: ...the wired room thermostat digital or analogue to the multi zoning base unit You need to connect the multi zoning base unit to the outdoor unit For cooling heating operation you also need to implement...

Страница 13: ...lation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model Make...

Страница 14: ...y SWB Switch box X6M Terminal field supply NOTICE Do NOT cut or remove the backup heater power supply cable 6 3 3 To connect the shut off valve INFORMATION Shut off valve usage example In case of one...

Страница 15: ...llustration below B C A A 6 5 4 3 S3S S2S C B X5M 5 6 3 4 X5M 3 Fix the cable with cable ties to the cable tie mountings 6 3 5 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump outpu...

Страница 16: ...r unit 45 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y2 X2M 1 2...

Страница 17: ...ital inputs cable to the appropriate terminals as shown in the illustration below B C A A 1 2 4 5 S6S S7S S8S S9S 3 C B A8P X801M a 5 4 3 2 1 a Installation of EKRP1AHTA is required 3 Fix the cable wi...

Страница 18: ...the Smart Grid relay kit EKRELSG The 2 incoming Smart Grid contacts can activate the following Smart Grid modes Smart Grid contact Smart Grid operation mode 1 2 0 0 Free running Smart Grid contact Sm...

Страница 19: ...Smart Grid relay kit installation STEP 2 Low voltage connections STEP 3 High voltage connections 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 a b Coil sides of relays c d C...

Страница 20: ...ser interface for the first time via the unit the configuration wizard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the...

Страница 21: ...g the dial 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0 1 2 3 4 Turn the left dial to select the second part of the setting 00 01 15 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 1 5 Turn the right dial to...

Страница 22: ...05 Thermistor type 0 Automatic 1 Type 1 5 8 6 0E Maximum tank temperature 60 C 75 C Emergency When the heat pump fails to operate the backup heater and or booster heater can serve as an emergency hea...

Страница 23: ...e system filled with glycol 0 No 1 Yes Booster heater capacity The capacity of the booster heater must be set for the energy metering and or power consumption control feature to work properly When mea...

Страница 24: ...m 55 C Variable 2 Radiator Maximum 70 C Fixed 10 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 This means that for a same leaving water temperature setpoint the average emit...

Страница 25: ...ration is allowed 1 Schedule reheat The domestic hot water tank is heated according to a schedule and between the scheduled heat up cycles reheat operation is allowed 2 Schedule only The domestic hot...

Страница 26: ...ing Additional zone Cooling Tank only available to installers INFORMATION To operate weather dependent correctly configure the setpoint of the main zone additional zone or tank See 7 3 4 Using weather...

Страница 27: ...Go to setpoint mode Set the setpoint mode to 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather dependent...

Страница 28: ...st protection However the room frost protection is only possible if C 2 Space heating cooling On Code Description 2 A C 05 External room thermostat type for the main zone 1 1 contact The used external...

Страница 29: ...temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor...

Страница 30: ...nted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit...

Страница 31: ...toring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In the menu go to Sensors 2 Select the temperature information 8 2...

Страница 32: ...sult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 9 Hand over to the user O...

Страница 33: ...ing diagram Indoor unit 3D120613B R2T R1T B1PW B1L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e S...

Страница 34: ...ireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wir...

Страница 35: ...ntinuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid For LV smartgrid For l...

Страница 36: ...ce Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ...4P644727 1 2021 02 Copyright 2021 Daikin 4P644727 1 0000000S Verantwortung f r Energie und Umwelt...

Отзывы: