6 Electrical installation

Installation manual

18

ETBH/9W

Daikin Altherma 3 H HT W

4P644727-1 – 2021.02

B

C

A

A

14

Q4L

13

C

B

13

14

X5M

X5M

3

Fix the cable with cable ties to the cable tie mountings.

NOTICE

Make  sure  to  select  and  install  the  safety  thermostat
according to the applicable legislation.

In  any  case,  to  prevent  unnecessary  tripping  of  the  safety
thermostat, we recommend the following:

▪ The safety thermostat is automatically resettable.

▪ The  safety  thermostat  has  a  maximum  temperature

variation rate of 2°C/min.

▪ There is a minimum distance of 2 m between the safety

thermostat  and  the  motorized  3‑way  valve  delivered
with the domestic hot water tank.

NOTICE

Error.

 If you remove the jumper (open circuit) but do NOT

connect the safety thermostat, stop error 8H-03 will occur.

6.3.11

To connect a Smart Grid

This topic describes 2 possible ways to connect the indoor unit to a
Smart Grid:

▪ In case of low voltage Smart Grid contacts

▪ In  case  of  high  voltage  Smart  Grid  contacts.  This  requires  the

installation of the Smart Grid relay kit (EKRELSG).

The 2 incoming Smart Grid contacts can activate the following Smart
Grid modes:

Smart Grid contact

Smart Grid operation mode

1

2

0

0

Free running

Smart Grid contact

Smart Grid operation mode

1

2

0

1

Forced off

1

0

Recommended on

1

1

Forced on

The use of a Smart Grid pulse meter is not mandatory:

If Smart Grid pulse meter is… Then [9.8.8] 

Limit setting kW

is…

Used

([9.A.2] 

Electricity meter 2

 ≠

None

)

Not applicable

Not used

([9.A.2] 

Electricity meter 2

 =

None

)

Applicable

In case of low voltage Smart Grid contacts

Wires (Smart Grid pulse meter): 0.5 mm²

Wires (low voltage Smart Grid contacts): 0.5 mm²

[9.8.4]=3 (

Benefit kWh power supply

 = 

Smart grid

)

[9.8.5] 

Smart grid operation mode

[9.8.6] 

Allow electrical heaters

[9.8.7] 

Enable room buffering

[9.8.8] 

Limit setting kW

The  wiring  of  the  Smart  Grid  in  case  of  low  voltage  contacts  is  as
follows:

14

13

S11S

6

5

S4S

4

3

X5M

S10S

10

9

a

2

1

a

Jumper (factory-mounted). If you also connect a safety
thermostat (Q4L), replace the jumper with the safety
thermostat wires.

S4S

Smart Grid pulse meter

1

/S10S

Low voltage Smart Grid contact 1

2

/S11S

Low voltage Smart Grid contact 2

1

Connect the wiring as follows:

B

C

A

A

X5M.4
X5M.3

S4S

X5M.10
X5M.9

S10S

X5M.6
X5M.5

S11S

2

1

Содержание Altherma 3 H HT W ETBH16EF6V

Страница 1: ...https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H HT W English Installation manual Daikin Altherma 3 H HT W ETBH16EF6V ETBH16EF9W ETBX16EF6V ETBX16EF9W...

Страница 2: ...yny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17 18 1...

Страница 3: ...21 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configuration wizard Main zone 24 7 2 6 Configuration wizard Additional zone 25 7 2 7 Configuration wizard Tank 25 7 3 Weather dependent curve 26 7...

Страница 4: ...trical device Possible consequence Electric shock or fire In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is possi...

Страница 5: ...heating operation 5 30 C Space cooling operation 5 35 C Domestic hot water production 5 35 C INFORMATION Cooling is only applicable in case of Reversible models Heating only models conversion kit EKHB...

Страница 6: ...1 2 3 2 5 Optional Remove the user interface panel NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 3 3 1 2 X14Y X1...

Страница 7: ...the applicable legislation 1 Connect a drain tube field supply to the drain pan connector as follows a a Drain pan connector It is recommended to use a tundish to collect the water 5 Piping installat...

Страница 8: ...at the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached a flow error 7H will be generated no heating or operation See the installer referen...

Страница 9: ...out of the freeze protection valves Freeze protection by glycol About freeze protection by glycol Adding glycol to the water lowers the freezing point of water WARNING Ethylene glycol is toxic WARNIN...

Страница 10: ...ning temperature of the freeze protection valve If lower freeze protection valves can open during cooling operation For more information see the installer reference guide 5 2 4 To fill the domestic ho...

Страница 11: ...1 External sensor Outdoor 9 B 2 Ext amb sensor offset 9 B 3 Averaging time Item Description Remote indoor sensor See Installation manual of the remote indoor sensor Addendum book for optional equipmen...

Страница 12: ...the wired room thermostat digital or analogue to the multi zoning base unit You need to connect the multi zoning base unit to the outdoor unit For cooling heating operation you also need to implement...

Страница 13: ...lation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model Make...

Страница 14: ...y SWB Switch box X6M Terminal field supply NOTICE Do NOT cut or remove the backup heater power supply cable 6 3 3 To connect the shut off valve INFORMATION Shut off valve usage example In case of one...

Страница 15: ...llustration below B C A A 6 5 4 3 S3S S2S C B X5M 5 6 3 4 X5M 3 Fix the cable with cable ties to the cable tie mountings 6 3 5 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump outpu...

Страница 16: ...r unit 45 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y2 X2M 1 2...

Страница 17: ...ital inputs cable to the appropriate terminals as shown in the illustration below B C A A 1 2 4 5 S6S S7S S8S S9S 3 C B A8P X801M a 5 4 3 2 1 a Installation of EKRP1AHTA is required 3 Fix the cable wi...

Страница 18: ...the Smart Grid relay kit EKRELSG The 2 incoming Smart Grid contacts can activate the following Smart Grid modes Smart Grid contact Smart Grid operation mode 1 2 0 0 Free running Smart Grid contact Sm...

Страница 19: ...Smart Grid relay kit installation STEP 2 Low voltage connections STEP 3 High voltage connections 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 a b Coil sides of relays c d C...

Страница 20: ...ser interface for the first time via the unit the configuration wizard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the...

Страница 21: ...g the dial 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0 1 2 3 4 Turn the left dial to select the second part of the setting 00 01 15 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 1 5 Turn the right dial to...

Страница 22: ...05 Thermistor type 0 Automatic 1 Type 1 5 8 6 0E Maximum tank temperature 60 C 75 C Emergency When the heat pump fails to operate the backup heater and or booster heater can serve as an emergency hea...

Страница 23: ...e system filled with glycol 0 No 1 Yes Booster heater capacity The capacity of the booster heater must be set for the energy metering and or power consumption control feature to work properly When mea...

Страница 24: ...m 55 C Variable 2 Radiator Maximum 70 C Fixed 10 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 This means that for a same leaving water temperature setpoint the average emit...

Страница 25: ...ration is allowed 1 Schedule reheat The domestic hot water tank is heated according to a schedule and between the scheduled heat up cycles reheat operation is allowed 2 Schedule only The domestic hot...

Страница 26: ...ing Additional zone Cooling Tank only available to installers INFORMATION To operate weather dependent correctly configure the setpoint of the main zone additional zone or tank See 7 3 4 Using weather...

Страница 27: ...Go to setpoint mode Set the setpoint mode to 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather dependent...

Страница 28: ...st protection However the room frost protection is only possible if C 2 Space heating cooling On Code Description 2 A C 05 External room thermostat type for the main zone 1 1 contact The used external...

Страница 29: ...temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor...

Страница 30: ...nted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit...

Страница 31: ...toring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In the menu go to Sensors 2 Select the temperature information 8 2...

Страница 32: ...sult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 9 Hand over to the user O...

Страница 33: ...ing diagram Indoor unit 3D120613B R2T R1T B1PW B1L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e S...

Страница 34: ...ireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wir...

Страница 35: ...ntinuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid For LV smartgrid For l...

Страница 36: ...ce Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ...4P644727 1 2021 02 Copyright 2021 Daikin 4P644727 1 0000000S Verantwortung f r Energie und Umwelt...

Отзывы: