5 Electrical installation
Installation manual
15
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598591-1A – 2019.12
5.2
Overview of electrical connections
for external and internal actuators
Item
Description
Power supply
See
"5.3 To connect the main power
15].
Remote outdoor
sensor
See
"5.4 To connect the remote outdoor
18].
Shut-off valve
See
"5.5 To connect the shut-off valve
Electricity meter
See
"5.6 To connect the electricity
Domestic hot water
pump
See
"5.7 To connect the domestic hot water
19].
Alarm output
See
Space cooling/heating
operation control
See
"5.9 To connect the space cooling/
21].
Changeover to
external heat source
control
See
"5.10 To connect the changeover to
22].
Power consumption
digital inputs
See
22].
Safety thermostat
See
"5.12 To connect the safety thermostat
Brine low pressure
switch
See
"5.13 To connect the brine low
Thermostat for passive
cooling
See
"5.14 To connect the thermostat for
24].
LAN adapter
connections
See
24].
Room thermostat
(wired or wireless)
See:
▪ Installation manual of the room
thermostat (wired or wireless)
▪ Addendum
book
for
optional
equipment
Wires for wired room thermostat: (3
for cooling/heating operation; 2 for
heating only operation)×0.75 mm²
Wires for wireless room thermostat: (5
for cooling/heating operation; 4 for
heating only operation)×0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9]
Control
▪ [2.A]
Thermostat type
For the additional zone:
▪ [3.A]
Thermostat type
▪ [3.9] (read-only)
Control
Item
Description
Heat pump convector
See:
▪ Installation manual of the heat
pump convectors
▪ Addendum
book
for
optional
equipment
Wires: 4×0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9]
Control
▪ [2.A]
Thermostat type
For the additional zone:
▪ [3.A]
Thermostat type
▪ [3.9] (read-only)
Control
Remote indoor sensor
See:
▪ Installation manual of the remote
indoor sensor
▪ Addendum
book
for
optional
equipment
Wires: 2×0.75 mm²
[9.B.1]=2 (
External sensor
=
Room
)
[1.7]
Room sensor offset
Current sensors
See the installation manual of the
current sensors.
Wires: 3×2. Use part of the cable
(40 m) delivered as accessory.
[9.9.1]=3 (
Power consumption
control
=
Current sensor
)
[9.9.E]
Current sensor offset
Human Comfort
Interface
See:
▪ Installation and operation manual of
the Human Comfort Interface
▪ Addendum
book
for
optional
equipment
Wires: 2×(0.75~1.25 mm²)
Maximum length: 500 m
[2.9]
Control
[1.6]
Room sensor offset
5.3
To connect the main power supply
Use one of the following layouts to connect the power supply (for
details of C1~C5, see below the table):
#
Layout
Open the unit
(a)
1 Single cable power supply (= combined
power supply)
C1
C1
: Power supply for the backup heater,
and the rest of the unit (1N~ or 3N~)
Not necessary
(connection to
factory-mounted
cable outside of the
unit)