6 Configuration

Installation manual

29

EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598591-1A – 2019.12

3

Turn the left dial to select the first part of the setting
and confirm by pressing the dial.

00
01
02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

0

1

2
3

4

Turn the left dial to select the second part of the
setting

00
01

15

02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

1

5

Turn the right dial to modify the value from 15 to 20.

00
01

20

02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

1

6

Press the left dial to confirm the new setting.

7

Press the center button to go back to the home
screen.

INFORMATION

When  you  change  the  overview  settings  and  you  go  back
to  the  home  screen,  the  user  interface  will  show  a  popup
screen and request to restart the system.

When  confirmed,  the  system  will  restart  and  recent
changes will be applied.

6.2

Configuration wizard

After first power ON of the system, the user interface will guide you
using  the  configuration  wizard.  This  way  you  can  set  the  most
important  initial  settings.  This  way  the  unit  will  be  able  to  run
properly.  Afterwards,  more  detailed  settings  can  be  done  via  the
menu structure if required.

6.2.1

Configuration wizard: Language

#

Code

Description

[7.1]

N/A

Language

6.2.2

Configuration wizard: Time and date

#

Code

Description

[7.2]

N/A

Set the local time and date

INFORMATION

By  default,  daylight  savings  time  is  enabled  and  clock
format  is  set  to  24  hours.  These  settings  can  be  changed
during  initial  configuration  or  via  the  menu  structure  [7.2]:

User settings

 > 

Time/date

.

6.2.3

Configuration wizard: System

Indoor unit type

The indoor unit type is displayed, but cannot be adjusted.

Backup heater type

The  backup  heater  is  adapted  to  be  connected  to  most  common
European electricity grids. The type of backup heater can be viewed
but not changed.

#

Code

Description

[9.3.1]

[E‑03]

▪ 4: 

9W

Domestic hot water

The following setting determines if the system can prepare domestic
hot water or not, and which tank is used. This setting is read only.

#

Code

Description

[9.2.1]

[E‑05]

(*)

[E‑06]

(*)

[E‑07]

(*)

No DHW

 (domestic hot water)

Integrated

The  backup  heater  will  also  be  used
for domestic hot water heating.

(*)

Menu structure setting [9.2.1] replaces the following 3
overview settings:

[E-05]

Can the system prepare domestic hot water?

[E-06]

Is a domestic hot water tank installed in the system?

[E-07]

What kind of domestic hot water tank is installed?

Emergency

When  the  heat  pump  fails  to  operate,  the  backup  heater  can  serve
as  an  emergency  heater.  It  then  takes  over  the  heat  load  either
automatically or by manual interaction.

▪ When 

Emergency

  is  set  to 

Automatic

  and  a  heat  pump  failure

occurs,  the  backup  heater  automatically  takes  over  the  domestic
hot water production and space heating.

▪ When 

Emergency

  is  set  to 

Manual

  and  a  heat  pump  failure

occurs, the domestic hot water heating and space heating stops.
To  manually  recover  it  via  the  user  interface,  go  to  the

Malfunctioning

  main  menu  screen  and  confirm  whether  the

backup heater can take over the heat load or not.

▪ Alternatively, when 

Emergency

 is set to:

auto  SH  reduced/DHW  on

,  space  heating  is  reduced  but

domestic hot water is still available.

auto  SH  reduced/DHW  off

,  space  heating  is  reduced  and

domestic hot water is NOT available.

auto  SH  normal/DHW  off

,  space  heating  operates  as

normally but domestic hot water is NOT available.

Similarly  as  in 

Manual

  mode,  the  unit  can  take  the  full  load  with

the  backup  heater  if  the  user  activates  this  via  the

Malfunctioning

 main menu screen.

To keep energy consumption low, we recommend to set 

Emergency

to 

auto SH reduced/DHW off

 if the house is unattended for longer

periods.

#

Code

Description

[9.5.1]

N/A

▪ 0: 

Manual

▪ 1: 

Automatic

▪ 2: 

auto SH reduced/DHW on

▪ 3: 

auto SH reduced/DHW off

▪ 4: 

auto SH normal/DHW off

INFORMATION

If  a  heat  pump  failure  occurs  and 

Emergency

  is  not  set  to

Automatic

  (setting  1),  the  room  frost  protection  function,

the  underfloor  heating  screed  dryout  function,  and  the
water pipe antifreeze function will remain active even if the
user does NOT confirm emergency operation.

Содержание Altherma 3 GEO EGSAH10UDA9W

Страница 1: ...Installation manual Daikin Altherma 3 GEO English Installation manual Daikin Altherma 3 GEO EGSAH06UDA9W EGSAH10UDA9W EGSAX06UDA9W EGSAX10UDA9W...

Страница 2: ...o le prescrizioni per de acordo com o previsto em 10 11 12 13 14 15 16 17 18 under iagttagelse af bestemmelserne i enligt villkoren i gitt i henhold til bestemmelsene i noudattaen m r yksi za dodr en...

Страница 3: ...staava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Страница 4: ...3 5 13 To connect the brine low pressure switch 23 5 14 To connect the thermostat for passive cooling 24 5 15 LAN adapter 24 5 15 1 About the LAN adapter 24 5 15 2 Overview of electrical connections 2...

Страница 5: ...to facilitate the installation and configuration of heating systems To access Heating Solutions Navigator registration to the Stand By Me platform is required For more information see https professio...

Страница 6: ...The appliance shall be stored in a room without continuously operating ignition sources example open flames an operating gas appliance or an operating electric heater 3 1 1 Installation site requirem...

Страница 7: ...nel 5 Installer switch box cover 6 Main switch box cover Open 1 Remove the top panel 5 T25 2 Remove the user interface panel Open the hinges at the top and slide the user interface panel upwards NOTIC...

Страница 8: ...r for servicing The removal of the module will significantly reduce the weight of the unit This makes the unit easier to handle and carry 1 Open the following see 3 2 1 To open the indoor unit 47 1 Us...

Страница 9: ...step 2 in 3 2 2 To remove the hydro module from the unit 48 2 Close the shut off valves by turning the lever handles 4 3 Remove the lower hydro module cover See step 5 in 3 2 2 To remove the hydro mod...

Страница 10: ...e brine circuit Do NOT use Zn coated piping as this may lead to excessive corrosion See also 4 2 4 To fill the brine circuit 411 NOTICE In case of plastic pipes make sure they are fully oxygen diffusi...

Страница 11: ...off valve below the vessel 5 Remove the safety valve on top of the vessel 6 Top up the vessel with brine until it is approximately 2 3 filled 7 Reconnect the safety valve 8 Open the shut off valve be...

Страница 12: ...hot water 412 a b c d b a Space heating cooling water OUT 22 mm b Space heating cooling water IN 22 mm and shut off valve with integrated filter accessory c Domestic hot water hot water OUT 22 mm d D...

Страница 13: ...G3 section 3 56 Table 03 and worked example 9 After completing the installation the installer has to fill out the warning label on the tank with indelible ink The warning label can be found on the un...

Страница 14: ...icular small leaks Small leaks can easily be overseen but can cause damage to the unit and surroundings over a longer period of time NOTICE After water piping installation check all connections for le...

Страница 15: ...ermostat 3 for cooling heating operation 2 for heating only operation 0 75 mm Wires for wireless room thermostat 5 for cooling heating operation 4 for heating only operation 0 75 mm Maximum running cu...

Страница 16: ...without separate normal kWh rate power supply b C1 C5 C2 X5M C1 Preferential kWh rate power supply for the backup heater 1N or 3N C2 Preferential kWh rate power supply contact C5 Preferential kWh rate...

Страница 17: ...GRY BLU YLW GRN a Factory mounted power supply cable b Field wiring F1B Overcurrent fuse field supply Recommended fuse for 1N 4 pole 32 A fuse C curve Recommended fuse for 3N 4 pole 16 A fuse C curve...

Страница 18: ...surement is important Remote outdoor sensor cable 40 m delivered as accessory 9 B 2 Ext amb sensor offset overview field setting 2 0B 9 B 3 Averaging time overview field setting 1 0A 1 Connect the ext...

Страница 19: ...tricity meter with transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Open the following see 3 2 1 To open the i...

Страница 20: ...anel 3 2 5 1 4 2 User interface panel 3 Front panel 4 Installer switch box cover 5 Main switch box cover 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration belo...

Страница 21: ...tch box cover 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below Make sure to put wires 2 and 3 between the installer switch box and main switch box in a...

Страница 22: ...X2X1 L N X2 X1 a a Installation of EKRP1HBAA is required 3 Fix the cable with cable ties to the cable tie mountings 5 11 To connect the power consumption digital inputs Wires 2 per input signal 0 75 m...

Страница 23: ...onfiguration the indoor unit will ignore the safety thermostat contact INFORMATION The preferential kWh rate power supply contact is connected to the same terminals X5M 9 10 as the safety thermostat T...

Страница 24: ...LAN adapter 5 15 1 About the LAN adapter The indoor unit contains an integrated LAN adapter model BRP069A61 which allows for App control of the heat pump system Integration of the heat pump system in...

Страница 25: ...y management system a2 230 V AC detection voltage b To electricity meter c Factory mounted cable to indoor unit P1 P2 d To router via the factory mounted Ethernet cable outside of the unit Connections...

Страница 26: ...Measurement type Depends on the installation 1N AC meter 3N AC meter balanced loads 3N AC meter unbalanced loads INFORMATION It is required that the electricity meter has a pulse output that can meas...

Страница 27: ...f high energy tariffs Open Closed Forced ON Energy buffering in the domestic hot water tank and or the room WITHOUT power limitation Closed Closed For more information see the installer reference guid...

Страница 28: ...ferent methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings v...

Страница 29: ...estic hot water or not and which tank is used This setting is read only Code Description 9 2 1 E 05 E 06 E 07 No DHW domestic hot water Integrated The backup heater will also be used for domestic hot...

Страница 30: ...towards a low temperature emitter Make sure you set the emitter types for the main zone 2 7 and for the additional zone 3 7 correctly in accordance with the connected emitter NOTICE An overpressure b...

Страница 31: ...tion 2 4 N A Setpoint mode Fixed WD heating fixed cooling Weather dependent When weather dependent operation is active low outdoor temperatures will result in warmer water and vice versa During weathe...

Страница 32: ...ensor on the North wall of the building If the outdoor temperature drops or rises the unit compensates instantly Thus the unit does not have to wait for feedback by the thermostat to increase or decre...

Страница 33: ...ing Domestic hot water X1 X2 Examples of outdoor ambient temperature Item Description Y1 Y2 Y3 Y4 Examples of desired tank temperature or leaving water temperature The icon corresponds to the heat emi...

Страница 34: ...2 A C 05 External room thermostat type for the main zone 1 1 contact The used external room thermostat can only send a thermo ON OFF condition There is no separation between heating or cooling demand...

Страница 35: ...Water pipe freeze prevention Benefit kWh power supply Power consumption control Energy metering Sensors Bivalent Alarm output Auto restart Power saving function Disable protections Overview field set...

Страница 36: ...Between the indoor unit and the valves if applicable Between the indoor unit and the room thermostat if applicable The system is properly earthed and the earth terminals are tightened The fuses or loc...

Страница 37: ...when ready 30 min To stop the test run manually 1 In the menu go to Stop test run 2 Select OK to confirm INFORMATION If the outdoor temperature is outside the range of operation the unit may NOT oper...

Страница 38: ...brine pump operation If a brine buffer vessel is part of the brine circuit or in case a horizontal brine loop is used it may be required to let the brine pump run continuously for 10 days after the s...

Страница 39: ...cal water conditions annual inspection of the integral line strainer pressure reducing valve cartridge and seating may be necessary c a b a Cartridge b Strainer c Calibration screw 1 Unscrew the plast...

Страница 40: ...e must be high enough Check if the water coming out of the relief valve is clean If it contains debris or dirt Open the valve until the discharged water does not contain debris or dirt anymore Flush a...

Страница 41: ...a pump to drain the tank via the access point 2 1 4 Tightening torques for installation Item Tightening torque Tube connection 30 N m Temperature and pressure relief valve 40 N m 9 4 To inspect the in...

Страница 42: ...m c1 Brine IN 28 mm c2 Brine OUT 28 mm d Shut off valve e Automatic air purge valve f Safety valve g Shut off valve h Manual air purge valve i Drain valve j Backup heater k Recirculation connection 3...

Страница 43: ...CB A3P On OFF thermostat A3P Heat pump convector A4P Digital I O PCB A4P Receiver PCB Wireless On OFF thermostat PC power circuit A6P Backup heater control PCB A7P Inverter PCB A8P Demand PCB A15P LAN...

Страница 44: ...ical meters Electricity meters For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat con...

Страница 45: ...ial kWh rate unit power supply installation Only with EKGSPOWCAB Compressor power supply 230 V earth Only with EKGSPOWCAB POWER SUPPLY FIELD SUPPLY OPTIONAL PART Only for EKCSENS INDOOR UNIT STANDARD...

Страница 46: ...parts Contact your local Daikin dealer Installed by name address tel No completion date TECHNICAL SPECIFICATIONS EN12897 2016 Maximum water supply pressure to pressure reducing valve 16 bar Operating...

Страница 47: ......

Страница 48: ...4P598591 1A 2019 12 Copyright 2019 Daikin 4P598591 1 A 00000007 Verantwortung f r Energie und Umwelt...

Отзывы: