Code
Range
Resolution
Default
S
0177 SAVED AMOUNT 2
—
1 = 1000
(Currency)
—
Energy saved in local currency in thousand currency units . Eg value 5 means 5000 currency units . See parameter 0176 SAVED AMOUNT 1 .
Local energy price is set with parameter 4502 ENERGY PRICE . Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time) .
See Group 45 ENERGY SAVING,
0178 SAVED CO
2
—
1 = 0 .1 tn
—
Reduction on carbon dioxide emissions in tn . CO
2
conversion factor is set with parameter 4507 CO
2
CONV FACTOR . Can be reset with parameter 4509 ENERGY RESET
(resets all energy calculators at the same time) . See Group 45 ENERGY SAVING,
.
Group 03: Actual Signals
This group monitors fieldbus communications.
Table 24: Group 03: Actual Signals
Code Description
Range
Resolution
Default
S
0301 FB CMD WORD 1
—
—
—
Read-only copy of the Fieldbus Command Word 1 .
• The fieldbus command is the principal means for controlling the drive from a fieldbus controller. The command consists of two Command Words. Bit-coded instructions in the
Command Words switch the drive between states .
• To control the drive, using the Command Words, an external location (EXT1 or EXT2) must be active and set to COMM . (See parameters 1001 and 1002 .)
• The control panel displays the word in hex . For example, all zeros and a 1 in Bit 0 displays as 0001 . All zeros and a 1 in BIt 15 displays as 8000 .
Bit #
0301, fb cmd word 1
0302, fb cmd word 2
Bit #
0301, fb cmd word 1
0302, fb cmd word 2
0
STOP
FBLOCAL_CTL
8
STPMODE_EM
Reserved
1
START
FBLOCAL_REF
9
STPMODE_C
Reserved
2
REVERSE
START_DISABLE1
10
RAMP_2
Reserved
3
LOCAL
START_DISABLE2
11
RAMP_OUT_0
REF_CONST
4
RESET
Reserved
12
RAMP_HOLD
REF_AVE
5
EXT2
Reserved
13
RAMP_IN_0
LINK_ON
6
RUN_DISABLE
Reserved
14
RREQ_LOCALLOC
REQ_STARTINH
7
STPMODE_R
Reserved
15
TORQLIM2
OFF_INTERLOCK
0302
FB CMD WORD 2
—
—
—
Read-only copy of the Fieldbus Command Word 2 .
.
0303
FB STS WORD 1
—
1
- hex
Read-only copy of the Status Word 1 .
• The drive sends status information to the fieldbus controller. The status consists of two Status Words.
Bit #
0303, sts cmd word 1
0304, fb sts word 2
Bit #
0303, sts cmd word 1
0304, fb sts word 2
0
READY
ALARM
8
LIMIT
Reserved
1
ENABLED
REQ_MAINT
9
SUPERVISION
Reserved
2
STARTED
DIRLOCK
10
REV_REF
REQ_CTL
3
RUNNING
LOCALLOCK
11
REV_ACT
REQ_REF1
4
ZERO_SPEED
CTL_MODE
12
PANEL_LOCAL
REQ_REF2
5
ACCELERATE
Reserved
13
FIELDBUS_LOCAL
REQ_REF2EXT
6
DECELERATE
Reserved
14
EXT2_ACT
ACK_STARTINH
7
AT_SETPOINT
Reserved
15
FAULT ACK_
OFF_ILCK
0304
FB STS WORD 2
—
1
- hex
Read-only copy of the Status Word 2 .
.
0305 FAULT WORD 1
—
1
0000 hex
Read-only copy of the Fault Word 1 .
• When a fault is active, the corresponding bit for the active fault is set in the Fault Words .
• Each fault has a dedicated bit allocated within Fault Words .
• See Fault Tracing,
for a description of the faults .
The control panel displays the word in hex . For example, all zeros and a 1 in Bit 0 displays a 0001 . All zeros and a 1 in Bit 15 displays as 8000 .
Bit #
0305,fault word 1
0306 fault word 2
0307 fault word 3
Bit #
0305, fault word 1
0306, fault word 2
0307, fault word 3
0
OVERCURRENT
UNDERLOAD
EFB 1
8
MOT OVERTEMP
Reserved
Reserved
1
DC OVERVOLT
THERM FAIL
EFB 2
9
PANEL LOSS
DRIVE ID
Reserved
2
DEV OVERTEMP
OPEX LINK
EFB 3
10
ID RUN FAIL
CONFIG FILE
System Error
3
SHORT CIRC
OPEX PWR
Incompatible software type
11
MOTOR STALL
SERIAL 1 ERR
System Error
4
Reserved
CURR MEAS
Reserved
12
Reserved
EFB CON FILE
System Error
5
DC UNDERVOLT
SUPPLY PHASE
Reserved
13
EXT FLT 1
FORCE TRIP
System Error
6
AI1 LOSS
ENCODER ERROR
Reserved
14
EXT FLT 2
MOTOR PHASE
Hardware Error
7
AI2 LOSS
OVERSPEED
Reserved
15
EARTH FAULT
OUTPUT WIRING
Param . Setting Fault
0306 FAULT WORD 2
-
1
0000 hex
A16-bit data word. For the possible causes and remedies and fieldbus equivalents, see Fault Tracing,
.
Bit #
Bit #
Bit #
0
Reserved
6
Reserved
11
SERIAL 1 ERR
1
THERM FAIL
7
OVERSPEED
12
EFB CON FILE
2 . . .3
Reserved
8
Reserved
13
FORCE TRIP
4
CURR MEAS
9
DRIVE ID
14
MOTOR PHASE
5
SUPPLY PHASE
10
CONFIG FILE
15
OUTP WIRING
a
CTual
s
Ignals
and
p
arameTers
www .DaikinApplied .com 35
OM 1190-1 • MD4 VFD