Group 01: Operating Data
This group contains drive operating data, including actual
signals . The drive sets the values for actual signals, based on
measurements or calculations . You cannot set these values .
Table 23: Group 01: Operating Data
Code
Description
Range
Resolution
Default
S
0101
SPEED & DIR
-30000 . . .30000
1 rpm
—
The calculated speed of the motor (rpm) & motor direction .
0102
SPEED
0 . . .30000 rpm
1 rpm
—
The calculated speed of the motor (rpm) .
0103
OUTPUT FREQ
0 .0 . . .500 .0 Hz
1Hz
—
The frequency (Hz) applied to the motor . (Also shown by default in OUTPUT display .)
0104
CURRENT
0 .0 . . .1 .5*I2N
0 .1 A
—
The motor current, as measured by the ACH550 . (Also shown by default in OUTPUT display .)
0105
TORQUE
-200%…
200%
0 .1%
—
Output torque . Calculated value of torque on motor shaft in % of motor nominal torque .
0106
POWER
-1 .5…1 .5*PN
0 .1 kW
—
The measured motor power in kW .
0107
DC BUS VOLTAGE
0 V…2 .5*VdN
1 V
—
The DC bus voltage in VDC, as measured by the ACH550 .
0109
OUTPUT VOLTAGE
0 V…2 .0*VdN
1 V
—
The voltage applied to the motor .
0110
DRIVE TEMP
0°C…150°C
1°C
—
The temperature of the drive power transistors in Centigrade .
0111
EXTERNAL REF 1
0 . . .30000 rpm
/ 0 . . .500 Hz
1 rpm / 0 .1 Hz
—
External reference, REF1, rpm or Hz - units determined by parameter 9904 .
0112
EXTERNAL REF 2
0% . . .100%
(torque:
0% . . .600%
0 .1%
—
External reference, REF2, in %
0113
CTRL LOCATION
0 . . .2
1
—
Active control location . Alternatives are:
0 = HAND
1 = EXT1
2 = EXT2
0114
RUN TIME(R)
0 . . .65,535 h
1 h
0 h
The drive’s accumulated running time in hours (h) .
• Can be reset by pressing UP and DOWN buttons simultaneously when in parameter set mode .
0115
KWH COUNTER (R)
0 . . .65,535
kWh
1 kWh
—
The drive’s accumulated power consumption in kilowatt hours .
• Can be reset by pressing UP and DOWN buttons simultaneously when in parameter set mode .
0116 APPL BLK OUTPUT
0 . . .100%
(torque:
0 . . .600%)
0 .1%
—
Application block output signal . Value is from either:
• PFA control, if PFA Control is active, or
• Parameter 0112 EXTERNAL REF 2 .
0120
AI1
0 . . .100%
0 .1%
—
Relative value of analog input 1 in % .
0121 AI2
0 . . .100%
0 .1%
—
Relative value of analog input 2 in % .
0124 AO1
0 . . .20 mA
0 .1 mA
—
The analog output 1 value in milliamperes .
0126
PID 1 OUTPUT
-1000 . . .1000%
0 .1%
—
The PID Controller 1 output value in % .
0127
PID 2 OUTPUT
-100 . . .100%
0 .1%
—
The PID Controller 2 output value in % .
0128 PID 1 SETPNT
—
—
—
The PID 1 controller setpoint signal .
• Units and scale defined by PID parameters 4006/4106 & 4007/4107.
0129 PID 2 SETPNT
—
—
—
The PID 2 controller setpoint signal .
• Units and scale defined by PID parameters 4206 & 4207.
0130 PID 1 FBK
—
—
—
The PID 1 controller feedback signal .
• Units and scale defined by PID parameters 4006/4106 & 4007/4107.
0131 PID 2 FBK
—
—
—
The PID 2 controller feedback signal .
• Units and scale defined by PID parameters 4206 & 4207.
a
CTual
s
Ignals
and
p
arameTers
www .DaikinApplied .com 33
OM 1190-1 • MD4 VFD